austlii:vic/VBAB/2025/95
General information, not legal advice.
VBAB
2025-07-01
Original judgment source is linked above.


The eastern wall of the Building abuts Fleming Place as shown below -
Fleming Place is only a road at its northern end abutting Little Collins Street.



(a) Contrary to reg 10 of the Building Regulations 2018 (the Regulations), ACP had been used as a component of the external walls of the Building in contravention of Performance Requirements CP2 and CP4; and
(b) The Building is a danger to the life, safety, or health of any member of the public or any person using the Building or to any property (the Building Notice).
(a) The ACP should not be removed and replaced with a material compliant with the Regulations and the Building Code of Australia (the BCA); or
(b) As far as it is reasonably practicable, remove and replace the ACP whereby it can be demonstrated that the extent and configuration of the cladding satisfies the Regulations and the BCA performance requirements.



(a) Naming First, Second and Third Parties as Interested Parties to the Application;
(b) Requiring the Applicant to file with the BAB and send to the Interested Parties its Statement of Contentions, and
(c) Giving the Interested Parties the opportunity to file and serve a Statement of Contentions (if any) responding to the Application.
THE APPLICANT'S STATEMENT OF CONTENTIONS (IN SUMMARY)
(a) Around the Ground Floor entry and the entry canopy and first floor on the North elevation;
(b) Around the booster assembly and up to 9 metres on the East elevation; and
(c) Up to 9 metres from the roof of the adjoining building on the West elevation.
THE FIRST INTERESTED PARTY'S STATEMENT OF CONTENTIONS
THE SECOND INTERESTED PARTY'S STATEMENT OF CONTENTIONS
THE THIRD INTERESTED PARTY'S STATEMENT OF CONTENTIONS (IN SUMMARY)
Sector 1 - Little Collins Street Elevation (North)
Sector 3 - South Elevation (Access Laneway - extension of Fleming Place)
(a) The Cladding Assessment Report Rev.01 dated April 2023 (the 2023 CAR);
(b) How the wall insulation on the internal side of the ACP influences the evaluation or rectification strategy;
(c) How the Queensland Guideline is relevant to this proceeding which involves a building in Victoria;
(d) Architectural Drawing No: 24-20-WD08 A1 (Early Works) does not show removal of ACP to a height of 9 metres above Ground Level; and
(e) The hose reel cabinet adjoining the Early Warning Intercommunication System (EWIS) cabinet is used for storage of items obstructing the use of the hose reel which may prevent the occupants of the Building undertaking an initial fire attack.
(2) An Application may be made to the Building Appeals Board that a provision of the building regulations -
(a) does not apply; or
(b) applies with the modifications or variations specified in the application -
to a building or land specified in the application.