[2025] QCAT 175
General information, not legal advice.
Queensland Civil and Administrative Tribunal
2025-04-29
Original judgment source is linked above.
PROFESSIONS AND TRADES - BUILDERS -STATUTORY POWER TO REQUIRE RECTIFICATION OF DEFECTIVE OR INCOMPLETE BUILDING WORK - where applicant seeks to review decisions by QBCC to issue directions to rectify - where the applicant sought review of a decision by QBCC to issue a direction to rectify defective building work - whether unfair to issue a direction to rectify
S E Seefeld of counsel instructed by HWL Ebsworth Lawyers
(a) Was the work "building work"?
(b) Was the building work "defective" or incomplete?
(c) Was the building work carried out by the builder?
(d) Is it unfair to direct the builder to rectify the building work in all the circumstances?'
(a) Complaint items 1, 2, 4, 8, 9, 10, 14, 15, 16, 17, 22, 24, 25, 29, 32 and 33 were non-structural defective work in need of rectification ('Defective Work'); and
(b) Complaint items 3, 5, 6, 7, 11, 12, 18, 19, 20, 21, 23, 26, 27, 28, 31 and 34 were not defective work in need of rectification ('Non-defective Work').[8]
Item 34 - Structural concerns: We do not feel that the engineering was taken into consideration at the required level. We feel that an engineer is required to make a decision on the works being sufficient structurally or not. We do not understand where the structural alteration being less than 20% of the entire house structure comes from. There were 4 walls removed from the internal of the house as well as a downstairs laundry structure raised to the house height to become the ensuite and walk in robe, removal of parts of the wall adjacent to the original laundry to create entrances to the walk-in robe and an addition to the study wall.
The referred to 7.2.4.3 advises that the ceiling joists should be fixed to the 'hanging beam' using timber cleats, steel strapping, steel celling joist hangers or equivalent approved fasteners. Each alternate connection shall be fixed to opposite sides of the hanging beam. This not addressed in the what the inspector found at time of inspection part of the report and was only addressed in the photos after with no confirmation if the measurement were to the required Australian Standard.
Given the fixing of the beam was raised as a concern in our provided report, this should have been addressed specifically.
We provided both a report from a qualified builder and a retired engineer that confirmed several questions that have not been answered and raised concerns regarding the point load from the beam onto the wall structure and onto the stumps. We requested our builder to engage an engineer for a full structural assessment. The engineer hired, completed a certification of the beam only. They are unwilling to complete a form 15, this causes us concern.
As the previously provided paperwork is insufficient to have all of our concerns address, we have engaged the services of NJA Engineering who are attending our home on Tuesday 28 September 2021 and will have the report to us shortly after. Given the current business of the construction Industry we were unable to find an engineer with capacity sooner that was able to complete the works. We request that we are able to submit the report. once received as consideration of the structural issues.
17. The installation of the gypsum plasterboard on the wall between the master bedroom and the living room does not comply with AS/NZS 2589.1:1997 Clause 7.1.4(b) in that a deviation in the wall exceeds 4mm measured over a 1.8m span along the wall resulting in an unsightly wall finish. Pertains to item 11 of the QBCC Complaint; and
18. The installation of the hanging beam (250PFC) position over the living room does not comply with AS 1684.2:2010 in that the end supports of the hanging beam are not held into position using the methods set out in clause 7.2.5.2 and the ceiling joists have not been fixed in accordance with the methods as set out in clause 7.2.4.3 resulting in a detrimental effect of the structural stability of the beam and ceiling joists. Pertains to item 34 of the QBCC Complaint Form.
Item number 11 of your complaint form has been investigated and there was insufficient evidence to reveal any obvious defective construction practices by Gerard Lazarus at the time of inspection. Therefore, the QBCC is unable to provide you with any further assistance with the resolution of the item.
17. The installation of the gypsum plasterboard on the wall between the master bedroom and the living room does not comply with AS/NZS 2589.1:1997 Clause 7.1.4(b) in that a deviation in the wall exceeds 4mm measured over a 1.8m span along the wall resulting in an unsightly wall finish. Pertains to item 11 of the QBCC Complaint;
(a) By placing the level on high spots either side of the deviation and measuring the distance from the straight edge to the deviation; or
(b) By evenly supporting the straightedge on either side of a raised section in a wall and measuring the deviation from the wall at either end of the straightedge.
Clause 7.2.5.1 of AS 1684.2 states:
Hanging beams shall support ceiling joists and the attached ceiling material only. Hanging beams are usually at right angles to the ceiling joist and are located directly above them.
(a) A hanging beam supports ceiling joists and attached ceiling material only. In this circumstance, it supported the original, now obsolete, roof rafters which remained in place as well and ends of the ceiling joists; and
(b) A hanging beam is located directly above the ceiling joists.
c) The 250 PFC appears to be straight and not deforming under static load however a structural calculation needs to be done to confirm its sizing under dead and live load conditions
d) The 250 PFC is not bolted to the support columns, nor is it restrained and can potentially rotate (fall flat onto its flanges) due to the fact that it is not restrained and the location of the rafter loading on the top flange and truss loading onto the bottom flange causing an unbalanced load situation. and hence rotation.
e) The original cottage rafters and the lean to extension rafters simply sit on to the 250PFC and are not attached in any way. Uplift from wind loads can potentially lift sections of the roof off the 250 PFC.
f) The 250 PFC is only partially supported by the column at the rear of the house and is not physically attached nor has full bearing support.
(a) AS 1684.2:2001 - Residential timber-framed construction, Part 2: Non-cyclonic areas, require that timber structures are designed to resist imposed stresses, including uplift by way of tie-downs which provide uplift resistance.
(b) In its performance of the work the Builder has replaced the pre-existing roof beam, which would have provided uplift resistance together with at least nominal connection to the ceiling joists, with a 250 PFC beam ('beam').
(i) Which does not have formal framing at either end, with no restraint to prevent movement of the beam; and
(ii) No tie-down studs to support the beam post were observed.
(c) In order for the ceiling joist and rafters to have been adequately fixed to the beam, an uplift connection would have been required on both ends of the beam;
(d) Consequently, the Builder's installation of the beam does not comply with the tie-down requirements of AS 1684.2:2001 - Residential timber-framed construction, Part 2: Non-cyclonic areas.
Lazarus
Queensland Building and Construction Commission [2025] QCAT 175