Yarra Planning Scheme; Application pursuant to Section 79 of the Planning and Environment Act 1987; Business 1 Zone; Heritage Overlay (HO43); Noise; Patron numbers; Hours of operation.
Kamari & Associates Pty Ltd v Yarra CC [2008] VCAT 1968
in accordance with the endorsed plans and subject to the permit conditions set out in the Appendix.
Mr Lloyd Bryant, Barrister. He called written and oral evidence from Mr Geoffrey Barnes, Acoustical Consultant and Mr Robert Steane, Liquor Consultant.
Mr Damien Hancox, Traffic Engineer of TTM Consulting Pty Ltd prepared a witness statement but with the agreement of parties was not called to give oral evidence or answer questions.
(a) As shown on Drawing TP-04 the wall separating the bar area from the toilet and store/office is to be acoustically treated.
(b) This wall must consist of a timber or metal stud frame and be faced on each side with minimum one layer of 16mm thickness plasterboard. The cavity must incorporate acoustic insulation minimum 100mm thickness, such as Tontine Acoustisorb I or equivalent. The wall will extend from the floor and be sealed to the ceiling with a non-setting mastic sealer.
(c) New rear external door to be a flush panel 45mm - 50mm thickness timber door clad with steel sheeting. The door is to have a sound rating of Rw - 40dB(A). A suitable door with matching frame and acoustic seals such as Raven RP-24 and RP-38 perimeter seals or equivalent. The door should also be fitted with a heavy duty door closer. The existing door & window above to be bricked up.
(d) Toilet/rear passageway door to be a flush panel nominally 45mm thickness solid core door having a sound rating of minimum Rw - 30 dB(A). A suitable door with matching frame and acoustic seals such as Raven RP-24 and RP-3 8 perimeter seals or equivalent. The door should also be fined with a heavy duty door closer.
(e) Bar area/toilet access door also to be a flush panel nominally 45mm thickness solid core door having a sound rating of minimum Rw - 30 dB(A). A suitable door with matching frame and acoustic seals such as Raven RP-24 and RP-3 8 perimeter seals or equivalent. It may be fitted with a small courtesy window incorporating one layer of minimum 8mm safety glass. The door should also be fitted with a heavy duty door closer.
(f) Front entry doors - a pair of glazed double door leaves fitted with heavy duty door leaves. These doors will normally be closed except for ingress and egress purposes.
(g) The split air conditioning system external condenser unit must have a sound power rating not exceeding 65 dB(A), selected and positioned to ensure the sound level at the boundary does not exceed 47 dB(A) when operated during the night period.
(h) Exhaust fans and kitchen fans must not generate sound levels that exceed 47dB(A) at the boundary when operated during the night period.
(i) External refrigeration units must be located at ground level or otherwise screened and must not generate sound levels that exceed 47 dB(A) at the boundary when operated during the night period.
[1] In accordance with Section 4 (2) (d) of the Victorian Civil and Administrative Tribunal Act 1998 a failure to make a decision is deemed to be a decision to refuse the application.