Contessa Condominiums [2025] QBCCMCmr 255
Body Corporate and Community Management Act 1997 (Qld) (), and (3)(a)
BY-LAWS - where the respondents have installed hard flooring in their lot - whether the respondents have complied with the hard flooring by-laws.
(a) Removal of recently installed floor tiles in the lot 71 ensuite, bathroom and powder room, and professional installation of a high quality acoustic underlay system (such as Regupol 6010 dimpled rubber, or similar, as recommended by the acoustic engineer).
(b) Laying a cement screed of at least 30mm before installing new floor tiles.
(c) Ensuring that all pipes are acoustically lagged with pyrotek 4525c pipe lagging (or similar) and sealed to the slab.
(d) Undertaking post-installation impact tests and provide a sound impact isolation test certificate of compliance to the applicants.
I HEREBY CERTIFY this is a true copy of the order and reasons for decision.
1. That the owners of Lot 71 implement the recommendations of the Alpha Acoustics engineers report in full in all wet areas with new flooring (ensuite, bathroom, powder room). These recommendations will require:
(a) The owners of Lot 71 remove all newly installed floor tiles in their ensuite, bathroom and powder room and have a high-quality acoustic underlay system (such as Regupol 6010 or similar as recommended by the acoustic engineer) professionally installed before reinstalling floor tile
(b) Install properly acoustically lagged pyrotek 4525c pipe lagging, sealed to the slab, to all pipe
(c) The owners of Lot 71 undertake a post-installation sound impact test in their ensuite
(d) The owners of Lot 71 undertake a post-installation sound impact test of the adjacent Master bedroom in Lot 67 from their ensuite
(e) Install a sound-dampening ceiling with resilient hangers in the master bedroom of Lot 67
(f) All sound impact tests conducted and a sound impact isolation test certificate of compliance is provided to the applicant
2. The owners undertake all the above at their own cost
3. The owners of Lot 71 compensate the owners of Lot 67 for all costs due their failure to comply with the By-laws
2.1.11.1 any installed floor surface is to provide a level of floor impact isolation of L'NT,W 54 or better, between lower or adjacent Occupier areas;
2.1.11.2 prior to the installation of the floor surface, the Owner must obtain advice from a recognised acoustical consulting company with regard to suitable floor treatments to meet this level of isolation. This may include testing on a sample of the isolation system to be used to confirm the final performanc outcome;
2.1.11.3 upon completion of the works, the Owner must have the floor tested to ensure the minimum impact isolation requirement has been met. This test must be carried out in accordance with procedures defined in ISO 140 Part 7 by a company experienced with and recognised for this type of work;
2.1.11.4 the owner must submit an impact isolation test certificate to the Body Corporate within ten days of the test showing compliance with the defined limit;
2.1.11.5 should the test fail to meet the minimum requirements of this By-law, the owner must, within 30 days, remove the flooring and replace it with flooring which complies with this By-law, at the Owner's cost.
Within 3 months of the date of this order, the owners of Lot 71, Mark and Patricia Kingaby, must engage an appropriately qualified professional to conduct acoustic testing of the floor installed in the ensuite of Lot 71 in accordance with the terms of By-law 2.1.11.3.
It is "unreasonable to expect tiles laid in a laundry or bathroom could achieve the criteria of L'nT,w 54".
On many apartment buildings in Queensland, floor impact insulation layers are not installed in the wet areas including kitchens, bathrooms and laundries. As the design of an apartment becomes more compact, to save floor height, plasterboard ceilings are now installed exposing the bar concrete slab. The distance between the upper level wet areas to living area underneath is generally less than 500mm. This is a potential problem (depending on the living habits of the people on the upper level) for people below. We advise clients to apply an acoustic underlay on tiled floor areas, to minimise impact for kitchens, bathrooms, entries, hallways and laundries.
What appears to be the most cost-effective means of reducing impact noise is to install an impact isolation layer under the hard floor surface. These are generally a proprietary product located under tiles, stone or timber floor systems. On tiled floors such products should provide at-least a 15 unit improvement in isolation with isolation of up to 25 units possible. The impact systems can be a rolled out resilient element (1mm to 15mm thick), a screeded wet system (typically 5 to 10mm), or a solid board system laid out across the floor (approx. 10mm thick).
Smaller spaces often have more low-frequency reverberation, which can be a challenge. Also, bathroom flooring is frequently compromised due to pipe work, drainage, and waterproofing, which can limit the effectiveness of certain acoustic treatments.
It's important to understand that failures in bathroom and laundries when tested against NCC 2020, are not uncommon. It is therefore unreasonable to expect tiles laid in either the laundry or bathroom could achieve the criteria of L'nT,w 54 or less. Structural engineering would be required - including removing the pipes as this provides the greatest level of transmission.
Smaller spaces often have more low -frequency reverberations, which can be a challenge. Also bathroom flooring is frequently compromised due to pipework, drainage, and waterproofing, which can limit the effectiveness of certain acoustic treatments. It is therefore unreasonable to expect tiles laid in either the laundry or bathroom could achieve the criteria of L'nT,w 54 or less.
2.1.11.1 any installed floor surface is to provide a level of floor impact isolation of L'nT,w 54 or better, between lower or adjacent Occupier areas;
2.1.11.2 prior to the installation of the floor surface, the Owner must obtain advice from a recognised acoustical consulting company with regard to suitable floor treatments to meet this level of isolation. This may include testing on a sample of the isolation system to be used to confirm the final performanc outcome;
2.1.11.3 upon completion of the works, the Owner must have the floor tested to ensure the minimum impact isolation requirement has been met. This test must be carried out in accordance with procedures defined in ISO 140 Part 7 by a company experienced with and recognised for this type of work;
2.1.11.4 the owner must submit an impact isolation test certificate to the Body Corporate within ten days of the test showing compliance with the defined limit;
2.1.11.5 should the test fail to meet the minimum requirements of this By-law, the owner must, within 30 days, remove the flooring and replace it with flooring which complies with this By-law, at the Owner's cost.
F 7P1 - Sound transmission through floors - 2019: FP5.1
A floor separating sole-occupancy units or a sole-occupancy unit from a plant room, lift shaft,
stairway, public corridor, public lobby, or the like, or parts of a different classification, must
minimise the transmission of airborne and impact generated sound such that the separating
floor, including the effect of services and their penetrations, has -
a. a weighted standardised level difference with spectrum adaptation term (DnT,w + Ctr) not
b. a weighted standardised impact sound pressure level (LnT,w) not more than 62 for impact
Compliance with F7P1 to avoid the transmission of airborne and impact generated sound through floors is verified when it is measured in-situ that the separating floor has -
On many apartment buildings in Queensland, floor impact insulation layers are not installed in the wet areas including kitchens, bathrooms and laundries. As the design of an apartment becomes more compact, to save floor height, plasterboard ceilings are now installed exposing the bar concrete slab. The distance between the upper level wet areas to living area underneath is generally less than 500mm. This is a potential problem (depending on the living habits of the people on the upper level) for people below. We advise clients to apply an acoustic underlay on tiled floor areas, to minimise impact for kitchens, bathrooms, entries, hallways and laundries.
What appears to be the most cost-effective means of reducing impact noise is to install an impact isolation layer under the hard floor surface. These are generally a proprietary product located under tiles, stone or timber floor systems.
A noise model was used to simulate the existing ensuite performance and it was difficult to achieve the results without adding some form of flanking. It is also noted that modelling is only approximate. Never the less the existing floor was modelled to Lntw 67. Then applying underlays (assuming no airborne leakage through services) to develop various performances and to form the basis of comparison to estimate an underlays relative performance:
Given the ongoing noise dispute Alpha Acoustics recommend the best performer is selected:
As an acoustics professional and Lot owner I do not believe the By-Laws require amendment. The current By Laws have served the building well since we have been owners and in my professional opinion there is no technical reason to change the By Laws at this time. Any change would only see a reduction in the acoustic amenity of the building and open the door to disgruntlement amongst owners.
There is a distinct difference in professional opinion between the two acoustic consulting firms in this case. This in turn may well have led to the need for adjudication. The noise level By Laws have not recently been changed and all owners are aware of their responsibility, as should be their contractors.
Respondents' claims that the tiling work met with "QBCC and "Australian Standards".
External - BCA Part H2D8 & AS4654.2-2012[21]
(a) Removal of recently installed floor tiles in the lot 71 ensuite, bathroom and powder room, and having a high-quality acoustic underlay system (such as Regupol 6010 dimpled rubber or similar, as recommended by the acoustic engineer) professionally installed. > > (b) Laying a cement screed of at least 30mm before installing new floor tiles. > > (c) Ensuring that all pipes are acoustically lagged with pyrotek 4525c pipe lagging (or similar) and sealed to the slab. > > (d) Undertaking post-installation impact tests and provide a sound impact isolation test certificate of compliance to the applicants.
[1] This CMS was registered 30 September 2022. A subsequent CMS was recorded in November 2023.
[2] See Contessa Condominiums [2024] QBCCMCmr 267 at [36] to [37]
[3] Attachment to application - Conference Paper
[4] Contessa Condominiums [2024] QBCCMCmr 267
[7] See sections 184, 227, 228, 276 and Schedule 5 of the Act
[9] See sections 246 and 244 of the Act, respectively
[11] See section 271 of the Act for the investigative powers of an adjudicator
[13] See Contessa Condominiums [2024] QBCCMCmr 267 at [36] to [37]
[14] This CMS was registered 30 September 2022. A subsequent CMS was recorded in November 2023.
[17] As distinct from common property stairways, corridors and lobbies.