69Disinfection, cleaning and re-disinfection of cooling tower system
Start here
Get a plain-English read of 69
Turn the raw legal text into a practical explanation grounded in Public Health and Wellbeing Regulations 2019.
69 Disinfection, cleaning and re-disinfection of cooling tower system
Immediately prior to a cooling tower system being put into operation for the first time, or following any shut down period of greater than one month and at intervals not exceeding 6 months, a responsible person must ensure that—
(a) a chlorine-compatible bio-dispersant is added to the recirculating water; and
(b) the recirculating water is disinfected; and
(c) the interior of each cooling tower in the cooling tower system is cleaned; and
(d) the recirculating water is re-disinfected.