VICIn ForceRegulation
Public Health and Wellbeing Regulations 2019
70Routine service and testing obligations
Start here
Get a plain-English read of 70
Turn the raw legal text into a practical explanation grounded in Public Health and Wellbeing Regulations 2019.
70 Routine service and testing obligations
(1) A responsible person must ensure that a cooling tower system is serviced at least once each month to determine whether the cooling tower system is operating without defects.
(2) A responsible person must ensure that at least once each month a sample of recirculating water is taken and provided to a laboratory to determine the heterotrophic colony count of the recirculating water.
(3) A responsible person must ensure that at least once every 3 months a sample of recirculating water is taken and provided to a laboratory to test for Legionella.