{"id":"sr:electricity-safety-registration-and-licensing-regulations-2020","name":"Electricity Safety (Registration and Licensing) Regulations 2020","slug":"electricity-safety-registration-and-licensing-regulations-2020","collection":"regulation","jurisdiction":"vic","status":"in_force","isInForce":true,"actNumber":null,"makingDate":null,"administeringDepartment":null,"currentVersion":{"id":181393,"registerId":"vic-sr:electricity-safety-registration-and-licensing-regulations-2020-current","compilationNumber":null,"startDate":"2026-04-05","status":"InForce","reasons":null,"registeredAt":null},"sections":[{"sectionNumber":"1","sectionType":"section","heading":"Electricity Safety (Registration and Licensing) Regulations 2020","content":"Version No. 003\n\n**Electricity Safety (Registration and Licensing) Regulations 2020**\n\n**S.R. No. 136/2020**\n\nVersion incorporating amendments as at  \n5 April 2024\n\n**TABLE OF PROVISIONS**\n\n*Regulation Page*\n\nPart 1—Preliminary 1\n\n1 Objectives 1\n\n2 Authorising provisions 1\n\n3 Commencement 1\n\n4 Definitions 2\n\nPart 2—Electrical contracting 8\n\nDivision 1—Classes of electrical contracting work that require registration 8\n\n5 Prescribed classes of electrical contracting 8\n\nDivision 2—Restriction on the employment of certain persons 8\n\n6 Restriction on the employment of persons to carry out electrical installation work 8\n\nDivision 3—Registration of electrical contractors 8\n\n7 Applications for a grant of registration as an electrical contractor or renewal of registration 8\n\n8 Application and renewal fees 11\n\n9 Registration as an electrical contractor 11\n\n10 Qualification requirements for registration as an electrical contractor 13\n\n11 Refusal of registration 15\n\n12 Prescribed insurance 17\n\n13 Conditions of registration 17\n\n14 Obligations of registered contractors 19\n\n15 Cancellation of registration 21\n\n16 The register 21\n\n17 Registration cards 22\n\nPart 3—Electrical work 24\n\nDivision 1—Classes of electrical work that require a licence 24\n\n18 Classes of electrical installation work that require a licence 24\n\n19 Classes of electrical inspection work that require a licence 25\n\n20 Classes of electrical linework work that require a licence 26\n\nDivision 2—Licensing of electrical workers 26\n\n21 Applications for issue of licences 26\n\n22 Electrician's licence 28\n\n23 Supervised electrical installation worker's licence 29\n\n24 Electrician (Supervised) worker's licence 30\n\n25 Occupier's licence 30\n\n26 Electrical switchgear worker's licence 31\n\n27 Restricted electrical worker's licence (Class 1) 32\n\n28 Restricted electrical worker's licence (Class 2) 34\n\n29 Electrical inspector's licence 36\n\n30 Class \"L\" inspector's licence 37\n\n31 Electrical lineworker's licence 37\n\n32 Supervised class \"R\" electrical lineworker's licence 38\n\n33 Restricted class \"C\" electrical lineworker's licence 38\n\n34 Refusal of licence 39\n\n35 Renewal of licences 41\n\n36 Energy Safe Victoria to specify continuing professional development requirements 43\n\n37 Cancellation of licence 43\n\nPart 4—Other matters 44\n\n38 Apprentices 44\n\n39 Change of name or address 44\n\n40 Licence cards 44\n\n41 Licence card to be produced on demand 45\n\nPart 5—Fees 46\n\n42 Fees—rebates 46\n\n43 Fees—refunds 46\n\n44 Fees—waiver—additional classes of electrical work 46\n\n45 Fees—waiver—lineworker's licence 46\n\nPart 6—Infringement notices 48\n\n46 Provisions under which infringement notices may be served 48\n\nSchedule 1—Occupational areas 49\n\nSchedule 2 50\n\nSchedule 3 53\n\n═════════════\n\nEndnotes 57\n\n1 General information 57\n\n2 Table of Amendments 59\n\n3 Explanatory details 60\n\n**Version No.** **003**\n\n**Electricity Safety (Registration and Licensing) Regulations 2020**\n\n**S.R. No. 136/2020**\n\nVersion incorporating amendments as at  \n5 April 2024\n\nPart 1—Preliminary\n\n\t1 Objectives\n\nThe objectives of these Regulations are to—\n\n(a) provide for the registration of electrical contractors; and\n\n(b) provide for the licensing of electrical workers; and\n\n(c) prescribe fees, penalties and other matters authorised by the **Electricity Safety Act 1998**; and\n\n(d) prescribe certain provisions of these Regulations that create offences as provisions in respect of which infringement notices may be served.\n\n\t2 Authorising provisions\n\nThese Regulations are made under sections 149, 152, 156 and 157 of the **Electricity Safety Act 1998**.\n\n\t3 Commencement\n\nThese Regulations come into operation on 1 January 2021.\n\n\t4 Definitions\n\nIn these Regulations—\n\na.c. electricity generation system means an electricity generation system (other than a battery energy storage system) that has a nominal operating voltage exceeding 50 volts alternating current;\n\naccessories  has the same meaning as \"accessory\" has in the Australian/New Zealand Wiring Rules;\n\n***alternative design solution*** has the same meaning as it has in the Electricity Safety (General) Regulations 2019[[1]](#endnote-2);\n\n***applicant***—\n\n(a) in Part 2 means a person referred to in regulation 7(1);\n\n(b) in Part 3 and regulations 44 and 45 means a person referred to in regulation 21(1);\n\n***ARBN*** has the same meaning it has in the Corporations Act;\n\n***AS/NZS 3003*** means AS/NZS 3003 Electrical installations—Patient areas, as published or amended from time to time;\n\nAS/NZS 5139 means AS/NZS 5139 Electrical installations—Safety of battery systems for use with power conversion equipment, as published or amended from time to time;\n\nAustralian/New Zealand Wiring Rules means AS/NZS 3000 Electrical installations, as published or amended from time to time;\n\n***Australian regulatory authority*** means—\n\n(a) Energy Safe Victoria; or\n\n(b) a person or body that, under a law of another State or a Territory administers the licensing of electrical workers in that State or Territory;\n\nbattery energy storage system has the same meaning as \"battery energy storage system BESS\" has in AS/NZS 5139;\n\nReg. 4 def. of *battery system* inserted by S.R. No. 103/2022 reg. 5.\n\n***battery system*** means a battery or battery energy storage system that has—\n\n(a) a nominal operating voltage exceeding 12 volts direct current; and\n\n(b) an individual or combined rated storage capacity equal to or greater than one kilowatt hour;\n\nBusiness Names Register has the same meaning as it has in the Business Names Registration Act 2011 of the Commonwealth;\n\ncommunication equipment includes data transfer equipment, security system equipment, intercom and public address system equipment, nurse call system equipment and audio-visual equipment;\n\nd.c. electricity generation system means an electricity generation system (other than a battery energy storage system) that has—\n\n(a) a nominal operating voltage or open circuit voltage exceeding 50 volts direct current; and\n\n(b) an individual or combined rated generation capacity equal to or greater than 240 watts;\n\n***effective supervision***, in relation to electrical work, means—\n\n(a) being present at the site of the electrical work to the extent necessary to ensure that the work is being correctly performed and carried out in accordance with the Act and any of the regulations relating to the work and the operation of electrical installations and supply networks; and\n\n(b) being aware of the details of the electrical work being performed and  giving detailed instructions and directions with respect to the electrical work;\n\nelectricity generation system means an a.c. electricity generation system or a d.c. electricity generation system;\n\n***electrical switchgear fitting work*** means electrical installation work that consists of the assembly, alteration, repair and maintenance of switchgear and controlgear assemblies;\n\n***extra low voltage*** means a voltage not exceeding—\n\n(a) 50 volts alternating current; or\n\n(b) 120 volts ripple-free direct current;\n\n***fault finding*** means the testing of the operation of electrical equipment to determine if that electrical equipment is safe and working correctly;\n\n***hazardous area*** has the same meaning as \"Area, hazardous\" has in the Australian/New Zealand Wiring Rules;\n\n***high voltage*** means a voltage exceeding low voltage;\n\n***licensed electrical switchgear worker*** means an electrical installation worker holding a licence issued under section 40 of the Act for electrical switchgear fitting work in accordance with regulation 26;\n\n***licensed electrician*** means an electrical installation worker holding a licence issued under section 40 of the Act for electrical installation work in accordance with regulation 22;\n\n***licensed lineworker*** means an electrical lineworker holding a licence issued under section 40 of the Act for a class of electrical linework in accordance with regulation 31 or 33;\n\n***low voltage*** means a voltage exceeding extra low voltage but not exceeding—\n\n(a) 1000 volts alternating current; or\n\n(b) 1500 volts direct current;\n\n***network infrastructure company*** means a contractor who is engaged by a major electricity company to carry out electrical linework on the supply network of the major electricity company;\n\n***nominated business supervisor*** means a person nominated under regulation 7(2)(c);\n\n***nominated technical supervisor*** means a person nominated under regulation 7(2)(b);\n\n***patient area*** has the same meaning as it has in AS/NZS 3003;\n\n***primary work function*** means a work function that is primarily related to one of the occupational areas specified in Schedule 1;\n\n***railway company*** means a person who owns or operates a railway supply network or tramway supply network;\n\n***railway infrastructure company*** means a contractor who is engaged by a railway company to carry out electrical linework on a railway supply network or tramway supply network;\n\n***railway supply network*** means the supply network of a railway that is used by electric trains;\n\n***regulatory authority*** means—\n\n(a) an Australian regulatory authority; or\n\n(b) a person or body that, under a law of New Zealand, administers the licensing of electrical workers in New Zealand;\n\n***restricted electrical installation work*** means work of a type prescribed by regulation 18(d) or 18(e);\n\nReg. 4 def. of *stand-alone power system* inserted by S.R. No. 103/2022 reg. 5.\n\n***stand-alone power system*** means an electricity generation system connected to an electrical installation that is not connected to an electricity supplier's supply network;\n\n***switchgear and controlgear assembly*** means electrical equipment that is—\n\n(a) a combination of one or more switching devices together with associated control, measuring, signalling, protective and regulating equipment including all the internal electrical and mechanical interconnections and structural parts; and\n\n(b) completely assembled under the responsibility of a manufacturer;\n\n***the Act*** means the **Electricity Safety Act 1998**;\n\n***tramway supply network*** means the supply network of a tramway.\n\nPart 2—Electrical contracting\n\nDivision 1—Classes of electrical contracting work that require registration\n\n\t5 Prescribed classes of electrical contracting\n\nFor the purposes of Division 1 of Part 3 of the Act, any contracting or undertaking to carry out electrical installation work of a class prescribed by regulation 18 is a prescribed class of electrical contracting.\n\n**Note**\n\nSee also section 30 of the Act.\n\nDivision 2—Restriction on the employment of certain persons\n\n\t6 Restriction on the employment of persons to carry out electrical installation work\n\nFor the purposes of Division 1 of Part 3 of the Act, work of a class prescribed by regulation 18 is prescribed.\n\n**Note**\n\nSee also section 36(1) of the Act.\n\nDivision 3—Registration of electrical contractors\n\n\t7 Applications for a grant of registration as an electrical contractor or renewal of registration\n\n(1) A person may apply to Energy Safe Victoria for registration or renewal of registration as an electrical contractor.\n\n(2) An application for registration must be in writing and contain or be accompanied by the following—\n\n(a) the applicant's name, telephone number, email address and the address of the applicant's residence and place of business;\n\n(b) if the applicant will not be responsible for the effective supervision of electrical installation work or only electrical switchgear fitting work carried out on behalf of the applicant—\n\n(i) the name of the person who the applicant nominates to be the nominated technical supervisor who will be responsible for that work; and\n\n(ii) a declaration of each person nominated to be a technical supervisor of electrical contracting work that sets out the person's name, telephone number, email address and residential address and the person's consent to be such a supervisor;\n\n(c) if the applicant will not be responsible for the business management and administration of the electrical contracting work—\n\n(i) the name of the person who the applicant nominates to be the business supervisor responsible for that management and administration; and\n\n(ii) a declaration of the person nominated to be the business supervisor of electrical contracting work that sets out the person's name, telephone number, email address and residential address and the person's consent to be such a supervisor;\n\n(d) if the applicant will use a business name that is not the applicant's name—\n\n(i) the details of the business name that the applicant will use; and\n\n(ii) documentary evidence that the business name is registered in the Business Names Register and that the registration is held in the applicant's name;\n\n(e) the ABN the applicant will use;\n\n(f) if the applicant is a member of a partnership—\n\n(i) the name, telephone number, email address and residential address of each member of the partnership; and\n\n(ii) a signed statement from each member of the partnership stating that they consent to the applicant's application and agree to be bound by the conditions of registration set out in regulation 13 and the obligations set out in regulation 14;\n\n(g) in the case of an applicant which is a body corporate—\n\n(i) a copy of the certificate of registration of the company under the Corporations Act; and\n\n(ii) the name and address of each director of the body corporate; and\n\n(iii) evidence that any person making an application on behalf of the body corporate is authorised to do so; and\n\n(iv) the ABN or ARBN (if applicable) of the body corporate;\n\n(h) evidence of the qualifications required by regulation 10 that the applicant relies on for registration;\n\n(i) a statement that the applicant holds or will hold, at the time of carrying on electrical contracting, the insurance required by section 30 of the Act.\n\n(3) An application for renewal of registration must be in writing and contain or be accompanied by the following—\n\n(a) details of any changes in the information provided in the original application for the registration or for the most recent renewal of the registration or in any other circumstances relating to the application;\n\n(b) a statement that the applicant holds or will hold, at the time of carrying on electrical contracting, the insurance required by section 30 of the Act.\n\n(4) Energy Safe Victoria may require the applicant to provide further information or material in respect of an application.\n\n\t8 Application and renewal fees\n\nThe prescribed fee—\n\n(a) for an application for registration as an electrical contractor is 42⸱52 fee units;\n\n(b) for an application for renewal of registration as an electrical contractor is 20⸱42 fee units.\n\n\t9 Registration as an electrical contractor\n\nFor the purposes of section 31 of the Act, Energy Safe Victoria may register or renew the registration of an applicant if Energy Safe Victoria is satisfied that—\n\n(a) in the case of a natural person—\n\n(i) the applicant—\n\n(A) will be responsible for the effective supervision of the electrical installation work or only electrical switchgear fitting work carried out on behalf of the applicant; or\n\n(B) has nominated a natural person or a sufficient number of natural persons to be technical supervisors who will be responsible for that supervision; and\n\n(ii) the applicant—\n\n(A) will be responsible for the business management and administration of the electrical contracting work; or\n\n(B) has nominated a natural person to be the business supervisor who will be responsible for that management and administration; and\n\n(b) in the case of a body corporate—\n\n(i) the applicant has nominated a natural person or a sufficient number of natural persons to be technical supervisors who will be responsible for that supervision; and\n\n(ii) the applicant has nominated a natural person to be the business supervisor who will be responsible for that management and administration; and\n\n(c) if the applicant will be responsible for the effective supervision of the electrical installation work or only electrical switchgear fitting work, that the applicant is a licensed electrician or a licensed electrical switchgear worker who has completed the requirements specified in regulation 10; and\n\n(d) each person nominated under an application to which paragraph (a)(i)(A) or (b)(i) relates to be responsible for the effective supervision of electrical installation work or only electrical switchgear fitting work is a licensed electrician or a licensed electrical switchgear worker who has completed the requirements specified in regulation 10; and\n\n(e) if the applicant will be responsible for the business management and administration of the electrical contracting work, that the applicant has completed the requirements specified in regulation 10; and\n\n(f) each person nominated under an application to which paragraph (a)(ii)(B) or (b)(ii) relates to be responsible for business management and administration of the electrical contracting is a person who has completed the requirements specified in regulation 10.\n\n\t10 Qualification requirements for registration as an electrical contractor\n\n(1) For the purposes of regulation 9, the requirements for a person to undertake effective supervision of electrical installation work are that the person is a licensed electrician who has—\n\n(a) satisfactorily completed the Licensed Electrician's Assessment (the ***LEA***) conducted by a body approved by Energy Safe Victoria within the relevant period; or\n\n(b) satisfactorily completed a substantially equivalent examination conducted by Energy Safe Victoria or a body approved by Energy Safe Victoria within the relevant period; or\n\n(c) has attained proficiency and experience in electrical installation work that is assessed by Energy Safe Victoria to be at least of an equivalent standard to the LEA.\n\n(2) For the purposes of regulation 9, the requirements for a person to undertake effective supervision of electrical switchgear fitting work are that the person is—\n\n(a) a licensed electrical switchgear worker who has—\n\n(i) successfully completed the Licensed Switchgear Worker's Assessment (the ***LSWA***) conducted by a body approved by Energy Safe Victoria within the relevant period; or\n\n(ii) successfully completed a substantially equivalent examination conducted by Energy Safe Victoria or a body approved by Energy Safe Victoria within the relevant period; or\n\n(iii) has attained proficiency and experience in electrical switchgear fitting work that is assessed by Energy Safe Victoria to be at least of an equivalent standard to the LSWA; or\n\n(b) a licensed electrician who complies with the requirements set out in subregulation (1) or (2)(a).\n\n(3) For the purposes of regulation 9, the requirements for a person to be responsible for the business management and administration of the electrical contracting work are that the person has—\n\n(a) successfully completed a course of training about establishing an electrical contracting business that is approved by Energy Safe Victoria; or\n\n(b) passed an examination conducted by Energy Safe Victoria or a body approved by Energy Safe Victoria; or\n\n(c) successfully completed an assessment or course of training or passed an examination that is assessed by Energy Safe Victoria to be at least of an equivalent standard to that required under paragraph (a) or (b); or\n\n(d) at least 5 years experience in the management and administration of an electrical contracting business.\n\n(4) In this regulation, ***relevant period*** means—\n\n(a) in the case of an applicant undertaking supervision of electrical work, within 5 years of the date of the applicant's application for registration; and\n\n(b) in the case of a person nominated to undertake the supervision of electrical work, within 5 years of the date the person is nominated.\n\n\t11 Refusal of registration\n\nFor the purposes of section 31 of the Act, Energy Safe Victoria may refuse to register or renew the registration of an applicant if it is satisfied that—\n\n(a) a person nominated to be the technical supervisor is employed or appointed as the nominated technical supervisor of another electrical contractor and is not, or will not be, able to provide effective supervision of all the electrical installation work the person is responsible for supervising; or\n\n(b) the applicant has, within 5 years of submitting the application to Energy Safe Victoria, contravened a provision of—\n\n(i) the Act; or\n\n(ii) these Regulations; or\n\n(iii) the Electricity Safety (Installations) Regulations 2009 as in force immediately before their revocation; or\n\n(iv) the Electricity Safety (Registration and Licensing) Regulations 2010[[2]](#endnote-3) as in force immediately before their revocation; or\n\n(v) the Electricity Safety (General) Regulations 2019; or\n\n(vi) a law of another State or a Territory or of New Zealand which substantially corresponds to the Act, these Regulations or the regulations specified in subparagraph (iii), (iv) or (v); or\n\n(c) the applicant has attempted to obtain registration as an electrical contractor by fraud, misrepresentation or concealment of facts; or\n\n(d) the applicant has, within 5 years of submitting the application to Energy Safe Victoria—\n\n(i) been convicted of any offence involving fraud, dishonesty, drug trafficking or violence that was punishable by a term of imprisonment of 6 months or more; or\n\n(ii) been negligent or incompetent, or was a party to any negligence or incompetence, in connection with the carrying out of electrical installation work; or\n\n(iii) engaged in fraudulent conduct in the carrying out of electrical installation work; or\n\n(e) the applicant's ABN, ARBN or business name is not properly registered in the applicant's name.\n\n\t12 Prescribed insurance\n\nFor the purposes of section 30 of the Act, the prescribed insurance is insurance against public liability for personal injury or damage to property in connection with the electrical contracting work of the registered electrical contractor with a minimum cover of $5 000 000.\n\n\t13 Conditions of registration\n\nThe following conditions apply to the registration of a registered electrical contractor—\n\n(a) if the electrical contractor has the qualifications referred to in regulation 10(1), all electrical installation work except that actually carried out by the electrical contractor must be effectively supervised by—\n\n(i) the electrical contractor; or\n\n(ii) in the case of electrical installation work, a nominated technical supervisor who has the qualifications set out in regulation 10(1); or\n\n(iii) in the case of electrical switchgear fitting work, a nominated technical supervisor who has the qualifications set out in regulation 10(1) or 10(2)(a);\n\n(b) if the electrical contractor has the qualifications referred to in regulation 10(2)(a)—\n\n(i) all electrical switchgear fitting work except that actually carried out by the electrical contractor must be effectively supervised by—\n\n(A) the electrical contractor; or\n\n(B) a nominated technical supervisor who has the qualifications set out in regulation 10(1) or 10(2)(a); and\n\n(ii) all other electrical installation work must be effectively supervised by a nominated technical supervisor who has the qualifications set out in regulation 10(1);\n\n(c) if the electrical contractor does not have the qualifications referred to in regulation 10(1) or 10(2)(a) or the electrical contractor is not able to effectively supervise all electrical installation work or only electrical switchgear fitting work carried out on behalf of the electrical contractor,  that work must be effectively supervised by a nominated technical supervisor who has—\n\n(i) in the case of the supervision of electrical installation work, the qualifications set out in regulation 10(1); and\n\n(ii) in the case of the supervision of electrical switchgear fitting work, the qualifications set out in regulation 10(1) or 10(2)(a);\n\n(d) the nomination of a nominated technical supervisor ceases if that supervisor is nominated to be the technical supervisor of another registered electrical contractor unless the supervisor is able to provide effective supervision of all electrical installation work for which the supervisor is responsible for supervising;\n\n(e) the business of the electrical contracting work of the electrical contractor must be effectively managed and administered by the contractor or a nominated business supervisor.\n\n\t14 Obligations of registered contractors\n\n(1) A registered electrical contractor must notify Energy Safe Victoria in writing of the following events within 10 business days after the relevant event occurs—\n\n(a) any change in the information provided in the application for the original registration or for the most recent renewal of the registration;\n\n(b) any change in the circumstances of the nominated technical supervisor that would affect the supervisor's ability to effectively supervise electrical installation work carried out by the electrical contractor;\n\n(c) any change in the circumstances of the nominated business supervisor that would affect the supervisor's ability to be responsible for the management and administration of the business of the electrical contractor;\n\n(d) if the contractor is a body corporate—\n\n(i) any change of its name; or\n\n(ii) any change to the address of its principal place of business; or\n\n(iii) if it is deregistered under the Corporations Act;\n\n(e) any change in the business name, ABN or ARBN that the electrical contractor uses.\n\nPenalty: 5 penalty units.\n\n(2) If the nominated technical supervisor of a registered electrical contractor ceases to carry out that function or is no longer able to effectively supervise electrical installation work carried out by the electrical contractor, the electrical contractor must—\n\n(a) notify Energy Safe Victoria; and\n\n(b) nominate another person who has the required qualifications; and\n\n(c) send to Energy Safe Victoria within 10 business days after the nomination a declaration by the nominated person that sets out the person's name, telephone number, email address and residential address and the person's consent to be such a supervisor.\n\nPenalty: 5 penalty units.\n\n(3) If the nominated business supervisor of a registered electrical contractor ceases to carry out that function or is no longer able to be responsible for the management and administration of the business, the electrical contractor must—\n\n(a) notify Energy Safe Victoria; and\n\n(b) nominate another person who has the required qualifications; and\n\n(c) send to Energy Safe Victoria within 10 business days after the nomination a declaration by the nominated person that sets out the person's name, telephone number, email address and residential address and the person's consent to be such a supervisor.\n\nPenalty: 5 penalty units.\n\n\t15 Cancellation of registration\n\n(1) Energy Safe Victoria may cancel the registration of an electrical contractor who applies to it in writing for that cancellation.\n\n(2) Energy Safe Victoria must cancel the registration of an electrical contractor who fails to apply for renewal of registration by the renewal date.\n\n\t16 The register\n\n(1) For the purposes of section 33(2) of the Act, the register must be kept in electronic form and contain the following information about each registered electrical contractor—\n\n(a) the name and business address of the electrical contractor;\n\n(b) the telephone number and email address of the business;\n\n(c) the date of registration or renewal of registration;\n\n(d) the registration number;\n\n(e) the ABN or ARBN of the electrical contractor (if applicable);\n\n(f) the registered business name of the electrical contractor (if applicable).\n\n(2) A person's residential address must not appear on any part of the register that is available to the public unless the person—\n\n(a) has nominated that address as the person's business address; or\n\n(b) authorises Energy Safe Victoria to do so.\n\n(3) Energy Safe Victoria must publish the information recorded in the register on an internet site maintained by Energy Safe Victoria.\n\n\t17 Registration cards\n\n(1) Energy Safe Victoria must issue a registration card to a registered electrical contractor that sets out the details of registration.\n\n(2) A registration card issued to an electrical contractor under subregulation (1) is evidence of the registration of that contractor.\n\n(3) A person who is issued with a registration card must, upon receipt of the registration card—\n\n(a) sign the card; or\n\n(b) in the case of a body corporate, ensure that the card is signed by the secretary or a director of the body corporate.\n\nPenalty: 10 penalty units.\n\n(4) An electrical contractor whose registration has been cancelled must send the contractor's registration card to Energy Safe Victoria within 10 business days after the contractor receives notice of the cancellation.\n\nPenalty: 10 penalty units.\n\n(5) If a registered electrical contractor demonstrates to Energy Safe Victoria that the registration card issued to the contractor has been lost, damaged, or destroyed, Energy Safe Victoria must issue a duplicate registration card to that electrical contractor.\n\nPart 3—Electrical work\n\nDivision 1—Classes of electrical work that require a licence\n\n\t18 Classes of electrical installation work that require a licence\n\nFor the purposes of Division 2 of Part 3 of the Act, the following classes of electrical installation work are prescribed classes of electrical work—\n\n(a) electrical installation work carried out on an electrical installation ordinarily operated—\n\n(i) at low voltage or a voltage exceeding low voltage in any area; or\n\n(ii) at any voltage in a patient area (other than communication equipment operated at extra low voltage);\n\n(b) electrical installation work carried out on electricity generation systems including any wiring systems, switchgear, controlgear or accessories installed that are part of those generation systems;\n\n(c) electrical installation work carried out on all or part of a battery energy storage system including work on associated wiring systems, switchgear, controlgear and accessories;\n\n(d) electrical installation work required to carry out a primary work function relating to low voltage fixed electrical equipment that involves—\n\n(i) the disconnection of that electrical equipment or a component of that electrical equipment; and\n\n(ii) the reconnection of that electrical equipment or component of that electrical equipment or the connection of other equipment or any component of equivalent power and current in the same location and without alteration to existing cables; and\n\n(iii) the testing of that electrical equipment or a component of that electrical equipment; and\n\n(iv) fault finding in relation to that electrical equipment or a component of that electrical equipment;\n\n(e) electrical installation work required to carry out a primary work function relating to low voltage fixed electrical equipment that involves—\n\n(i) the disconnection of that electrical equipment or a component of that electrical equipment; and\n\n(ii) the reconnection of that electrical equipment or component of that electrical equipment or the connection of other equipment or any component of equivalent power and current in the same location and without alteration to existing cables; and\n\n(iii) the testing of that electrical equipment or a component of that electrical equipment.\n\n\t19 Classes of electrical inspection work that require a licence\n\nFor the purposes of Division 2 of Part 3 of the Act, the classes of electrical inspection work specified in Part A of Schedule 2 are prescribed classes of electrical work.\n\n\t20 Classes of electrical linework work that require a licence\n\nFor the purposes of Division 2 of Part 3 of the Act, the classes of electrical linework specified in Part A of Schedule 3 are prescribed classes of electrical work.\n\nDivision 2—Licensing of electrical workers\n\n\t21 Applications for issue of licences\n\n(1) A person may apply to Energy Safe Victoria for a licence for one or more classes of electrical work.\n\n(2) An application must be in writing and contain details of the following—\n\n(a) the applicant's name, residential address, postal address, telephone number and email address;\n\n(b) the name, address, telephone number and email address of any current or former employer of the applicant, the period of the employment and the electrical work carried out under that employment;\n\n(c) the applicant's experience in electrical work;\n\n(d) any refusal of any regulatory authority to issue a licence to carry out electrical work or the cancellation or suspension of such a licence;\n\n(e) the class of electrical work for which the licence is being sought.\n\n(3) An application must be accompanied by—\n\n(a) evidence of the training and qualifications and experience on which the applicant relies for licensing; and\n\n(b) in the case of an applicant for a licence under regulation 27 or 28—\n\n(i) a written description of the applicant's primary work function and of the electrical installation work required to carry out that function; and\n\n(ii) written evidence that the electrical installation work is a necessary component of the applicant's primary work function; and\n\n(c) in the case of an applicant for a licence under regulation 32 or 33, a written statement from the applicant's employer stating the following—\n\n(i) that the applicant is their employee;\n\n(ii) that the applicant is required as part of their employment to carry out the type of electrical linework to which the application relates;\n\n(iii) that the applicant has (or will obtain through appropriate training) the skills, knowledge and experience necessary to carry out the type of electrical linework to which the application relates correctly and safely.\n\n(4) Energy Safe Victoria may require the applicant to provide proof of identity or any other information or material in respect of an application.\n\n(5) The prescribed fee for a licence application (other than a Restricted electrical worker's licence or Electrical inspector's licence) is 27⸱30 fee units.\n\n(6) The prescribed fee for an application for a Restricted electrical worker's licence or Electrical inspector's licence is 42⸱52 fee units.\n\n\t22 Electrician's licence\n\n(1) For the purposes of section 40 of the Act, Energy Safe Victoria may, if Energy Safe Victoria is satisfied of the matters specified in subregulation (2), issue a licence to a person under which the person may carry out all electrical installation work of the class prescribed by regulation 18(a), (b) and (c).\n\n(2) For the purposes of subregulation (1), the following matters are specified—\n\n(a) the person—\n\n(i) has completed a 4 year contract of training as an electrician that included at least 12 months experience in carrying out electrical installation work; and\n\n(ii) holds a Certificate III in Electrotechnology Electrician; and\n\n(iii) has satisfactorily completed the Licensed Electrician's Assessment conducted by Energy Safe Victoria or a body approved by Energy Safe Victoria; or\n\n(b) the person's standard of qualifications, proficiency and experience in electrical installation work is at least of an equivalent standard to that required under paragraph (a).\n\n(3) If the applicant is applying for an electrician's licence for the first time or applying to renew a licence that has been expired for more than 5 years, the Licensed Electrician's Assessment specified in subregulation (2)(a)(iii) must have been satisfactorily completed within 5 years of the date of the applicant's application.\n\n\t23 Supervised electrical installation worker's licence\n\n(1) For the purposes of section 40 of the Act, Energy Safe Victoria may issue a licence to a person under which the person may carry out all electrical installation work of the classes prescribed by regulation 18(a), (b) and (c) under the effective supervision of a licensed electrician for a period not exceeding 3 years if Energy Safe Victoria is satisfied that—\n\n(a) the person—\n\n(i) has completed a 4 year contract of training as an electrical fitter; and\n\n(ii) holds a Certificate III in Electrical Fitting; and\n\n(iii) has satisfactorily completed a practical examination conducted by Energy Safe Victoria or a body approved by Energy Safe Victoria in safe work practices; or\n\n(b) the person has—\n\n(i) completed a 4 year contract of training as an electrician that included at least 12 months experience in carrying out electrical installation work; and\n\n(ii) partially completed the Certificate III in Electrotechnology Electrician; and\n\n(iii) satisfactorily completed a practical examination conducted by Energy Safe Victoria or a body approved by Energy Safe Victoria in safe work practices; or\n\n(c) the person's standard of qualifications, proficiency and experience in electrical installation work is at least of an equivalent standard to that required under paragraph (a) or (b).\n\n(2) The safe work practices examination specified in subregulations (1)(a)(iii) and (1)(b)(iii) must have been satisfactorily completed within 5 years of the date of the person's application.\n\n\t24 Electrician (Supervised) worker's licence\n\n(1) This regulation applies to a person who, on the commencement of these Regulations, holds a licence that was issued under section 40 of the Act and in accordance with regulation 22 of the Electricity Safety (Registration and Licensing) Regulations 2010.\n\n(2) Subject to complying with the requirements of regulation 35, the person is eligible, at any time before the expiry of that licence, to have issued to that person a licence under which the person may carry out electrical installation work of the following classes —\n\n(a) all electrical installation work of the classes prescribed by regulations 18(a), (b) and (c) subject to the condition that the person carry out all installation work under the effective supervision of a licensed electrician; and\n\n(b) all installation work of the class prescribed by regulation 18(e).\n\n\t25 Occupier's licence\n\n(1) This regulation applies to a person who, on the commencement of these Regulations, holds a licence that was issued under section 40 of the Act and in accordance with regulation 23 of the Electricity Safety (Registration and Licensing) Regulations 2010.\n\n(2) Subject to complying with the requirements of regulation 35, the person is eligible, at any time before the expiry of that licence, to have issued to that person a licence to carry out all electrical installation work of the classes prescribed by regulations 18(a), (b) and (c) that is limited to premises to which the person to be licensed occupies for residential purposes.\n\n\t26 Electrical switchgear worker's licence\n\n(1) For the purposes of section 40 of the Act, Energy Safe Victoria may issue a licence to a person under which the person may carry out electrical installation work of the classes prescribed by regulation 18(a), (b) and (c) that is limited to the assembly, alteration, repair and maintenance of switchgear and controlgear assemblies if Energy Safe Victoria is satisfied that—\n\n(a) the person—\n\n(i) has completed a 4 year contract of training in switchgear and controlgear that included at least 12 months experience in carrying out electrical switchgear and controlgear fitting work; and\n\n(ii) holds a Certificate III in Switchgear and Controlgear; and\n\n(iii) has satisfactorily completed the Licensed Switchgear Worker's Assessment conducted by Energy Safe Victoria or a body approved by Energy Safe Victoria; or\n\n(b) the person's standard of qualifications, proficiency and experience in electrical switchgear fitting work is at least of an equivalent standard to that required under paragraph (a).\n\n(2) If the applicant is applying for an electrical switchgear worker's licence for the first time or applying to renew a licence that has been expired for more than 5 years, the Licensed Switchgear Worker's Assessment specified in subregulation (1)(a)(iii) must have been satisfactorily completed within 5 years of the date of the application.\n\n\t27 Restricted electrical worker's licence (Class 1)\n\n(1) For the purposes of section 40 of the Act, Energy Safe Victoria may issue a licence to a person under which the person may carry out restricted electrical installation work of a class prescribed by regulation 18(d) if Energy Safe Victoria is satisfied that the person has—\n\n(a) a demonstrated need to undertake the restricted electrical installation work because the work is ancillary to a primary work function; and\n\n(b) the necessary qualifications.\n\n(2) In determining whether a person has a demonstrated need referred to in subregulation (1)(a), Energy Safe Victoria may take into account—\n\n(a) any of the following—\n\n(i) whether it is impractical or inefficient to require a licensed electrician to undertake the proposed restricted electrical installation work in all instances;\n\n(ii) whether the need to undertake the restricted electrical installation work is sufficiently frequent;\n\n(iii) whether there is a sufficient connection between the proposed electrical installation work and the person's primary work function;\n\n(iv) whether the level of risk associated with the proposed restricted electrical installation work outweighs the person's demonstrated need; and\n\n(b) any other matters Energy Safe Victoria considers relevant.\n\n(3) For the purpose of subregulation (1)(b), the person has the necessary qualifications if—\n\n(a) the person has—\n\n(i) the qualifications or training (if any) required to carry out the primary work function; and\n\n(ii) satisfactorily completed a course of instruction required by Energy Safe Victoria; and\n\n(iii) satisfactorily completed a practical examination conducted by Energy Safe Victoria or a body approved by Energy Safe Victoria in safely disconnecting, reconnecting and testing electrical equipment and fault finding; or\n\n(b) the person's standard of qualifications, proficiency and experience in the primary work function and electrical installation work is at least of an equivalent standard to that required under paragraph (a).\n\n(4) If the applicant is applying for a class 1 restricted worker's licence for the first time or applying to renew a licence that has been expired for more than 5 years, the examination referred to in subregulation (3)(a)(iii) must have been satisfactorily completed within 5 years of the date of the applicant's application.\n\n(5) Energy Safe Victoria must, by condition imposed on a licence, limit the type of electrical installation work that the licensed person may undertake under the licence to an occupational area or areas specified in Schedule 1.\n\n\t28 Restricted electrical worker's licence (Class 2)\n\n(1) For the purposes of section 40 of the Act, Energy Safe Victoria may issue a licence to a person under which the person may carry out restricted electrical installation work of a class prescribed by regulation 18(e) if Energy Safe Victoria is satisfied that the person has—\n\n(a) a demonstrated need to undertake the restricted electrical installation work because the work is ancillary to a primary work function; and\n\n(b) the necessary qualifications.\n\n(2) In determining whether a person has a demonstrated need referred to in subregulation (1)(a), Energy Safe Victoria may take into account—\n\n(a) any of the following—\n\n(i) whether it is impractical or inefficient to require a licensed electrician to undertake the proposed restricted electrical installation work in all instances;\n\n(ii) whether the need to undertake the restricted electrical installation work is sufficiently frequent;\n\n(iii) whether there is a sufficient connection between the proposed electrical installation work and the person's primary work function;\n\n(iv) whether the level of risk associated with the proposed restricted electrical installation work outweighs the person's demonstrated need; and\n\n(b) any other matters Energy Safe Victoria considers relevant.\n\n(3) For the purpose of subregulation (1)(b), the person has the necessary qualifications if—\n\n(a) the person has—\n\n(i) the qualifications or training (if any) required to carry out the primary work function; and\n\n(ii) satisfactorily completed a course of instruction required by Energy Safe Victoria; and\n\n(iii) satisfactorily completed a practical examination conducted by Energy Safe Victoria or a body approved by Energy Safe Victoria in safely disconnecting, reconnecting and testing electrical equipment; or\n\n(b) the person's standard of qualifications, proficiency and experience in the primary work function and electrical installation work is at least of an equivalent standard to that required under paragraph (a).\n\n(4) If the applicant is applying for a class 2 restricted worker's licence for the first time or applying to renew a licence that has been expired for more than 5 years, the examination referred to in subregulation (3)(a)(iii) must have been satisfactorily completed within 5 years of the date of the applicant's application.\n\n(5) Energy Safe Victoria must, by condition imposed on a licence, limit the type of electrical installation work that the licensed person may undertake under the licence to an occupational area or areas specified in Schedule 1.\n\n\t29 Electrical inspector's licence\n\n(1) For the purposes of section 40 of the Act, Energy Safe Victoria may issue a licence to a person under which the person may carry out electrical inspection work of any or all of the classes specified in Part A of Schedule 2 (except class \"L\") if—\n\n(a) the person—\n\n(i) has demonstrated to the satisfaction of Energy Safe Victoria the qualifications, experience, competence and proficiency in the matters specified in Part B of Schedule 2 for the relevant class of electrical inspection work; and\n\n(ii) if required by Energy Safe Victoria to do so, has satisfactorily completed a course of instruction required by Energy Safe Victoria; and\n\n(iii) has satisfactorily completed any practical or theory examinations in electrical inspection required by Energy Safe Victoria to be completed; or\n\n(b) the person's standard of qualifications, proficiency and experience in electrical installation work is at least of an equivalent standard to that required under paragraph (a).\n\nReg. 29(1A) inserted by S.R. No. 103/2022 reg. 6.\n\n(1A) If Energy Safe Victoria is satisfied that a person has demonstrated qualifications, experience, competence and proficiency in some of the electrical inspection work in a class referred to in subregulation (1), Energy Safe Victoria, by condition imposed on the licence, may specify the types of electrical inspection work that the person may carry out under the licence.\n\n(2) If the applicant is applying for an electrical inspector's licence for the first time or applying to renew a licence that has been expired for more than 5 years, the practical or theory examinations required by subregulation (1)(a)(iii) must have been satisfactorily completed within 5 years of the date of the application.\n\n\t30 Class \"L\" inspector's licence\n\n(1) This regulation applies to a person who, on the commencement of these Regulations, holds a licence that was issued under section 40 of the Act and in accordance with regulation 28 of the Electricity Safety (Registration and Licensing) Regulations 2010 under which the person may carry out electrical inspection work prescribed as class \"L\" in Part A of Schedule 2 to those Regulations.\n\n(2) Subject to complying with the requirements of regulation 35, the person is eligible, at any time before the expiry of that licence, to have issued to that person a licence under which the person may carry out electrical inspection work specified as class \"L\" in Part A of Schedule 2.\n\n\t31 Electrical lineworker's licence\n\nFor the purposes of section 40 of the Act, Energy Safe Victoria may issue a licence to a person under which the person may carry out electrical work of any or all of the classes specified in Part A of Schedule 3 if—\n\n(a) the person holds the qualification of the description specified in column 2 in the table in Part B of Schedule 3 for the corresponding class specified in column 1 of that table; or\n\n(b) the person's standard of qualifications, proficiency and experience in electrical work is at least of an equivalent standard to that required under paragraph (a).\n\n\t32 Supervised class \"R\" electrical lineworker's licence\n\nFor the purposes of section 40 of the Act, Energy Safe Victoria may issue a licence to a person under which the person may carry out electrical linework prescribed as class \"R\" in Part A of Schedule 3 under the effective supervision of a licensed lineworker who is licensed to carry out class \"R\" linework without supervision if Energy Safe Victoria is satisfied that—\n\n(a) the person is employed by a railway company or a railway infrastructure company; and\n\n(b) the person has (or will obtain through appropriate training) the skills, knowledge and experience to necessary to carry out class \"R\" linework correctly and safely under effective supervision.\n\n\t33 Restricted class \"C\" electrical lineworker's licence\n\n(1) For the purposes of section 40 of the Act, Energy Safe Victoria may issue a licence to a licensed class \"D\" lineworker under which the person may carry out specified types of electrical linework prescribed as class \"C\" in Part A of Schedule 3 if Energy Safe Victoria is satisfied that —\n\n(a) the person is employed by a major electricity company or a network infrastructure company; and\n\n(b) the person has (or will obtain through appropriate training) the skills, knowledge and experience to necessary to carry out the specified types of class \"C\" linework correctly and safely.\n\n(2) Energy Safe Victoria must, by condition imposed on the licence, specify the types of class \"C\" electrical linework that the licensed person may undertake under the licence.\n\n(3) Energy Safe Victoria may, by condition imposed on the licence, limit the licence so that it only authorises the electrical linework authorised by the licence to be carried out on a specified supply network or on supply networks within a specified geographical area of the State.\n\n\t34 Refusal of licence\n\n(1) For the purposes of section 40 of the Act, Energy Safe Victoria may refuse to issue a licence to an applicant if Energy Safe Victoria is satisfied that—\n\n(a) the applicant has not complied with these Regulations in relation to the class of licence applied for; or\n\n(b) the applicant has, within 5 years of submitting the application to Energy Safe Victoria, contravened a provision of—\n\n(i) the Act; or\n\n(ii) these Regulations; or\n\n(iii) the Electricity Safety (Installations) Regulations 2009 as in force immediately before their revocation; or\n\n(iv) the Electricity Safety (Registration and Licensing) Regulations 2010 as in force immediately before their revocation; or\n\n(v) the Electricity Safety (General) Regulations 2019; or\n\n(vi) a law of another State or a Territory or of New Zealand which substantially corresponds to the Act or these Regulations or the regulations specified in subparagraph (iii), (iv) or (v); or\n\n(c) the applicant has attempted to obtain a licence as an electrical worker by fraud, misrepresentation or concealment of facts; or\n\n(d) the applicant has, within 5 years of submitting the application to Energy Safe Victoria,—\n\n(i) been convicted of any offence involving fraud, dishonesty, drug trafficking or violence that was punishable by a term of imprisonment of 6 months or more; or\n\n(ii) been negligent or incompetent, or was a party to any negligence or incompetence, in connection with the carrying out of electrical work; or\n\n(iii) engaged in fraudulent conduct in the carrying out of electrical work.\n\n(2) In addition to the grounds of refusal specified in subregulation (1), Energy Safe Victoria may refuse to issue or renew a licence to a person under which the person may carry out electrical linework prescribed as class \"R\" in Part A of Schedule 3, under the effective supervision of a licensed lineworker who is licensed to carry out class \"R\" linework without supervision, for the purposes of—\n\n(a) limiting or reducing the number of supervised class \"R\" lineworker licences issued; or\n\n(b) phasing out or discontinuing the supervised class \"R\" lineworker licence.\n\n(3) In addition to the grounds of refusal specified in subregulation (1), Energy Safe Victoria may refuse to issue or renew a licence to a licensed class \"D\" lineworker under which the person may carry out specified types of electrical linework prescribed as class \"C\" in Part A of Schedule 3 for the purposes of—\n\n(a) limiting or reducing the number of restricted class \"C\" lineworker licences issued; or\n\n(b) phasing out or discontinuing the restricted class \"C\" lineworker licence.\n\n\t35 Renewal of licences\n\n(1) Subject to this regulation, a licensed electrical worker, other than the holder of a licence under regulation 23, may apply to Energy Safe Victoria for renewal of the worker's licence.\n\n(2) An application for renewal of a licence must be in writing and contain details of any changes in the information provided in the application for the licence or for the most recent renewal of the licence or in any other circumstances relating to the application.\n\n(3) An application for renewal of a licence must be accompanied by evidence of the completion of any continuing professional development that is required by Energy Safe Victoria to be completed before applying for the renewal of a licence or class of licence.\n\n(4) Energy Safe Victoria may require the applicant to provide further information or material relating to the competence of the applicant to carry out the class of electrical work for which the licence is to be renewed.\n\n(5) The prescribed fee for an application for the renewal of a licence (other than a Restricted electrical worker's licence or Electrical inspector's licence) is 13⸱65 fee units.\n\n(6) The prescribed fee for an application for the renewal of a Restricted electrical worker's licence or Electrical inspector's licence is 20⸱42 fee units.\n\n(7) In considering whether to grant a renewal of a licence, Energy Safe Victoria must have regard to whether the applicant has complied with any continuing professional development requirements that are required by Energy Safe Victoria to be completed before applying for the renewal of the licence.\n\n(8) For the purposes of section 40 of the Act, Energy Safe Victoria may refuse to renew the licence of an electrical worker on any of the grounds set out in regulation 34.\n\n(9) If the applicant has not complied with any continuing professional development requirements that are required by Energy Safe Victoria to be completed before applying for the renewal of the licence, Energy Safe Victoria may—\n\n(a) refuse to renew the licence; or\n\n(b) renew the licence with a condition that the required professional development requirements be completed within a specified time not exceeding 12 months from the date the licence is renewed; or\n\n(c) renew the licence without conditions if Energy Safe Victoria considers it is not appropriate or necessary for the applicant to complete the applicable professional development requirements for any reason.\n\n\t36 Energy Safe Victoria to specify continuing professional development requirements\n\n(1) For the purposes of regulation 35(3), Energy Safe Victoria may, by notice published on an internet site maintained by Energy Safe Victoria, specify the continuing professional development requirements for an electrical licence or a class of electrical licence.\n\n(2) The continuing professional development requirements may include skills maintenance or skills development activities or both and must not exceed for any one class of licence during a renewal period—\n\n(a) 8 hours of skills maintenance activities; and\n\n(b) 8 hours of skill development activities.\n\n(3) The continuing professional development requirements may specify that a skills maintenance requirement must be completed within the 2 year period immediately before making an application for the renewal of a licence.\n\n(4) In this regulation, ***renewal period*** means  the period between the date the licence is issued or renewed and the date the licence is next due to expire.\n\n\t37 Cancellation of licence\n\n(1) Energy Safe Victoria may cancel the licence of an electrical worker who surrenders the written licence for cancellation or applies to Energy Safe Victoria in writing for the issue of a licence of another class.\n\n(2) Energy Safe Victoria must cancel the licence of an electrical worker who does not apply for renewal of the licence by the renewal date specified on the licence card.\n\nPart 4—Other matters\n\n\t38 Apprentices\n\nFor the purposes of section 39 of the Act, an apprentice is required to carry out all electrical work under the effective supervision of—\n\n(a) in the case of electrical installation work (other than restricted electrical installation work), a licensed electrician; or\n\n(b) in the case of restricted electrical installation work, a person licensed to carry out the class of restricted electrical installation work they are supervising; or\n\n(c) in the case of electrical switchgear fitting work—\n\n(i) a licensed electrician; or\n\n(ii) a licensed electrical switchgear worker; or\n\n(d) in the case of electrical linework, a licensed lineworker that is licensed to carry out the class of electrical linework they are supervising.\n\n\t39 Change of name or address\n\nThe holder of a licence must notify Energy Safe Victoria within 10 business days after any change in that person's name or address.\n\nPenalty: 10 penalty units.\n\n\t40 Licence cards\n\n(1) Energy Safe Victoria must issue a licence card to a licensed electrical worker.\n\n(2) A licence card issued to a licensed electrical worker under subregulation (1) is evidence that the electrical worker is licensed by Energy Safe Victoria to carry out a particular class of electrical work.\n\n(3) A person who is issued with a licence card must, upon receipt of the card, sign the card.\n\n1. 10 penalty units.\n\n\n(4) An electrical worker whose licence has been cancelled must send the licence card to Energy Safe Victoria within 10 business days after the worker receives notice of the cancellation.\n\nPenalty: 10 penalty units.\n\n(5) If a licensed electrical worker demonstrates to Energy Safe Victoria that the licence card issued to the worker has been lost, damaged, or destroyed, Energy Safe Victoria must issue a duplicate card to that electrical worker.\n\n\t41 Licence card to be produced on demand\n\nA person who is carrying out a class of electrical work prescribed in Division 1 of Part 3 of these regulations must, at the request of an enforcement officer—\n\n(a) produce the person's licence card to the enforcement officer; or\n\n(b) provide details of the person's licence to the officer.\n\nPenalty: 10 penalty units.\n\nPart 5—Fees\n\n\t42 Fees—rebates\n\n(1) Energy Safe Victoria may rebate the payment of an application fee for the issue or renewal of a registration for an electrical contractor if the registration is to be issued for a period of less than 5 years.\n\n(2) Energy Safe Victoria may rebate the payment of an application fee for the issue or renewal of a licence for an electrical worker if the licence is to be issued for a period of less than 5 years.\n\n\t43 Fees—refunds\n\nEnergy Safe Victoria may refund part of the application fee for the issue or renewal of a licence for an electrical worker if the licence is to be cancelled for the issue of a licence of another class.\n\n\t44 Fees—waiver—additional classes of electrical work\n\nEnergy Safe Victoria may waive the application fee for the issue of a licence to an applicant who is a licensed electrical worker if the applicant is applying to have an additional class of electrical work added to their licence.\n\n\t45 Fees—waiver—lineworker's licence\n\n(1) Energy Safe Victoria may waive the application fee for the issue of a lineworker licence for an applicant if—\n\n(a) the applicant applied for the lineworker licence within one year after the day these Regulations commenced; and\n\n(b) in the opinion of Energy Safe Victoria, the applicant met the requirements of regulation 31, 32 or 33 in relation to the class of lineworker licence the applicant is applying for immediately before the commencement of these Regulations.\n\n(2) Energy Safe Victoria may waive part of the application fee for the renewal of a lineworker licence for an applicant if—\n\n(a) the applicant was issued a lineworker licence on or after 1 January 2021; and\n\n(b) that licence was issued for a period that was less than 5 years duration.\n\nPart 6—Infringement notices\n\n\t46 Provisions under which infringement notices may be served\n\nFor the purposes of paragraph (b) of the definition of ***prescribed offence*** in section 140A of the Act, regulations 14(1)(a), 14(1)(d), 14(1)(e), 14(2) and 14(3), 17(3)(a), 17(3)(b) and 17(4), 39, 40(3) and 40(4), and 41 are prescribed provisions.\n\nSchedule 1—Occupational areas\n\nRegulations 4, 27(5) and 28(5)\n\n1. Air conditioning and refrigeration\n\n2. Instrumentation\n\n3. Electronics\n\n4. Water heaters\n\n5. Electrical appliances\n\n6. Preassembled neon signs\n\n7. Composite equipment\n\n8. Control devices\n\n9. Gas appliances\n\n10. Motors\n\n11. Hazardous area equipment\n\nSch. 2 amended by S.R. No. 103/2022 regs 7, 8.\n\nSchedule 2\n\nRegulations 19, 29 and 30\n\nPart A—Specified classes of electrical inspection work\n\n| *Class* | *Description* |\n| --- | --- |\n| L | Electrical installations comprising a low voltage single phase, 2 wire supply comprising consumers mains, main earthing systems, consumer terminals connection devices or those parts of main switchboards that are related to the control of installations and the protection against the spread of fire but does not include electrical equipment installed as part of an alternative design solution. |\n| G | Any low voltage electrical installations except—<br> (i) class H; and<br> (ii) class M; and<br> (iii) class RE; and<br> (iv) electric fences intended primarily for the control or containment of animals. |\n| RE | Electrical installations that are—<br> (i) electricity generation systems including any wiring systems, switchgear, controlgear or accessories installed to provide control or protection to those generation systems (excluding stand-alone power systems with a power rating that is less than 500 voltamperes); or<br> (ii) a battery system including any associated wiring systems, switchgear, controlgear and accessories. |\n| H    <br>V | Electrical installations located in a hazardous area and electrical equipment associated with the protection of the hazardous area but not installed within the hazardous area.<br>High voltage electrical installations except high voltage electrical equipment that is—<br> (i) associated with an electric discharge lighting system; or<br> (ii) associated with X-ray equipment; or<br> (iii) associated with high frequency equipment; or<br> (iv) within self-contained equipment supplied at low voltage; or<br> (v) associated with electric fences intended primarily for the control or containment of animals. |\n| M | Electrical installations located in a patient area (other than electrical installations associated with communication equipment operating at extra-low voltage). |\n\n\nPart B—Required qualifications, proficiency and experience in electrical inspection work\n\n| *Class* | *Description* |\n| --- | --- |\n| L | 1 A detailed understanding of safety in electrical installations. |\n|  | 2 Testing methods for electrical installations. |\n|  | 3 The requirements of the Regulations relating to consumers mains, main earthing systems, main switchboards and consumer terminals connection devices. |\n| G | 1 A detailed understanding of safety in electrical installations that are covered by this class. |\n|  | 2 Testing methods for electrical installations that are covered by this class. |\n|  | 3 The requirements of the Regulations relating to low voltage electrical installations. |\n| RE | 1 Has the qualifications, proficiency and experience for the person to be issued a licence to carry out class G electrical inspection work under regulation 29. |\n|  | 2 A detailed understanding of safety in electricity generation systems and battery systems. |\n|  | 3 Testing methods for electricity generation systems and battery systems. |\n|  | 4 The requirements of the Regulations relating to electricity generation systems and battery systems. |\n| H | 1 A detailed understanding of safety in electrical installations in hazardous areas. |\n|  | 2 Testing methods in hazardous areas and for electrical equipment associated with the protection of hazardous areas. |\n|  | 3 The requirements of the Regulations relating to electrical installations in hazardous areas and electrical equipment associated with the protection of hazardous areas. |\n| V | 1 A detailed understanding of safety in high voltage electrical installations. |\n|  | 2 Testing methods for high voltage installations. |\n|  | 3 The requirements of the Regulations relating to high voltage electrical installations. |\n| M | 1 A detailed understanding of safety in fixed electrical equipment installed in a patient area. |\n|  | 2 Testing methods for electrical installations in those areas. |\n|  | 3 The requirements of the Regulations relating to those areas. |\n\n\nSchedule 3\n\nRegulations 20, 31, 32, 33 and 34\n\nIn this Schedule—\n\n***associated electrical distribution equipment*** means any of the following—\n\n(a) pole mounted insulators;\n\n(b) pole mounted switchgear including isolators, fuse switches, drop out switches, sectionalisers and surge arrestors;\n\n(c) vibration dampers;\n\n(d) crossarms;\n\n***associated electrical traction equipment*** means any of the following—\n\n(a) pole, tower, stanchion or gantry mounted insulators;\n\n(b) pole, tower, stanchion or gantry mounted switchgear including isolators, fuse switches, drop out switches, sectionalisers and surge arrestors.\n\n***associated electrical transmission equipment*** means insulators, corona rings, aerial ground wires, spacers, shackles, turnbuckles and vibration dampers;\n\n***conductor*** means the whole or any part of a wire, cable or other thing used, or designed to be used, for the purpose of transmitting, distributing or supplying electricity;\n\n***connecting***, in relation to an electrical cable, means the mechanical and electrical connection of electrical cables to each other or to another conductor or electrical equipment in a manner capable of receiving an electric current but does not include jointing;\n\n***distribution supply network*** means a supply network ordinarily operated at a nominal voltage exceeding extra low voltage but not exceeding 66 000 volts;\n\n***jointing***, in relation to an electrical cable, means the joining together of two or more insulated underground electric cables in a manner that meets the specification and construction of the cables being joined;\n\n***MEC distribution supply network*** means a distribution supply network owned or operated by a Major Electricity Company;\n\n***MEC transmission supply network*** means a transmission supply network owned or operated by a Major Electricity Company;\n\n***overhead electrical conductors*** means conductors that are placed above the ground or water and in the open air;\n\n***terminating***, in relation to an electrical cable, means making ready the end of an insulated underground electric cable in a manner suitable for connection to electrical equipment;\n\n***traction supply network*** means the supply network of a railway or tramway;\n\n***transition jointing*** means the joining of two or more cables of differing specification or construction in a manner that maintains, as far as practicable, the characteristics of both cable types;\n\n***transmission supply network*** means a supply network ordinarily operated at a nominal voltage of 66 000 volts or above;\n\n***underground electric cable*** means a conductor placed under the ground and includes any part of the conductor that is at or above the surface of the ground;\n\n***underground service cable*** means an underground electric cable that—\n\n(a) has a cross sectional area no greater than 50 millimetres; and\n\n(b) is the final span or section of an underground MEC distribution supply network used to connect a premises to electricity supply;\n\nPart A—Specified classes of electrical linework that require a licence\n\n| *Class* | *Description* |\n| --- | --- |\n| D | 1 electrical linework carried out on a MEC distribution supply network limited to—<br>(a) the installation, maintenance, modification, stringing, tensioning, terminating, securing, connection and disconnection of overhead electrical conductors; and<br>(b) the installation, maintenance, modification, securing, connection and disconnection of associated electrical distribution equipment; and<br>(c) the connection and disconnection of pole mounted or ground type transformers with an MEC distribution supply network;<br>2 electrical linework limited to the jointing, terminating and connecting of underground service cables to other parts of an underground MEC distribution supply network ordinarily operated at a voltage exceeding extra low voltage but not exceeding low voltage; and<br>3 electrical linework limited to connecting and disconnecting underground electric cables with any above ground parts of an MEC distribution supply network. |\n| T | 1 electrical linework carried out on a MEC transmission supply network limited to—<br>(a) the installation, maintenance, modification, stringing, tensioning, terminating, securing, connection and disconnection of overhead electrical conductors; and<br>(b) the installation, maintenance, modification, securing, connection and disconnection of associated electrical transmission equipment. |\n| R | 1 electrical linework carried out on a traction supply network limited to—<br>(a) the installation, maintenance, modification, stringing, tensioning, terminating, securing, connection and disconnection of overhead electrical conductors, catenary wires and conductor support wires; and<br>(b) the installation, maintenance, modification, securing, connection and disconnection of associated electrical traction equipment. |\n| C | 1 electrical linework carried out on a MEC distribution supply network limited to the jointing, transition jointing, connecting or terminating of underground electric cables; and<br>2 electrical linework carried out on a MEC distribution supply network limited to the connecting of underground electric cables to the de-energised load side terminals of low voltage pole mounted switchgear; and<br>3 electrical linework carried out on a MEC distribution supply network limited to the jointing and terminating of high voltage aerial bundled cables. |\n\n\n**Part B—Required qualifications in electrical linework for a class of lineworker licence**\n\n| *Column 1*<br>*Class* | *Column 2*<br>*Qualifications* |\n| --- | --- |\n| D | 1 Completion of a 4 year contract of training as a lineworker that included at least 12 months experience in carrying out class D electrical linework. |\n|  | 2 Certificate III in ESI-Power Systems-Distribution Overhead. |\n| T | 1 Completion of a 4 year contract of training as a lineworker that included at least 12 months experience in carrying out class T electrical linework. |\n|  | 2 Certificate III in ESI-Power Systems-Transmission Overhead |\n| R | 1 Completion of a 4 year contract of training as a lineworker that included at least 12 months experience in carrying out class R electrical linework |\n|  | 2 Certificate III in ESI-Power Systems-Rail Traction |\n| C | 1 Completion of a 4 year contract of training as a lineworker that included at least 12 months experience in carrying out class C electrical linework |\n|  | 2 Certificate III in ESI-Power Systems-Distribution Cable Jointing |\n\n\n**Note**\n\nRegulation 31(b) provides that Energy Safe Victoria may issue a lineworker licence to a person if the person's standard of qualifications, proficiency and experience in electrical work is at least of an equivalent standard to the requirements set out in Part B of this Schedule.\n\n═════════════\n\nEndnotes\n\n1 General information\n\nSee [www.legislation.vic.gov.au](http://www.legislation.vic.gov.au) for Victorian Bills, Acts and current Versions of legislation and up-to-date legislative information.\n\nThe Electricity Safety (Registration and Licensing) Regulations 2020, S.R. No. 136/2020 were made on 15 December 2020 by the Governor in Council under sections 149, 152, 156 and 157 of the **Electricity Safety Act 1998**, No. 25/1998 and came into operation on 1 January 2021: regulation 3.\n\nThe Electricity Safety (Registration and Licensing) Regulations 2020 will sunset 10 years after the day of making on 15 December 2030 (see section 5 of the **Subordinate Legislation Act 1994**).\n\nINTERPRETATION OF LEGISLATION ACT 1984 (ILA)\n\nStyle changes\n\nSection 54A of the ILA authorises the making of the style changes set out in Schedule 1 to that Act.\n\nReferences to ILA s. 39B\n\nSidenotes which cite ILA s. 39B refer to section 39B of the ILA which provides that where an undivided regulation, rule or clause of a Schedule is amended by the insertion of one or more subregulations, subrules or subclauses the original regulation, rule or clause becomes subregulation, subrule or subclause (1) and is amended by the insertion of the expression \"(1)\" at the beginning of the original regulation, rule or clause.\n\nInterpretation\n\nAs from 1 January 2001, amendments to section 36 of the ILA have the following effects:\n\n• Headings\n\nAll headings included in a Statutory Rule which is made on or after  \n1 January 2001 form part of that Statutory Rule. Any heading inserted in a Statutory Rule which was made before 1 January 2001, by a Statutory Rule made on or after 1 January 2001, forms part of that Statutory Rule.  \nThis includes headings to Parts, Divisions or Subdivisions in a Schedule; Orders; Parts into which an Order is divided; clauses; regulations; rules; items; tables; columns; examples; diagrams; notes or forms.  \nSee section 36(1A)(2A)(2B).\n\n• Examples, diagrams or notes\n\nAll examples, diagrams or notes included in a Statutory Rule which is made on or after 1 January 2001 form part of that Statutory Rule. Any examples, diagrams or notes inserted in a Statutory Rule which was made before 1 January 2001, by a Statutory Rule made on or after 1 January 2001, form part of that Statutory Rule. See section 36(3A).\n\n• Punctuation\n\nAll punctuation included in a Statutory Rule which is made on or after  \n1 January 2001 forms part of that Statutory Rule. Any punctuation inserted in a Statutory Rule which was made before 1 January 2001, by a Statutory Rule made on or after 1 January 2001, forms part of that Statutory Rule.  \nSee section 36(3B).\n\n• Provision numbers\n\nAll provision numbers included in a Statutory Rule form part of that Statutory Rule, whether inserted in the Statutory Rule before, on or after  \n1 January 2001. Provision numbers include regulation numbers, rule numbers, subregulation numbers, subrule numbers, paragraphs and subparagraphs. See section 36(3C).\n\n• Location of \"legislative items\"\n\nA \"legislative item\" is a penalty, an example or a note. As from 13 October 2004, a legislative item relating to a provision of a Statutory Rule is taken to be at the foot of that provision even if it is preceded or followed by another legislative item that relates to that provision. For example, if a penalty at the foot of a provision is followed by a note, both of these legislative items will be regarded as being at the foot of that provision. See section 36B.\n\n• Other material\n\nAny explanatory memorandum, table of provisions, endnotes, index and other material printed after the Endnotes does not form part of a Statutory Rule. See section 36(3)(3D)(3E).\n\n2 Table of Amendments\n\nThis publication incorporates amendments made to the Electricity Safety (Registration and Licensing) Regulations 2020 by statutory rules, subordinate instruments and Acts.\n\n–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––\n\nElectricity Safety (Registration and Licensing) Amendment Regulations 2022, S.R. No. 103/2022\n\n| *Date of Making:* | 4.10.22 |\n| --- | --- |\n| *Date of Commencement:* | Regs 5, 6, 7(2), 8 on 5.10.22: reg. 3(1); reg. 7(1) on 5.4.24: reg. 3(2) |\n\n\n–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––\n\n3 Explanatory details\n\n1. Reg. 4 def. of ***alternative design solution***: S.R. No. 113/2019. [↑](#endnote-ref-2)\n\n2. Reg. 11(b)(iv): S.R. No. 21/2010.\n\n  **——**\n\n  **Fee Units**\n\n  These Regulations provide for fees by reference to fee units within the meaning of the **Monetary Units Act 2004**.\n\n  The amount of the fee is to be calculated, in accordance with section 7 of that Act, by multiplying the number of fee units applicable by the value of a fee unit.\n\n  The value of a fee unit for the financial year commencing 1 July 2023 is $15.90. The amount of the calculated fee may be rounded to the nearest 10 cents.\n\n  The value of a fee unit for future financial years is to be fixed by the Treasurer under section 5 of the **Monetary Units Act 2004**. The value of a fee unit for a financial year must be published in the Government Gazette and a Victorian newspaper before 1 June in the preceding financial year.\n\n  **Penalty Units**\n\n  These Regulations provide for penalties by reference to penalty units within the meaning of section 110 of the **Sentencing Act 1991**. The amount of the penalty is to be calculated, in accordance with section 7 of the **Monetary Units Act 2004**, by multiplying the number of penalty units applicable by the value of a penalty unit.\n\n  The value of a penalty unit for the financial year commencing 1 July 2023 is $192.31. The amount of the calculated penalty may be rounded to the nearest dollar.\n\n  The value of a penalty unit for future financial years is to be fixed by the Treasurer under section 5 of the **Monetary Units Act 2004**. The value of a penalty unit for a financial year must be published in the Government Gazette and a Victorian newspaper before 1 June in the preceding financial year.\n\n  **——**\n\n  **Table of Applied, Adopted or Incorporated Matter**\n\n  The following table of applied, adopted or incorporated matter is included in accordance with the requirements of regulation 5 of the Subordinate Legislation Regulations 2014.\n\n    | **Statutory Rule Provision** | **Title of applied, adopted or incorporated document** | **Matter in applied, adopted or incorporated document** |\n    | --- | --- | --- |\n    | Regulation 4, definitions of ***accessories***, ***Australian/New Zealand Wiring Rules***, ***hazardous area*** | AS/NZS 3000:2018 Electrical Installations (known as the Australian/New Zealand Wiring Rules), 6th edition, published by Standards Australia on 26 June 2018 incorporating amendment No. 1 (January 2020) | Section 1 |\n    | Regulation 4, definitions of ***AS/NZS 3003***, ***patient area*** | AS/NZS 3003:2018 Electrical installations—Patient areas, 6th edition, published by Standards Australia on 26 March 2018 incorporating amendment No. 1 (July 2019) | Section 1 |\n    | Regulation 4, definitions of ***AS/NZS 5139***, ***battery energy storage system*** | AS/NZS 5139:2019 Electrical installations—Safety of battery systems for use with power conversion equipment, published by Standards Australia on 11 October 2019 | Section 1 |\n\n   [↑](#endnote-ref-3)","sortOrder":0}],"analysis":{"kimi_summary":{"content_quality":"ok","complexity_score":7,"scope_assessment":{"changed":false,"description":"The legislation appears consistent with its original intent as stated in regulation 1: providing for registration of electrical contractors, licensing of electrical workers, and prescribing fees and penalties. The 2022 amendments (incorporated in this version) added definitions for battery systems and stand-alone power systems, and updated inspection classes to cover renewable energy systems, but these represent evolutionary updates to keep pace with technology (solar/battery storage) rather than scope creep. The structure remains focused on the core safety regulatory framework established by the parent Electricity Safety Act 1998."},"complexity_factors":["47 defined terms in the interpretation section (regulation 4), many cross-referencing external standards (AS/NZS 3000, 3003, 5139) and other regulations","Multiple nested conditional requirements for registration and licensing with alternative pathways (e.g., regulation 10 has 3 sub-pathways for supervision qualifications plus experience-based equivalents)","Complex supervisor nomination requirements with cascading conditions—different rules apply depending on whether the contractor is a natural person vs body corporate, and whether they personally hold electrician vs switchgear qualifications (regulations 7, 9, 13)","15 distinct licence classes across three categories (installation, inspection, linework) with specific eligibility criteria, experience requirements, and examination prerequisites (regulations 22-33)","Extensive cross-referencing to external documents—Australian/New Zealand Wiring Rules, Certificate III qualifications, and assessments conducted by approved bodies","Grandfathering provisions for transitional licences (regulations 24, 25, 30) that reference repealed 2010 regulations","Detailed schedules (Schedules 1-3) containing tabular data on occupational areas, inspection classes, and linework qualifications that are integral to the operational provisions","Conditional fee structures with waivers, rebates, and refunds based on timing, licence class, and specific circumstances (Part 5)","Multiple penalty provisions scattered throughout (regulations 14, 17, 39-41) with specific penalty unit amounts"],"plain_english_summary":"This legislation sets out the rules for who can legally do electrical work in Victoria and how they get permission to do it. It covers two main groups: **electrical contractors** (businesses that employ electricians) and **electrical workers** (the individual electricians and lineworkers themselves).\n\n**For electrical contractors:**\n- Businesses must register with Energy Safe Victoria (the safety regulator) before they can legally contract to do electrical work\n- They must have proper insurance ($5 million minimum)\n- They need qualified supervisors—either the business owner or nominated technical supervisors who are licensed electricians\n- They must also have someone responsible for business management who understands how to run an electrical business\n- Registration lasts 5 years and must be renewed\n\n**For electrical workers:**\n- Individuals need specific licences to do different types of electrical work, including:\n  - **Electrician's licence**—for general electrical installation work\n  - **Restricted licences**—for workers in other trades (like refrigeration or plumbing) who need to do limited electrical work as part of their main job\n  - **Lineworker licences**—for working on power lines and networks (with different classes for distribution, transmission, and railway systems)\n  - **Inspector's licences**—for checking that electrical work meets safety standards\n- Most licences require completing apprenticeships, holding specific certificates, and passing assessments\n- Workers must do ongoing professional development (up to 16 hours per renewal period) to keep their licences\n- Licences can be refused or cancelled for criminal convictions, incompetence, or breaking safety laws\n\n**Why it matters:**\nThis system protects the public from dangerous electrical work. Unlicensed electrical work can cause fires, electrocution, or death. The rules ensure only properly trained, supervised, and insured people work on electrical systems—from home wiring to high-voltage transmission lines."},"flash_summary":{"complexity_score":7,"scope_assessment":{"changed":true,"description":"Since the original Regulations, later amendments (notably S.R. No. 103/2022) have broadened scope and updated technical coverage. Conspicuous changes include: explicit treatment of battery storage and ‘‘battery system’’ definitions and stand-alone power systems (Reg 4 insertions), amendments to inspection classes and qualifications (Schedule 2 amendments), and insertion of a selective provision permitting partial licensing for inspection work (reg 29(1A)). These changes extend the Regulations beyond a narrow registration/licensing framework to address emerging technologies (battery energy storage and generation systems) and to refine inspection and lineworker class coverage. The result is an instrument that now covers a wider range of equipment and work types, increases regulator discretion to specify competencies and CPD, and provides transitional arrangements and waivers for lineworkers — expanding administrative scope and regulatory reach compared with the original, more narrowly focused 2020 text."},"complexity_factors":["Single interpretation section (Regulation 4) containing around 50 defined terms and technical cross-references to AS/NZS standards (AS/NZS 3000, 3003, 5139).","Multiple licence and registration types: ~16 distinct licence/registration variations (electrician, supervised electrician, electrician (supervised) transition, occupier, switchgear worker, restricted class 1 and 2, electrical inspector, class 'L' inspector transition, lineworker classes D/T/R/C, supervised/ restricted lineworker variants).","Extensive conditional qualification routes and equivalence tests (Reg 10 and regs 22–31 allow multiple alternative assessment paths: formal qualifications, regulator assessments, or regulator-assessed equivalence).","Nested rules and exceptions: conditions of registration (Reg 13) and licence conditions (regs 27–29, 33) contain multi-level conditional logic (who supervises whom, when nominations cease, limits to occupational areas).","Schedules with technical breakdowns: Schedule 2 (inspection classes and required competencies) and Schedule 3 (linework classes and required qualifications) add cross-references and granular scope distinctions.","Delegated rulemaking: important content (continuing professional development content and other operational details) is set by Energy Safe Victoria via public notice (Reg 36), increasing reliance on external administrative instruments.","Multiple time limits and currency requirements: assessments/examinations must have been completed within 5 years for many applications/renewals (Regs 10(4), 22(3), 26(2), 27(4), 28(4), 29(2)).","Fees, waivers, rebates and refund rules with specific thresholds and transitional waivers (Part 5, Regs 42–45) add administrative complexity for applicants and the regulator.","Cross-jurisdictional recognition: definitions and regulatory authority provisions allow recognition of licensing in other Australian states, territories and New Zealand, adding equivalence assessment complexity (Reg 4).","Infringement notice mapping: specific provisions across the instrument are designated as enforceable by infringement notices (Reg 46) and penalty units are employed throughout, requiring parallel calculation rules (Endnotes re: fee/penalty units)."],"plain_english_summary":"**What these Regulations do (mechanics first)**\n\n- Establish a system for registering electrical contractors and licensing individual electrical workers in Victoria. (Regs 1, 7, 21)\n- Define the classes of work that require registration or a licence (installation, inspection, linework, battery/generation work and certain restricted tasks) and set which licence or registration covers each class. (Regs 5, 18–20; Schedules 2–3)\n- Set the information, qualifications and evidence applicants must supply, the assessments or equivalent standards required, and time limits on when assessments must have been completed. (Regs 7, 10, 21–31)\n- Require supervision and set what “effective supervision” means for apprentices, supervised licences and registered contractors. (Regs 4 definition of “effective supervision”, 13, 23, 38)\n- Prescribe minimum insurance for registered contractors ($5,000,000 public liability) and require contractors to hold it when carrying out contracting work. (Reg 12, 7(2)(i))\n- Create an electronic public register of electrical contractors and provide registration and licence cards that must be signed and produced on demand by enforcement officers. (Regs 16–17, 40–41)\n- Provide fee levels, fee waivers or rebates for certain circumstances, renewal rules and continuing professional development (CPD) requirements (delegated to Energy Safe Victoria by notice). (Part 5; Regs 35–36)\n- Identify specified offences for which infringement notices may be issued and set penalties by reference to penalty units. (Reg 46; various penalty clauses)\n\n**Who this affects**\n\n- Individuals who perform or wish to perform electrical installation, inspection or linework in Victoria (electricians, switchgear fitters, inspectors, lineworkers, apprentices, and people applying for restricted licences). (Part 3; Schedules 2–3)\n- Businesses that carry out electrical contracting — they must register, nominate supervisors and hold prescribed insurance. (Part 2, regs 7–14)\n- Employers who nominate supervised workers or sponsor licence applications for restricted or supervised lineworkers. (Regs 21(3)(c), 32, 33)\n- Energy Safe Victoria, which decides applications, sets CPD by public notice, may impose conditions, and publishes the register. (Regs 9, 29(1A), 36, 16)\n\n**Why it matters (official purpose and practical implications)**\n\n- The Regulations say their objectives are to provide for registration, licensing, prescribe fees and infringement notice provisions (Reg 1). Mechanically, they implement those objectives by spelling out who must be registered or licensed, the minimum qualifications/assessments, supervision rules, insurance, and enforcement tools.\n\n- Who pays: applicants and licence-holders pay application and renewal fees (Part 5; Regs 8, 21(5)–(6), 35(5)–(6)); registered contractors must obtain and fund public liability insurance (Reg 12). Penalties for breaches are payable by the offender (see penalty unit references and specific penalty clauses such as regs 14(1) and 39).\n\n- Who decides: Energy Safe Victoria is the regulator with broad discretion to:\n  - accept equivalent qualifications/experience in place of specified awards or assessments (Regs 10(1)(c), 22(2)(b), 26(1)(b), 31(b));\n  - impose licence conditions (e.g. limit restricted licences to occupational areas, regs 27(5), 28(5));\n  - require extra material, conduct or accept assessments, set CPD by public notice, and publish the contractor register (Regs 7(4), 29(1)(a)(ii)–(iii), 36(1), 16(3)).\n\n**Trade-offs, incentives and implementation risks**\n\n- Compliance costs: the Regulations increase compliance tasks (application paperwork, costly assessments, CPD hours, insurance, record updates within 10 business days (reg 14(1))). These are concentrated costs on contractors and individual workers.\n\n- Barriers and scope of work: multiple licence classes and restricted licences (regs 27–28, Schedules 1–3) create narrow permissions for some workers; Energy Safe Victoria can limit or phase out supervised/restricted classes (reg 34(2)–(3)), which can raise switching costs for employers and employees and affect workforce supply for particular tasks.\n\n- Delegation and discretion: the regulator can recognise “equivalent” qualifications and set CPD by notice (Regs 10, 29, 36). That provides flexibility for recognising non-standard training and adapting to technology (e.g. battery systems), but gives the regulator significant administrative discretion — implementation depends on clarity and timeliness of published requirements.\n\n- Market effects: registration, insurance and assessment requirements raise the fixed cost of supplying electrical contracting services. This can reduce entry by marginal providers, potentially favouring established businesses that can absorb administrative costs (see regs 7–13, 12). Fee waivers and rebates for certain additions or initial transition periods (Regs 42–45) mitigate some transitional burdens.\n\n- Safety vs productivity trade-off: supervision and mandatory assessments (Regs 10, 13, 23, 38) are designed to raise safety and competency standards; they also constrain how quickly firms can deploy less-experienced staff without a supervising licensed person present.\n\n- Scope for substitution and unintended consequences: the Regulations allow restricted licences tied to an employee’s primary work function (regs 27–28), which can shift some electrical tasks in-house to non-electrician staff with restricted licences rather than hiring electricians — potentially lowering costs but raising risk if supervision/competence limits are not effectively enforced.\n\n**Notable delegated/technical features**\n\n- Many standards and technical definitions are imported by reference to Australian/New Zealand Standards (AS/NZS 3000, AS/NZS 3003, AS/NZS 5139) (Reg 4; Endnotes). This keeps technical content aligned to external standards but links regulatory outcomes to amendments of those standards.\n\n- CPD is capped per renewal period (max 8 hours skills maintenance and 8 hours skills development) but the content and timing are specified by public notice rather than in the Regulations (Reg 36).\n\n**Sections to look at first if you are affected**\n\n- Contractors: registration requirements, nominated supervisors, insurance and obligations — regs 7–17 and 12.\n- Individual workers: licence classes, qualification/assessment requirements and renewal/CPD — regs 21–37 and Schedules 2–3.\n- Employers: obligations for supervised licences and statements for restricted/lineworker applications — regs 21(3)(c), 32–33.\n\n**Concrete operational effects (who pays, who decides, what changes)**\n\n- Employers and electrical contractors pay fees, insurance and bear administrative costs for nominations and notifications (Regs 8, 12, 14).\n- Energy Safe Victoria decides acceptance of equivalence, issues licences/registrations, sets CPD by notice and publishes the register (Regs 9, 29(1A), 36, 16(3)).\n- Workers will change behaviour to either obtain required assessments, seek supervised licences, or work under nominated supervisors; apprentices must be effectively supervised (Reg 38).\n\n(Official rationale: Reg 1 states the objectives as registration, licensing, prescribing fees/penalties and prescribing infringement notice offences. The Regulations implement that mechanically, while delegating technical competency and CPD details to the regulator and drawing on external standards for technical definitions.)"},"summary":{"complexity_score":4,"scope_assessment":{"changed":false,"description":"Based on available information, these regulations appear to operate within their originally intended scope — establishing a licensing and registration framework for electrical workers and businesses in Victoria under the Electricity Safety Act 1998. No significant scope creep or departure from original intent is apparent, though the limited content in the source document prevents a definitive assessment."},"complexity_factors":["Regulatory licensing schemes typically involve multiple licence categories and tiers, each with different requirements","Interaction with parent legislation (Electricity Safety Act 1998 Vic) adds a layer of complexity","Registration and renewal processes often involve administrative procedures that can be confusing for individuals","The source document provided was largely metadata and version history with minimal substantive content, limiting full analysis","Compliance obligations differ between individual workers and business entities, creating parallel regulatory tracks"],"plain_english_summary":"These Victorian regulations set who may legally carry out electrical work by requiring electricians, electrical workers and electrical businesses to hold proper licences or registration and meet safety standards. \n\nThey affect individual tradespeople, contractors, employers and anyone hiring electrical services — protecting the public by reducing risks like fire or electrocution and creating penalties for unlicensed work."},"issue_detection":{"absurdities":[{"type":"other","section":"regulation 9(d), read with regulations 7(2)(b), 9(a)(i) and 9(c)","severity":"high","reasoning":"Regulation 7(2)(b) provides for nomination where the applicant will not supervise. Regulation 9(a)(i)(B) is the corresponding natural-person nomination path, while 9(a)(i)(A) is the applicant-self-supervision path. Regulation 9(d) instead refers to a person nominated under an application to which 9(a)(i)(A) or 9(b)(i) relates. No person is nominated through 9(a)(i)(A), and 9(a)(i)(B) is omitted. Regulation 9(c) checks only an applicant who will personally supervise. Consequently, the supplied text contains no qualification check for the natural-person nominee path in 9(a)(i)(B).","confidence":0.99,"description":"A broken cross-reference omits the qualification check for a technical supervisor nominated by a natural-person applicant.","source_quotes":["(A) will be responsible for the effective supervision of the electrical installation work or only electrical switchgear fitting work carried out on behalf of the applicant; or\n\n(B) has nominated a natural person or a sufficient number of natural persons to be technical supervisors who will be 负责 for","(d) each person nominated under an application to which paragraph (a)(i)(A) or (b)(i) relates to be responsible for the effective supervision of electrical installation work or only electrical switchgear fitting work is a licensed electrician or a licensed electrical switchgear worker who has rese 责","(c) if the applicant will be responsible for the effective supervision of the electrical installation work or only electrical switchgear fitting work, that the applicant is a licensed electrician or a licensed electrical switchgear worker who has completed the requirements specified in regulation 10"]}],"contradictions":[]},"flash_summary_failed":{"failed":true,"reason":"A positive credit balance is required for all requests, including BYOK, so fallback providers remain available. Add credits at https://vercel.com/d?to=%2F%5Bteam%5D%2F%7E%2Fai%3Fmodal%3Dtop-up to continue.","source":"analysis-cron"}},"importantCases":[],"_links":{"self":"/api/acts/electricity-safety-registration-and-licensing-regulations-2020","history":"/api/acts/electricity-safety-registration-and-licensing-regulations-2020/history","analysis":"/api/acts/electricity-safety-registration-and-licensing-regulations-2020/analysis","conflicts":"/api/acts/electricity-safety-registration-and-licensing-regulations-2020/conflicts","importantCases":"/api/acts/electricity-safety-registration-and-licensing-regulations-2020/important-cases","documents":"/api/acts/electricity-safety-registration-and-licensing-regulations-2020/documents"}}