[2025] NSWCATAP 194
General information, not legal advice.
NCAT Appeal Panel
2025-08-13
P Durack, Senior MemberN Kennedy, Senior Member
Original judgment source is linked above.
The Tribunal erred (at [126]-[134]) in its construction of Clause 3.3 of Australian Standard 3740-2011 (sic) ("AAS 3740"), in finding that Clause 3.3 required, in the general bathroom area, a minimum fall to any installed waste of 1:100.
Particular
1.1. Clause 3.3 requires a fall of 1:100 in any wet area where such a fall "is required";
1.2. Clause 3.3 does not of itself require a fall in any wet area;
1.3. AAS 3740 does not otherwise require a fall to the wastes in the general bathroom area (cf. an enclosed shower area).
3.3 FALLS IN FLOOR FINISHES
Where required, falls in floor finishes shall allow all surface water to drain without ponding except for residual water remaining due to surface tension.
For general bathroom floor area, the minimum fall to the waste shall be 1:100.
NOTES:
1 For information on falls in the floor finishes, see Appendix B.
2 For information on the laying of tiles to enable them to drain without retaining water, see AS 3958.1.
3.4 SHOWER FLOORS
Falls in shower floors shall be sufficient to prevent-
(a) surface water being retained on the shower floor (except for residual water remaining due to surface tension); and
(b) water from discharging outside the shower area.
For shower areas with a vertical separation between the shower area and the wet area, such as a shower screen, hob, step-down or water stop, the fall to the waste shall be 1:100.
As a minimum for other shower areas, the fall shall be a minimum of 1:80.
3.11 REQUIRED FLOOR WASTES FOR WET AREA FLOORS
Where a floor waste is required, floor finish shall be constructed so that water flows to the waste without water being retained on the finished surface with the exception of residual water remaining due to surface tension
NOTE: For additional information on floor gradients, see Appendix B.
An area within the building supplied with water from a water supply system, which includes bathrooms, showers, laundries and sanitary compartments and excludes kitchens, bar areas, kitchenettes domestic food and beverage preparation areas.
As identified above, the issue with the bathrooms (with the exception of ensuite two which has two additional alleged defects) concerns grading to floor wastes. The experts agree that the floor wastes in question are not required by the NCC, as they are floor wastes that are installed in the main bathroom area, and separate to the floor wastes installed in the shower areas.
Have you ever wondered whether the floor surrounding a floor waste is required by the NCC to be graded to that floor waste in all circumstances?
While not likely to be a dinner party conversation topic, this question has been occupying the minds of some NCC users. So earlier this year at a joint meeting of the ABCB's Building Codes Committee and Plumbing Code Committee considered it.
When are floor wastes required?
Floor wastes are only required by the Deemed-to Satisfy Provisions of the NCC in prescribed situations:
In the above situations, the floor is required by the NCC to be graded to the floor waste to prevent water overflow from penetrating or other occupancies public spaces in the same building.
......
Floor wastes not required by the NCC
Floor wastes may also be installed even though they are not required by the NCC, for example, outside the shower area in a residential bathroom. As there is no requirement in the NCC to control overflows in these circumstances, it follows that there is also no requirement in the NCC to drain the floor to these floor wastes.
Of course, even though the NCC may not require floors to be graded to some floor wastes, there is nothing that prevents this being done if desired, but in those circumstances it should be understood it is not a regulated requirement under the NCC.
13. Reading AS 3470 as a whole therefore, the requirements for the grading of the floor in a bathroom area are as follows:
13.1 Clause 3.4 requires the installation of a floor waste in the shower area;
13.2 Clause 3.11 applies to all wet areas where a floor waste is required, and therefore applies to shower areas;
13.3 Clause 3.11 requires falls in all wet areas to which it applies, with the consequences that shower areas must have falls;
13.4 Clause 3.3 applies to all wet areas where falls are required, therefore applies to shower area;
13.5 Clause 3.3 requires the floors where falls are required to be "constructed so that water flows to the waste without water being retained on the finished surface with the exception of residual water remaining due to surface tension", with the result that shower area floors have to be constructed in that manner; and
13.6 As AS 3470 does not otherwise require floor wastes or falls to be installed in the general bathroom area, clauses 3.3 and 3.11 do not apply to that area.
14 That construction is entirely in keeping with the commentary published by the ABCB.
5. In that context, publications by the Board, whose responsibility it is to produce the Standard, which articulate in definitive terms what those requirements are where there is ambiguity, is highly relevant to the proper construction of the Standard. In this regard, the Appeal Panel can take into account that the Board must have an educative function for the profession, as well as an obligation to articulate what the relevant requirements are for the public at large.
6. The Connect article is plainly published for the purposes of those functions.
(1) An extension of time until 12 March 2025 is granted in which to lodge the appeal.
(2) The appellant's application for leave to adduce new evidence on the appeal and for that purpose to adjourn the hearing of the appeal is refused.
(3) The appeal is dismissed
I hereby certify that this is a true and accurate record of the reasons for decision of the Civil and Administrative Tribunal of New South Wales.
Southern Pacific Builders Pty Limited
Kelly [2025] NSWCATAP 194;