Automatic Fire Sprinkler System...throughout the Basement carpark in accordance with AS2118.1...[and] throughout the remainder of the building in accordance with AS2118.4', and 'Fire Hydrant coverage ...provided in accordance with the BCA [deemed to satisfy] Provisions or to satisfy [FRV] requirements.
a) Towns mains test failed to achieve 20l/s @50kPa. Independent Certifier recorded 0 kPa at pump inlet during pump appliance test. > > b) Sprinkler flow test did not pass duty demands. > > c) Insufficient clearance at front of Fire Indicator Panel.
confirmation from a suitably qualified expert as to whether the sprinkler system complies in all aspects if the fire hydrant demand on the water supply is ignored.
Based on the system requirements and the pressure and flow data (physical testing) obtained during commissioning, there is suitable flow for the townhouse sprinkler system however insufficient pressure and flow for the carpark system.
(a) it may be permissible to omit the fire hydrant water supply demand required in accordance with the BCA and/or requirements of FRV from the calculation and testing of the water supply characteristics which determine the hydraulic performance of the fire sprinkler systems served directly from the town mains; and
(b) it may be possible to re-design the hydraulic performance of the fire sprinkler system serving the carpark to comply with AS 2118.4-2012, Clause 4.3.4 in lieu of compliance with AS 2118.1 Ordinary Hazard 2 for the carpark area as currently proposed in the FER.
�Riversdale Capitol Group Pty Ltd
Fire Rescue Commissioner [2025] VBAB 65;