141Signage
Start here
Get a plain-English read of 141
Turn the raw legal text into a practical explanation grounded in ELECTRICAL SAFETY REGULATIONS 2024.
141 Signage (1) A person installing power conversion equipment for a photovoltaic array located indoors in a building used for commercial purposes must mark the location of the equipment in accordance with this (2) The location of the power conversion equipment must be marked: (a) at the main switchboard; and (b) at the sub-board; and (c) on the fire indicator panel block plan (where applicable). (3) For subregulation (1), the wording of either of the following is sufficient: INVERTER LOCATIONS INVERTER LOCATION Battery: ___________ or __________________ Solar: ____________ __________________