Greenhouse and Energy Minimum Standards (Air Conditioners up to 65kW) Determination 2019
40Product performance—average true power factor
Start here
Get a plain-English read of 40
Turn the raw legal text into a practical explanation grounded in Greenhouse and Energy Minimum Standards (Air Conditioners up to 65kW) Determination 2019.
40 Product performance—average true power factor
(1) The specified product performance requirements in relation to tested average true power factor are as follows:
(a) air conditioners with a rated power input of less than or equal to 850W must have:
(i) a tested input that does not exceed 1000VA; and
(ii) a tested average true power factor greater than or equal to 0.5;
(b) air conditioners with a rated power input of greater than 850W and a rated capacity of less than or equal to 15kW must have a tested average true power factor greater than or equal to 0.85;
(c) air conditioners with a rated capacity of greater than 15kW and less than or equal to 20kW must have a tested average true power factor greater than or equal to:
View image in the official source
(d) air conditioners with a rated capacity of greater than 20kW must have a tested average true power factor greater than or equal to 0.80.
(2) In this section:
rated capacity means:
(a) rated standard cooling full capacity; or
(b) for a heating‑only product—rated standard heating full capacity.
(3) In this section:
average true power factor means the average ratio over a given time of the tested kilowatt hours (kWh) divided by the tested kilo volt ampere hours (kVAh).
Note: It is not the average of regular instantaneous power factor measurements.