Disability (Access to Premises — Buildings) Standards 2010
F3.9 Door and door controlsF3.9 Door and door controls
Start here
Get a plain-English read of F3.9 Door and door controls
Turn the raw legal text into a practical explanation grounded in Disability (Access to Premises — Buildings) Standards 2010.
F3.9 Door and door controls
The entrance door and associated door controls must be automated and must comply with the following:
(a) the threshold must incorporate a smooth transition without a step or lip;
(b) the minimum clear opening width must be:
(i) 1,100 mm in locations where beach wheelchairs are likely to be used; or
(ii) 950 mm in all other locations;
(c) the doorway must achieve a luminance contrast of at least 30% between:
(i) the door leaf and door jamb; or
(ii) the door leaf and adjacent wall; or
(iii) the architraves (where used) and adjacent wall; or
(iv) the door leaf and architrave (where used); or
(v) the door jamb and adjacent wall;
(d) the operation of the door must be calibrated such that:
(i) it has a gentle opening and closing movement; and
(ii) there is sufficient dwell time for a user to safely travel through the doorway;
(e) the door must be fitted with a fail-safe opening mechanism that opens the door if an obstruction is detected during its closing movement;
(f) door controls must be located internally and externally:
(i) between 900 mm and 1,200 mm above finished floor level; and
(ii) not less than 500 mm from any internal corner;
(g) door control buttons must:
(i) have a minimum diameter of 25 mm; and
(ii) be proud of the surrounding surface; and
(iii) activate the door operation before the button becomes level with the surrounding surface; and
(iv) be of a contrasting colour to the surrounding plate;
(h) the surrounding plates of both internal and external door controls must include the words “Push to Open”;
(i) the following indicator lights must be provided:
(i) “Occupied” and “Vacant” on the external plate;
(ii) “Locked” and “Unlocked” on the internal plate;
(j) braille and tactile signage complying with Part D4 must identify the door controls.