Electricity Safety (General) Regulations 2019
611Minimum distances between materials, protected aerial lines and protected infrastructure
Start here
Get a plain-English read of 611
Turn the raw legal text into a practical explanation grounded in Electricity Safety (General) Regulations 2019.
611 Minimum distances between materials, protected aerial lines and protected infrastructure
(1) A person must not place any flammable material or allow flammable material to remain closer than 3000 millimetres in any direction from a wall or fence of any substation or switch yard that forms part of protected infrastructure.
(2) A person must not place any flammable material or allow flammable material to remain vertically below a protected aerial line.
(3) A person must not place any flammable material or allow flammable material to remain so that, at any time, the flammable material is closer than the relevant horizontal distance specified in Row A of Table 611 from any point of the vertical projection below a protected aerial line.
(4) A person must not place any material or allow any material to remain so that, at any time, the material is closer than the relevant horizontal distance marked "h" specified in Row B of Table 611 from any point of the vertical projection below a protected aerial line unless the material is no closer vertically below the line than the vertical distance marked "v" specified in Row B of Table 611.
Table 611—Minimum distances from materials to protected aerial lines
- Column 1 Column 2 Column 3 Column 4 Column 5 Column 6 Column 7
- Aerial lines Nominal voltage ("U")
- Type of material U ≤ 1500V d.c. traction conductor 1 kV a.c. or 1500V d.c. < U ≤ 33 kV 33 kV< U ≤ 132 kV 132 kV< U ≤ 275 kV 275 kV< U ≤ 330 kV 330 kV< U ≤ 500 kV
- Row AFlammable material Horizontal distance 3000 mm 3000 mm 3000 mm 4600 mm 5500 mm 6400 mm
- Row BAny other material "h" 1500 mm 2100 mm 3000 mm 4500 mm 5500 mm 6400 mm
- "v" 3700 mm 4600 mm 4600 mm 6800 mm 8000 mm 9800 mm