19 Two changes were made to the Plant in relation to the 098 valve in response to the incident. One was the immediate and temporary installation of an alarm to indicate the valve had opened. The other, somewhat later, and more enduring, was to introduce an automated process whereby, if toxic gases such as gas containing chlorine were being circulated in the system, the pressure relief point for the 098 valve would be reset automatically to 260 kPag. This "logic change" as it was called had been worked on before the incident as part of the development of what was called an Instrumented Protective System, or IPS, which was to change the way the Plant dealt with pressure build up beyond normal levels. Instead of the system, controlled by the DCS, dealing with overpressure through relief valves, and through pressure valves that vented to Snakes, the build-up to an overpressure problem would cause the IPS to shut down certain areas of the Plant. Development of the IPS was an involved process, however, because of the need to ensure, among other things, it worked in harmony with the DCS. The IPS, as at the trial before the Magistrate, had still not been implemented. However, the logic change was one that could be implemented earlier, and as I have indicated it was implemented, in response at least in part to the emission incident.