A static water supply, such as a tank, must be provided unless there is a hydrant connected to a reticulated water supply within 120 metres of the dwelling; pr
A static water supply must meet the following requirements:
¾ A minimum of 10,000 metres on-site storage must be provided on the land and be maintained solely for fire fighting;
¾ The water supply must be located within 60 metres of the dwelling;
¾ Fire brigade vehicles must be able to get to within four metres of the water outlet;
¾ The water supply must be readily identifiable from the building or appropriate signage (see Appendix A: Figure 1) must point to water supply.
All below ground water pipelines must be installed to the following depth
¾ All fixed above-ground water pipelines and fittings, including water supply, must be constructed of non-corrosive and non-combustible materials or protected from the effects of radiant heat and flame.
If the static water supply is above ground the following additional standards must apply:
¾ All above ground static water supply must provide at least one 64mm 3 thread/25mm x 50mm nominal bore British Standard Pipe (BSP), round male coupling (See Appendix A: Figure 2);
¾ All pipe work and valving between the water supply and the outlet must be no less than 50mm nominal bore;
¾ If less than 20 metres from the building, each outlet must face away from the building to allow access during emergencies.
Access to the dwelling hereby approved must be designed to allow emergency vehicles access. The minimum design requirements are as follows:
¾ Curves in driveway must have a minimum radius of ten metres;
¾ The average grade must be no more than 1 in 7 (14.4%) (8.1o) with a maximum of no more than 1 in 5 (20%)(11.3o) for no more than 50 metres;
¾ Dips must have no more than a 1in 8 (12.5%)(7.1o) entry and exit angle.
If the driveway from the road to the dwelling and water supply, including gates, bridges and culverts, is greater than 30 m long, the driveway:
¾ Must be designed, constructed and maintained for a load limit of at least 15 tonnes;
¾ Must provide a minimum trafficable width of four metres, and
¾ Be clear of encroachments 4 metres vertically (See appendix A: Figure 3).
A distance of 30 metres around the proposed dwelling or to the property boundary (whichever is the lesser) must be maintained to the following requirements during the declared 'Fire Danger Period' to the satisfaction of the Responsible Authority:
Note: Non-flammable features such as tennis courts, swimming pools, dams, patios, driveways or paths should be incorporated into the vegetation management plan especially on the north and western sides of the proposed building.
Features with high flammability such as coir doormats, firewood stacks should not be located near the dwelling during the fire danger period. Clumps of hedges and shrubs with low flammability and/or high moisture content may be retained to act as a barrier to ember and radiant heat.
The land is in a bushfire prone area designed under regulation 804 of the Building Regulations 2006. The planning permit conditions mean the building is located within 100metres of vegetation with a low fuel load, which corresponds to a low category of bushfire attach under AS3959.
These periods may be extended if a request is made in writing before the permit expires, or within three months afterwards.
The Responsible Authority is directed to issue a permit in accordance with this order under the provisions of Section 85(1)(b) of the Planning and Environment Act 1987.
A dwelling used by a resident of the dwelling, to provide accommodation for persons away from their normal place of residence.
Land in one ownership containing a number of dwellings used to accommodate persons away from their normal place of residence.