ELECTRICAL SAFETY REGULATIONS 2024
76Preliminary steps
Start here
Get a plain-English read of 76
Turn the raw legal text into a practical explanation grounded in ELECTRICAL SAFETY REGULATIONS 2024.
76 Preliminary steps (1) Before electrical work is performed, other than electric line work, the person must do all that is reasonably practicable to ensure: (a) the person consults with the person with management or control of the workplace; and (b) a risk assessment is conducted in relation to the proposed electrical work and records the results of the assessment; and (c) the area where the electrical work is to be performed is clear of obstructions to allow easy access and exit by the worker who will perform the electrical work; and (d) the point at which the electrical equipment can be disconnected or isolated from its electricity supply is: (i) clearly marked or labelled; and (ii) clear of obstructions so as to allow easy access and exit by the worker who will perform the electrical work; and (iii) capable of being used quickly. (2) Electrical work on energised electrical equipment is exempt from subregulation (1)(d) if: (a) the work is performed on the supply side of the main switch on the main switchboard for the equipment; and
Electrical Safety Regulations 2024 47 (b) the point at which the equipment can be disconnected from its electricity supply is not reasonably accessible from the workplace.