Residential Tenancy (Smoke Alarms) Regulations 2022
12Placement of smoke alarms in Class 4 building
Start here
Get a plain-English read of 12
Turn the raw legal text into a practical explanation grounded in Residential Tenancy (Smoke Alarms) Regulations 2022.
12 Placement of smoke alarms in Class 4 building
Smoke alarms, that are required to be in place for the purposes of section 36C of the Act, in relation to tenanted premises that are a Class 4 building located within a Class 5, 6, 7, 8 or 9 building, must be installed on or near the ceiling –
(a) if any storey of the premises contains a bedroom –
(i) in the premises, in every corridor, or hallway, associated with a bedroom in that storey; and
(ii) if there is no corridor, or hallway, that is associated with a bedroom in that storey, between that part of the premises containing the bedroom and the remainder of the premises; and
(b) in egress paths in any other storey of the premises that does not contain a bedroom.