### sec.24 Isolators for equipment driven by electricity
A coal mine’s electrical engineering manager must ensure the mine has a full current isolator for equipment driven by electricity at the mine.
The electrical engineering manager must ensure—
the isolator is—
clearly identified as the isolator for the equipment; and
situated in a location that is easily accessible by a person working on the equipment; and
the equipment is clearly identified as being supplied with electricity from the isolator.
by marking the isolator or equipment, or placing a notice near the isolator or equipment
(sec.24-ssec.1) A coal mine’s electrical engineering manager must ensure the mine has a full current isolator for equipment driven by electricity at the mine.
(sec.24-ssec.2) The electrical engineering manager must ensure— the isolator is— clearly identified as the isolator for the equipment; and situated in a location that is easily accessible by a person working on the equipment; and the equipment is clearly identified as being supplied with electricity from the isolator. by marking the isolator or equipment, or placing a notice near the isolator or equipment
- (a) the isolator is— (i) clearly identified as the isolator for the equipment; and (ii) situated in a location that is easily accessible by a person working on the equipment; and
- (i) clearly identified as the isolator for the equipment; and
- (ii) situated in a location that is easily accessible by a person working on the equipment; and
- (b) the equipment is clearly identified as being supplied with electricity from the isolator.
- (i) clearly identified as the isolator for the equipment; and
- (ii) situated in a location that is easily accessible by a person working on the equipment; and