Water Fluoridation Regulation 2020
sec.8Using automatic fluoride dosing equipment for fluoride compounds
Start here
Get a plain-English read of sec.8
Turn the raw legal text into a practical explanation grounded in Water Fluoridation Regulation 2020.
sec.8 Using automatic fluoride dosing equipment for fluoride compounds
The public potable water supplier must use automatic fluoride dosing equipment that— has the rate of feed of the fluoride compound paced to the flow of water into the public potable water supply; and has at least 2 devices that independently monitor the flow of the water, at least 1 of which measures the rate of flow of the water; and is designed in a way that ensures if part of the equipment fails, the fluoride compound is not added to the water supply.
- (a) has the rate of feed of the fluoride compound paced to the flow of water into the public potable water supply; and
- (b) has at least 2 devices that independently monitor the flow of the water, at least 1 of which measures the rate of flow of the water; and
- (c) is designed in a way that ensures if part of the equipment fails, the fluoride compound is not added to the water supply.