2025-04-17
Applicant Mr J, Party Mr P
Original judgment source is linked above.
(a) Application 2 is withdrawn.
(b) Application 3 was amended to permit the requirements under cl S43C9 to not apply to the Class 9 building.
(c) Application 5 was amended to permit an emergency power supply to provide support for 6 hours in total, to support the operation of the services under cl S43C12, instead of 4 hours before and 2 hours after the passing of the fire front during a bushfire event as required under cl S43C12 of Spec 43.
(2) An application may be made to the Building Appeals Board for a determination that a provision of the building regulations -
(a) does not apply; or
(b) applies with the modifications or variations specified in the application -
to a building or land specified in the application.
162 - Special powers - modification of regulations
(2) The Building Appeals Board must not determine that a provision of the building regulations does not apply to a building or land unless satisfied that, in the particular circumstances, the provision is inappropriate.
(3) The Building Appeals Board must not determine that a provision of the building regulations applies to a building or land in a modified or varied form unless satisfied that to do so is reasonable and not detrimental to the public interest.
A non-combustible pathway directly adjacent to the building and not less than 1.5 m wide must be provided around the perimeter of the building.
An external area designed to hold people unable to be safely accommodated within the building, that may be exposed to radiant heat flux from a fire front during a bushfire event, must not be exposed to an incident radiant heat flux from the fire front exceeding 1 kW/m2 above background solar radiant heat flux.
To maintain internal tenability throughout the duration of occupancy during a bushfire event, the building must comply with the following:
(a) An air handling system must be provided that is capable of -
- being adjusted for full recycling of internal air for a period of not less than 4 hours to avoid the introduction of smoke into the building; and
- maintaining an internal air temperature of not more than 25°C.
(b) The building envelope must be designed such that if an air handling system required by (a) fails, then -
- internal air temperatures can be maintained below 39°C; and
- internal surface temperatures can be maintained below 60°C.
(c) If the building is divided into separate compartments then, for the purposes of (a), each compartment must have a separate air handling system.
(d) Each air handling system required by (a) must be designed to account for the activation of smoke detectors from low concentrations of smoke from external sources, so as to ensure that air-conditioning and other essential systems remain operational.
The building envelope must be constructed in accordance with AS 3959 - BAL 19 or greater, except that where the use of combustible materials is permitted by AS 3959, they are not to be used unless permitted by C2D10(4), (5) or (6).
(1) Emergency power must be provided to support, for not less than 4 hours before and 2 hours after the passing of the fire front during a bushfire event, the ongoing operation of -
(2) Manual control for emergency back-up power supply must be provided to facilitate manual intervention where the power supply fails or runs out.
Signage must be provided to warn building occupants against storing combustible materials under or adjacent to the building.
(a) The external refuge is maintained in a state free of non-excludable vegetation and overgrowth of excludable vegetation; and
(b) The external refuge area remains unobstructed and is not built over wholly or in part.
Additional to what has been provided, the applicant should also nominate the full external wall construction system and roof/ceiling construction system, inclusive of the internal lining elements, for consideration with this application item.
(1) Emergency power must be provided to support, for not less than 4 hours before and 2 hours after the passing of the fire front during a bushfire event, the ongoing operation of -
(a) air handling systems to maintain internal tenability; and
(b) any pumps for fire-fighting; and
(c) any emergency lighting and exit signs; and
(d) any other emergency equipment listed in C3D14(6) and required to be provided.
(2) Manual control for emergency back-up power supply must be provided to facilitate manual intervention where the power supply fails or runs out.
(a) safeguard occupants from injury from the effects of a bushfire; and
(b) protect buildings from the effects of a bushfire; and
(c) facilitate temporary shelter for building occupants who may be unable to readily evacuate the building prior to a bushfire.
Accordingly, we will have regard to this objective in interpreting the clS43C12.
Signage must be provided to warn building occupants against storing combustible materials under or adjacent to the building.
WARNING - DO NOT STORE COMBUSTIBLE MATERIALS UNDER OR ADJACENT TO BUILDING