7 Temperature conditions—H1, H2, H3 and T1
H1 means the following temperature conditions:
(b) 7 ˚C dry-bulb and 6 ˚C wet-bulb outside.
H2 means the following temperature conditions:
(b) 2 ˚C dry-bulb and 1 ˚C wet-bulb outside.
H3 means the following temperature conditions:
(b) -7 ˚C dry-bulb and -8 ˚C wet-bulb outside.
T1 means the following temperature conditions:
(a) 27 C dry‑bulb and 19 C wet‑bulb inside;
(b) 35 C dry‑bulb and 24 C wet‑bulb outside.