VBAB
2025-07-29
Original judgment source is linked above.
..., the FER does not appear to fully consider or assess the large, isolated building having regard to the Deemed-to-Satisfy provisions of the Building Code of Australia; nor does it assess in full against the performance requirements applicable to such buildings.
(a) The Applicant to file and serve further information, including but not limited to the following-
(i) The Fire Rescue Victoria's (FRV) view regarding the classification of the buildings and whether the building is a large isolated building;
(ii) Premising that the canopy structures may have been constructed without building permits, whether the municipal building surveyor for the Kingston City Council be joined as an interested party; and
(iii) Having regard to the FRV's pre-regulation 129 Letter of Advice dated 5 April 2024 referred to 6 variations, whereas the FRV in its Report dated 25 July 2024 lists only 3 variations.
(b) The Interested Parties to file and serve any material in support of or in opposition to the Applicant's further material.
(a) The original (nine) Applications were withdrawn;
(b) Further applications (Applications 1-8) being commenced under s 160A of the Act; and
(c) An application (Application 9) being commenced under s 160 of the Act.
APPLICANT'S STATEMENT OF CONTENTIONS (IN SUMMARY FORM)
(a) The subject building is to be protected with an automatic sprinkler system throughout the warehouses including the canopy area. The warehouses are fire separated achieving an FRL of 90/90/90 with exception of a few parts of the walls; and
(b) The roller doors not achieving an FRL are to be protected with sidewall or wall wetting sprinklers (the 2nd FER is inconsistent on this requirement) and the parts of the walls concealed within the office ceilings are to be protected with fire resistant insulation from within the warehouses as specified in the 2nd FER.
SECOND INTERESTED PARTY'S STATEMENT OF CONTENTIONS (IN SUMMARY FORM)
A building must have elements which will, to the degree necessary, avoid the spread of fire...
The new canopy does not increase the risk of structural collapse and fire spread to adjoining fire compartments and unduly increase the risk to life safety of the occupants and firefighting personnel.
The fire brigade intervention is not expected to be unduly affected due to the provision of sprinklers and fire compartmentation between warehouse and canopy.
For this building, we expect that their main activities during a fire will include assistance with evacuation and fire extinguishment using the fire hydrant system, supported by the automatic sprinkler system.
The FRC's operational firefighting concerns around sufficient access has not been satisfactorily assessed or addressed.
[1] The listing dated 30 April 2025 was 'on the papers'.