F3.7 Change tableF3.7 Change table
Start here
Get a plain-English read of F3.7 Change table
Turn the raw legal text into a practical explanation grounded in Disability (Access to Premises — Buildings) Standards 2010.
F3.7 Change table
(1) The change table must be:
(a) permanently installed, with one of the long edges up against a wall and with a retractable safety rail on the opposite side; and
(b) motorised for the purposes of height adjustment; and
(c) height adjustable between 450 mm and 900 mm above finished floor level; and
(d) not less than 700 mm wide; and
(e) not less than 1,800 mm long.
(2) The change table must have a maximum safe working load of not less than 180 kg, including when raising or lowering the table.
(3) The change table must not encroach on any required circulation space.
(4) A dispenser for sanitary wipes must be provided.
(5) A shelf not less than 400 mm long and 150 mm wide must be provided.