{"id":"qld:sl-2026-0113","name":"Electrical Safety Regulation 2026","slug":"electrical-safety-regulation-2026","collection":"regulation","jurisdiction":"qld","status":"in_force","isInForce":true,"actNumber":"113 of 2026","makingDate":null,"administeringDepartment":null,"currentVersion":{"id":580013,"registerId":"qld-qld:sl-2026-0113-current","compilationNumber":null,"startDate":"2026-09-01","status":"InForce","reasons":null,"registeredAt":null},"sections":[{"sectionNumber":"pt.1","sectionType":"part","heading":"Preliminary","content":"# Preliminary","sortOrder":0},{"sectionNumber":"pt.1-div.1","sectionType":"division","heading":"Introduction","content":"## Introduction","sortOrder":1},{"sectionNumber":"sec.1","sectionType":"section","heading":"Short title","content":"### sec.1 Short title\n\nThis regulation may be cited as the Electrical Safety Regulation 2026 .","sortOrder":2},{"sectionNumber":"sec.2","sectionType":"section","heading":"Commencement","content":"### sec.2 Commencement\n\nThis regulation commences on 1 September 2026.","sortOrder":3},{"sectionNumber":"pt.1-div.2","sectionType":"division","heading":"Application","content":"## Application","sortOrder":4},{"sectionNumber":"sec.3","sectionType":"section","heading":"Application of this regulation","content":"### sec.3 Application of this regulation\n\nA duty imposed on a person under a provision of this regulation in relation to electrical safety does not limit or affect any duty the person has under the Act or, unless otherwise expressly provided, any other provision of this regulation.","sortOrder":5},{"sectionNumber":"sec.4","sectionType":"section","heading":"Application of regulation at mines and petroleum plants— Act , s&#160;6","content":"### sec.4 Application of regulation at mines and petroleum plants— Act , s&#160;6\n\nFor section&#160;6 (2) (b) of the Act , the following provisions of this regulation have application at a mine or petroleum plant—\npart&#160;1 ;\npart&#160;4 ;\npart&#160;5 , divisions&#160;1 and 2 ;\npart&#160;7 , other than to the extent it relates to electrical contractor licences;\npart&#160;13 ;\npart&#160;14 .\nFor subsection&#160;(1) (f) , a reference in part&#160;14 to a dangerous electrical event does not include a reference to a matter mentioned in section&#160;12 (a) , (b) or (c) of the Act if the matter is required to be notified to an inspector or chief inspector under—\nthe Coal Mining Safety and Health Act 1999 ; or\nthe Mining and Quarrying Safety and Health Act 1999 ; or\nthe Petroleum and Gas (Production and Safety) Act 2004 .\n(sec.4-ssec.1) For section&#160;6 (2) (b) of the Act , the following provisions of this regulation have application at a mine or petroleum plant— part&#160;1 ; part&#160;4 ; part&#160;5 , divisions&#160;1 and 2 ; part&#160;7 , other than to the extent it relates to electrical contractor licences; part&#160;13 ; part&#160;14 .\n(sec.4-ssec.2) For subsection&#160;(1) (f) , a reference in part&#160;14 to a dangerous electrical event does not include a reference to a matter mentioned in section&#160;12 (a) , (b) or (c) of the Act if the matter is required to be notified to an inspector or chief inspector under— the Coal Mining Safety and Health Act 1999 ; or the Mining and Quarrying Safety and Health Act 1999 ; or the Petroleum and Gas (Production and Safety) Act 2004 .\n- (a) part&#160;1 ;\n- (b) part&#160;4 ;\n- (c) part&#160;5 , divisions&#160;1 and 2 ;\n- (d) part&#160;7 , other than to the extent it relates to electrical contractor licences;\n- (e) part&#160;13 ;\n- (f) part&#160;14 .\n- (a) the Coal Mining Safety and Health Act 1999 ; or\n- (b) the Mining and Quarrying Safety and Health Act 1999 ; or\n- (c) the Petroleum and Gas (Production and Safety) Act 2004 .","sortOrder":6},{"sectionNumber":"sec.5","sectionType":"section","heading":"Prescribed workplaces— Act , s&#160;18","content":"### sec.5 Prescribed workplaces— Act , s&#160;18\n\nFor section&#160;18 (2) (d) of the Act , a workplace is prescribed if activities of a kind stated in schedule&#160;1 are carried out at the workplace.\nSchedule&#160;1 categorises workplaces according to the activities carried out at the workplaces using a system known as the Australian and New Zealand Standard Industrial Classification ( ANZSIC ).\nA category of workplace stated in schedule&#160;1 , column 2 has the ANZSIC class stated in column 1 of the schedule.\n(sec.5-ssec.1) For section&#160;18 (2) (d) of the Act , a workplace is prescribed if activities of a kind stated in schedule&#160;1 are carried out at the workplace.\n(sec.5-ssec.2) Schedule&#160;1 categorises workplaces according to the activities carried out at the workplaces using a system known as the Australian and New Zealand Standard Industrial Classification ( ANZSIC ).\n(sec.5-ssec.3) A category of workplace stated in schedule&#160;1 , column 2 has the ANZSIC class stated in column 1 of the schedule.","sortOrder":7},{"sectionNumber":"pt.1-div.3","sectionType":"division","heading":"Interpretation","content":"## Interpretation","sortOrder":8},{"sectionNumber":"sec.6","sectionType":"section","heading":"Definitions","content":"### sec.6 Definitions\n\nThe dictionary in schedule&#160;10 defines particular words used in this regulation.\nIf a word used in this regulation is not defined in this regulation or the Act , but is used in the wiring rules, it has, to the greatest practicable extent, the same meaning in this regulation as it has in the wiring rules.\ncircuit breaker\nfuse\nhazardous area\nluminaire\nresidual current device (RCD)\n(sec.6-ssec.1) The dictionary in schedule&#160;10 defines particular words used in this regulation.\n(sec.6-ssec.2) If a word used in this regulation is not defined in this regulation or the Act , but is used in the wiring rules, it has, to the greatest practicable extent, the same meaning in this regulation as it has in the wiring rules. circuit breaker fuse hazardous area luminaire residual current device (RCD)\n- • circuit breaker\n- • fuse\n- • hazardous area\n- • luminaire\n- • residual current device (RCD)","sortOrder":9},{"sectionNumber":"sec.7","sectionType":"section","heading":"Provisions linked to electrical safety duties in Act","content":"### sec.7 Provisions linked to electrical safety duties in Act\n\nEach of the following provisions states the way a person’s electrical safety duty under section&#160;30 of the Act is to be performed in relation to the matters and to the extent stated in the provision—\nsections&#160;12 and 18 (1) ;\nsections&#160;38 (1) , 39 , 40 , 41 (1) , 44 (1) , 45 (1) and 46 ;\nsections&#160;127 , 128 (1) – (4) , 129 (1) – (5) , 130 (1) – (4) , 132 , 133 (1) – (6) , 136 (1) – (4) , 138 (1) – (4) , 139 (1) – (4) , 140 (1) – (5) and 141 (1) – (5) .\nSection&#160;38 (2) states the way a worker’s electrical safety duty under section&#160;39 of the Act is to be performed in relation to the matters and to the extent stated in section&#160;38 (2) .\n(sec.7-ssec.1) Each of the following provisions states the way a person’s electrical safety duty under section&#160;30 of the Act is to be performed in relation to the matters and to the extent stated in the provision— sections&#160;12 and 18 (1) ; sections&#160;38 (1) , 39 , 40 , 41 (1) , 44 (1) , 45 (1) and 46 ; sections&#160;127 , 128 (1) – (4) , 129 (1) – (5) , 130 (1) – (4) , 132 , 133 (1) – (6) , 136 (1) – (4) , 138 (1) – (4) , 139 (1) – (4) , 140 (1) – (5) and 141 (1) – (5) .\n(sec.7-ssec.2) Section&#160;38 (2) states the way a worker’s electrical safety duty under section&#160;39 of the Act is to be performed in relation to the matters and to the extent stated in section&#160;38 (2) .\n- (a) sections&#160;12 and 18 (1) ;\n- (b) sections&#160;38 (1) , 39 , 40 , 41 (1) , 44 (1) , 45 (1) and 46 ;\n- (c) sections&#160;127 , 128 (1) – (4) , 129 (1) – (5) , 130 (1) – (4) , 132 , 133 (1) – (6) , 136 (1) – (4) , 138 (1) – (4) , 139 (1) – (4) , 140 (1) – (5) and 141 (1) – (5) .","sortOrder":10},{"sectionNumber":"sec.8","sectionType":"section","heading":"Assessment of risk in relation to classes of hazards, tasks, circumstances or things","content":"### sec.8 Assessment of risk in relation to classes of hazards, tasks, circumstances or things\n\nIf this regulation requires an assessment of risks to electrical safety associated with a hazard, task, thing or circumstance, an assessment of risks associated with a class of hazards, tasks, things or circumstances may be conducted if—\nall hazards, tasks, things or circumstances in the class are the same; and\nthe assessment of risks for the class does not result in any worker or other person being exposed to a greater, additional or different risk to electrical safety than if the risk assessment were carried out in relation to each individual hazard, task, thing or circumstance.\n- (a) all hazards, tasks, things or circumstances in the class are the same; and\n- (b) the assessment of risks for the class does not result in any worker or other person being exposed to a greater, additional or different risk to electrical safety than if the risk assessment were carried out in relation to each individual hazard, task, thing or circumstance.","sortOrder":11},{"sectionNumber":"sec.9","sectionType":"section","heading":"References to standards and other documents","content":"### sec.9 References to standards and other documents\n\nIn this regulation, unless otherwise stated—\na reference to a standard using the designation made up of ‘AS’ and a number is a reference to the standard as in effect from time to time under that designation; and\n‘AS 1319’ is a reference to the standard currently in effect under that designation.\na reference to a joint standard using the designation made up of ‘AS/NZS’ and a number is a reference to the joint standard as in effect from time to time under that designation.\n‘AS/NZS 3012’ is a reference to the joint standard currently in effect under that designation.\nSubsection&#160;(1) applies regardless of the edition or year of the standard or joint standard.\nIn this regulation, a reference to AS/NZS 3000 is a reference to that standard as amended from time to time, and as remade from time to time.\nBracketed words appearing after a standard’s designation are included for information purposes only.\n(sec.9-ssec.1) In this regulation, unless otherwise stated— a reference to a standard using the designation made up of ‘AS’ and a number is a reference to the standard as in effect from time to time under that designation; and ‘AS 1319’ is a reference to the standard currently in effect under that designation. a reference to a joint standard using the designation made up of ‘AS/NZS’ and a number is a reference to the joint standard as in effect from time to time under that designation. ‘AS/NZS 3012’ is a reference to the joint standard currently in effect under that designation.\n(sec.9-ssec.2) Subsection&#160;(1) applies regardless of the edition or year of the standard or joint standard. In this regulation, a reference to AS/NZS 3000 is a reference to that standard as amended from time to time, and as remade from time to time.\n(sec.9-ssec.3) Bracketed words appearing after a standard’s designation are included for information purposes only.\n- (a) a reference to a standard using the designation made up of ‘AS’ and a number is a reference to the standard as in effect from time to time under that designation; and Example— ‘AS 1319’ is a reference to the standard currently in effect under that designation.\n- (b) a reference to a joint standard using the designation made up of ‘AS/NZS’ and a number is a reference to the joint standard as in effect from time to time under that designation. Example— ‘AS/NZS 3012’ is a reference to the joint standard currently in effect under that designation.","sortOrder":12},{"sectionNumber":"sec.10","sectionType":"section","heading":"Meaning of exclusion zone for persons, operating plant and vehicles for overhead electric lines","content":"### sec.10 Meaning of exclusion zone for persons, operating plant and vehicles for overhead electric lines\n\nThis section applies in relation to the following—\na person;\noperating plant;\na vehicle.\nA person or thing mentioned in subsection&#160;(1) comes within an exclusion zone for an overhead electric line if the person or thing comes within the distance from the line stated for the person or thing in schedule&#160;2 .\n(sec.10-ssec.1) This section applies in relation to the following— a person; operating plant; a vehicle.\n(sec.10-ssec.2) A person or thing mentioned in subsection&#160;(1) comes within an exclusion zone for an overhead electric line if the person or thing comes within the distance from the line stated for the person or thing in schedule&#160;2 .\n- (a) a person;\n- (b) operating plant;\n- (c) a vehicle.","sortOrder":13},{"sectionNumber":"sec.11","sectionType":"section","heading":"Meaning of unsafe distance for persons, operating plant and vehicles for overhead electric lines","content":"### sec.11 Meaning of unsafe distance for persons, operating plant and vehicles for overhead electric lines\n\nThis section applies in relation to the following—\na person;\noperating plant;\na vehicle.\nA person or thing mentioned in subsection&#160;(1) comes within an unsafe distance of an overhead electric line if the person or thing is within the exclusion zone for the person or thing for the line.\nFor applying this section—\na person includes any article of clothing worn by the person, and any conductive object the person is handling; and\noperating plant includes anything the operating plant is handling, other than—\na person; or\na handheld object a person is handling; and\na vehicle includes anything the vehicle is carrying or otherwise handling.\nDespite subsection&#160;(3) , the person or thing does not include an object that—\nalone, or with 1 or more other objects, is an extension from the person or thing; and\nis insulated; and\nhas been tested and found to be safe for use on and near the electric line.\nIn this section—\nconductive object means a tool or other object readily able to conduct electricity.\n(sec.11-ssec.1) This section applies in relation to the following— a person; operating plant; a vehicle.\n(sec.11-ssec.2) A person or thing mentioned in subsection&#160;(1) comes within an unsafe distance of an overhead electric line if the person or thing is within the exclusion zone for the person or thing for the line.\n(sec.11-ssec.3) For applying this section— a person includes any article of clothing worn by the person, and any conductive object the person is handling; and operating plant includes anything the operating plant is handling, other than— a person; or a handheld object a person is handling; and a vehicle includes anything the vehicle is carrying or otherwise handling.\n(sec.11-ssec.4) Despite subsection&#160;(3) , the person or thing does not include an object that— alone, or with 1 or more other objects, is an extension from the person or thing; and is insulated; and has been tested and found to be safe for use on and near the electric line.\n(sec.11-ssec.5) In this section— conductive object means a tool or other object readily able to conduct electricity.\n- (a) a person;\n- (b) operating plant;\n- (c) a vehicle.\n- (a) a person includes any article of clothing worn by the person, and any conductive object the person is handling; and\n- (b) operating plant includes anything the operating plant is handling, other than— (i) a person; or (ii) a handheld object a person is handling; and\n- (i) a person; or\n- (ii) a handheld object a person is handling; and\n- (c) a vehicle includes anything the vehicle is carrying or otherwise handling.\n- (i) a person; or\n- (ii) a handheld object a person is handling; and\n- (a) alone, or with 1 or more other objects, is an extension from the person or thing; and\n- (b) is insulated; and\n- (c) has been tested and found to be safe for use on and near the electric line.","sortOrder":14},{"sectionNumber":"pt.2","sectionType":"part","heading":"General duties of person conducting a business or undertaking","content":"# General duties of person conducting a business or undertaking","sortOrder":15},{"sectionNumber":"pt.2-div.1","sectionType":"division","heading":"All persons conducting a business or undertaking at a workplace","content":"## All persons conducting a business or undertaking at a workplace","sortOrder":16},{"sectionNumber":"sec.12","sectionType":"section","heading":"Risk management","content":"### sec.12 Risk management\n\nA person conducting a business or undertaking at a workplace must manage risks to health and safety associated with electrical risks at the workplace in accordance with the WHS Regulation , chapter&#160;3 , part&#160;3.1 .\nelectrical risks associated with the design, construction, installation, protection, maintenance and testing of electrical equipment and electrical installations at the workplace\nThis section is linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).","sortOrder":17},{"sectionNumber":"sec.13","sectionType":"section","heading":"No person, plant or thing to come within unsafe distance of overhead electric line","content":"### sec.13 No person, plant or thing to come within unsafe distance of overhead electric line\n\nA person conducting a business or undertaking at a workplace must ensure, so far as is reasonably practicable, that no person, plant or thing at the workplace comes within an unsafe distance of an overhead electric line.\nMaximum penalty—60 penalty units.\nIf it is not reasonably practicable to ensure the safe distance of a person, plant or thing from an overhead electric line, the person conducting the business or undertaking must ensure that—\na risk assessment is conducted for proposed work that may come within an unsafe distance of an overhead electric line; and\ncontrol measures implemented are consistent with—\nthe risk assessment; and\nif an electricity entity is responsible for the electric line—any requirements of the entity.\nMaximum penalty—60 penalty units.\n(sec.13-ssec.1) A person conducting a business or undertaking at a workplace must ensure, so far as is reasonably practicable, that no person, plant or thing at the workplace comes within an unsafe distance of an overhead electric line. Maximum penalty—60 penalty units.\n(sec.13-ssec.2) If it is not reasonably practicable to ensure the safe distance of a person, plant or thing from an overhead electric line, the person conducting the business or undertaking must ensure that— a risk assessment is conducted for proposed work that may come within an unsafe distance of an overhead electric line; and control measures implemented are consistent with— the risk assessment; and if an electricity entity is responsible for the electric line—any requirements of the entity. Maximum penalty—60 penalty units.\n- (a) a risk assessment is conducted for proposed work that may come within an unsafe distance of an overhead electric line; and\n- (b) control measures implemented are consistent with— (i) the risk assessment; and (ii) if an electricity entity is responsible for the electric line—any requirements of the entity.\n- (i) the risk assessment; and\n- (ii) if an electricity entity is responsible for the electric line—any requirements of the entity.\n- (i) the risk assessment; and\n- (ii) if an electricity entity is responsible for the electric line—any requirements of the entity.","sortOrder":18},{"sectionNumber":"sec.14","sectionType":"section","heading":"No person, plant or thing to damage underground electric line","content":"### sec.14 No person, plant or thing to damage underground electric line\n\nA person conducting a business or undertaking at a workplace must ensure, so far as is reasonably practicable, that no person, plant or thing at the workplace damages an underground electric line.\nMaximum penalty—60 penalty units.","sortOrder":19},{"sectionNumber":"sec.15","sectionType":"section","heading":"Measures to avoid risk of contact with underground electric line","content":"### sec.15 Measures to avoid risk of contact with underground electric line\n\nThis section applies if work to be carried out at a workplace involves a risk of contact with an underground electric line.\nA person conducting a business or undertaking at the workplace must ensure that—\na risk assessment is conducted for the proposed work; and\ncontrol measures implemented are consistent with—\nthe risk assessment; and\nif an electricity entity is responsible for the electric line—any requirements of the entity.\nMaximum penalty—60 penalty units.\n(sec.15-ssec.1) This section applies if work to be carried out at a workplace involves a risk of contact with an underground electric line.\n(sec.15-ssec.2) A person conducting a business or undertaking at the workplace must ensure that— a risk assessment is conducted for the proposed work; and control measures implemented are consistent with— the risk assessment; and if an electricity entity is responsible for the electric line—any requirements of the entity.\n- (a) a risk assessment is conducted for the proposed work; and\n- (b) control measures implemented are consistent with— (i) the risk assessment; and (ii) if an electricity entity is responsible for the electric line—any requirements of the entity.\n- (i) the risk assessment; and\n- (ii) if an electricity entity is responsible for the electric line—any requirements of the entity.\n- (i) the risk assessment; and\n- (ii) if an electricity entity is responsible for the electric line—any requirements of the entity.","sortOrder":20},{"sectionNumber":"pt.2-div.2","sectionType":"division","heading":"Persons conducting a business or undertaking if worker performs work","content":"## Persons conducting a business or undertaking if worker performs work","sortOrder":21},{"sectionNumber":"sec.16","sectionType":"section","heading":"Application of division","content":"### sec.16 Application of division\n\nThis division applies to a person conducting a business or undertaking if the person, or a worker carrying out work for the person, performs work, whether or not electrical work, at a workplace.\nSee section&#160;22 (3) of the Act for when the person conducting the business or undertaking is also a worker.","sortOrder":22},{"sectionNumber":"sec.17","sectionType":"section","heading":"Unsafe electrical equipment","content":"### sec.17 Unsafe electrical equipment\n\nThe person conducting the business or undertaking must ensure any unsafe electrical equipment at the workplace—\nis disconnected, or isolated, from its electricity supply; and\nonce disconnected or isolated—\nis not reconnected until it is repaired or tested and found to be safe; or\nis replaced or permanently removed from use.\nMaximum penalty—36 penalty units.\nFor applying this section, electrical equipment or a component of electrical equipment is unsafe if there are reasonable grounds for believing it to be unsafe.\nHowever, subsection&#160;(1) does not apply to a person conducting a business or undertaking in relation to electrical equipment that is not under the person’s management or control.\n(sec.17-ssec.1) The person conducting the business or undertaking must ensure any unsafe electrical equipment at the workplace— is disconnected, or isolated, from its electricity supply; and once disconnected or isolated— is not reconnected until it is repaired or tested and found to be safe; or is replaced or permanently removed from use. Maximum penalty—36 penalty units.\n(sec.17-ssec.2) For applying this section, electrical equipment or a component of electrical equipment is unsafe if there are reasonable grounds for believing it to be unsafe.\n(sec.17-ssec.3) However, subsection&#160;(1) does not apply to a person conducting a business or undertaking in relation to electrical equipment that is not under the person’s management or control.\n- (a) is disconnected, or isolated, from its electricity supply; and\n- (b) once disconnected or isolated— (i) is not reconnected until it is repaired or tested and found to be safe; or (ii) is replaced or permanently removed from use.\n- (i) is not reconnected until it is repaired or tested and found to be safe; or\n- (ii) is replaced or permanently removed from use.\n- (i) is not reconnected until it is repaired or tested and found to be safe; or\n- (ii) is replaced or permanently removed from use.","sortOrder":23},{"sectionNumber":"sec.18","sectionType":"section","heading":"Cord extension sets and flexible cables","content":"### sec.18 Cord extension sets and flexible cables\n\nThe person conducting the business or undertaking must ensure any cord extension set or flexible cable at the workplace is—\nlocated where it is not likely to suffer damage; or\nprotected against damage.\nIn this section—\ndamage includes damage by liquid.\nSubsection&#160;(1) is linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n(sec.18-ssec.1) The person conducting the business or undertaking must ensure any cord extension set or flexible cable at the workplace is— located where it is not likely to suffer damage; or protected against damage.\n(sec.18-ssec.2) In this section— damage includes damage by liquid.\n- (a) located where it is not likely to suffer damage; or\n- (b) protected against damage.","sortOrder":24},{"sectionNumber":"pt.3","sectionType":"part","heading":"Ways of ensuring electrical safety of persons and property","content":"# Ways of ensuring electrical safety of persons and property","sortOrder":25},{"sectionNumber":"pt.3-div.1","sectionType":"division","heading":"Electric lines","content":"## Electric lines","sortOrder":26},{"sectionNumber":"sec.19","sectionType":"section","heading":"Definition for division","content":"### sec.19 Definition for division\n\nIn this division—\nprivate overhead electric line means an overhead electric line that is not owned by an electricity entity.","sortOrder":27},{"sectionNumber":"sec.20","sectionType":"section","heading":"Service line","content":"### sec.20 Service line\n\nThis section applies if an electrical installation receives electricity distributed by an electricity entity.\nThe person in control of the electrical installation must provide suitable means for the connection of the person’s electrical installation to a service line.\nMaximum penalty—40 penalty units.\nThe person in control of the electrical installation must maintain any facilities for—\nattaching an overhead service line to supply electricity to the electrical installation; or\nthe entrance, support, protection and termination of an underground service line to supply electricity to the electrical installation.\nMaximum penalty—40 penalty units.\na service riser bracket\ntimber backing for a closed eye bolt\nHowever, subsection&#160;(3) does not require the person to maintain the insulation of any clamp or apparatus supplied by the person for the purposes of a joint needed for consumer terminals.\n(sec.20-ssec.1) This section applies if an electrical installation receives electricity distributed by an electricity entity.\n(sec.20-ssec.2) The person in control of the electrical installation must provide suitable means for the connection of the person’s electrical installation to a service line. Maximum penalty—40 penalty units.\n(sec.20-ssec.3) The person in control of the electrical installation must maintain any facilities for— attaching an overhead service line to supply electricity to the electrical installation; or the entrance, support, protection and termination of an underground service line to supply electricity to the electrical installation. Maximum penalty—40 penalty units. a service riser bracket timber backing for a closed eye bolt\n(sec.20-ssec.4) However, subsection&#160;(3) does not require the person to maintain the insulation of any clamp or apparatus supplied by the person for the purposes of a joint needed for consumer terminals.\n- (a) attaching an overhead service line to supply electricity to the electrical installation; or\n- (b) the entrance, support, protection and termination of an underground service line to supply electricity to the electrical installation.\n- • a service riser bracket\n- • timber backing for a closed eye bolt","sortOrder":28},{"sectionNumber":"sec.21","sectionType":"section","heading":"Preserving insulation of electric line","content":"### sec.21 Preserving insulation of electric line\n\nThe person in control of an electrical installation must maintain, to a reasonable extent, the integrity of the insulation of an electric line, or connection to an electric line, that is—\npart of the electrical installation; and\nnear 1 or more of the following—\nthe point of attachment of the electric line to a structure;\na roof or structure where it is likely that a person, including, for example, a painter or plumber, could come into contact with the insulated wires or connectors of the line.\nMaximum penalty—40 penalty units.\n- (a) part of the electrical installation; and\n- (b) near 1 or more of the following— (i) the point of attachment of the electric line to a structure; (ii) a roof or structure where it is likely that a person, including, for example, a painter or plumber, could come into contact with the insulated wires or connectors of the line.\n- (i) the point of attachment of the electric line to a structure;\n- (ii) a roof or structure where it is likely that a person, including, for example, a painter or plumber, could come into contact with the insulated wires or connectors of the line.\n- (i) the point of attachment of the electric line to a structure;\n- (ii) a roof or structure where it is likely that a person, including, for example, a painter or plumber, could come into contact with the insulated wires or connectors of the line.","sortOrder":29},{"sectionNumber":"sec.22","sectionType":"section","heading":"Installation of structures supporting private overhead electric line","content":"### sec.22 Installation of structures supporting private overhead electric line\n\nThe person in control of a private overhead electric line must ensure that a pole, post or other structure supporting the line—\nis constructed of a material that is suitable for the conditions of use; and\nis of a size that is suitable for the conditions of use; and\nis secured in the ground, having regard to the size of the post, pole or structure and the quality of the soil.\nMaximum penalty—40 penalty units.\nFor guidance on the size and depth of poles and posts, see the wiring rules, Appendix D.\n- (a) is constructed of a material that is suitable for the conditions of use; and\n- (b) is of a size that is suitable for the conditions of use; and\n- (c) is secured in the ground, having regard to the size of the post, pole or structure and the quality of the soil.","sortOrder":30},{"sectionNumber":"sec.23","sectionType":"section","heading":"Trimming of trees near private overhead electric line","content":"### sec.23 Trimming of trees near private overhead electric line\n\nThe person in control of a private overhead electric line must ensure trees and other vegetation are trimmed, and other measures are taken, to prevent contact with the line that is likely to cause injury from electric shock to any person or damage to property.\nMaximum penalty—40 penalty units.","sortOrder":31},{"sectionNumber":"sec.24","sectionType":"section","heading":"Ensuring safety of disconnected private overhead electric line","content":"### sec.24 Ensuring safety of disconnected private overhead electric line\n\nThe person in control of a private overhead electric line must take all reasonable steps to ensure that, if the line is disconnected from its electricity supply, the line is—\ndismantled as soon as practicable after disconnection; or\nmaintained so it is electrically and mechanically safe.\nMaximum penalty—40 penalty units.\n- (a) dismantled as soon as practicable after disconnection; or\n- (b) maintained so it is electrically and mechanically safe.","sortOrder":32},{"sectionNumber":"pt.3-div.2","sectionType":"division","heading":"Installation of approved safety switches in domestic residences","content":"## Installation of approved safety switches in domestic residences","sortOrder":33},{"sectionNumber":"sec.25","sectionType":"section","heading":"Definitions for division","content":"### sec.25 Definitions for division\n\nIn this division—\ndomestic residence means a building or structure, or a part of a building or structure, that—\nis used, or designed to be used, as a single dwelling; and\na house, flat or unit\nis not used, or designed to be used, for temporary accommodation.\na boarding house or motel\ngeneral purpose socket-outlet means a low voltage socket-outlet that—\nhas a rating of 10A; and\nis designed to fit a three-pin flat-pin plug that complies with the relevant standard under part&#160;4 for the type of plug; and\nis used, or intended to be used, or could at some time reasonably be expected to be used, for more than 1 appliance.\nowner , of residential land, means the person registered or entitled to be registered, immediately after the transfer day for the land—\nunder the Land Act 1994 , as a lessee, or personal representative of a deceased lessee, of the land; or\nunder the Land Title Act 1994 , as an owner, or the personal representative of an owner, of the land.\npossession day , for residential land, means the day the transferee of the land enters into lawful possession of the land.\nresidential land means land on which a domestic residence is constructed, and includes an interest in residential land.\ntransfer day , for residential land, means the day the transferee of the land is entitled to lawful possession of the land.\ntransferee , of residential land, means the person who, on becoming entitled to possession of the land, may lodge an application for registration—\nunder the Land Act 1994 , as a lessee, or personal representative of a deceased lessee, of the land; or\nunder the Land Title Act 1994 , as an owner, or the personal representative of an owner, of the land.\ntransferor , of residential land, means—\nif, immediately before the transfer day for the residential land, there is a mortgagee in possession of the land—the mortgagee in possession; or\notherwise—the person registered, immediately before the transfer day for the land—\nunder the Land Act 1994 , as a lessee, or personal representative of a deceased lessee, of the land; or\nunder the Land Title Act 1994 , as an owner, or the personal representative of an owner, of the land.\n- (a) is used, or designed to be used, as a single dwelling; and Examples for paragraph&#160;(a) — a house, flat or unit\n- (b) is not used, or designed to be used, for temporary accommodation. Examples of temporary accommodation for paragraph&#160;(b) — a boarding house or motel\n- (a) has a rating of 10A; and\n- (b) is designed to fit a three-pin flat-pin plug that complies with the relevant standard under part&#160;4 for the type of plug; and\n- (c) is used, or intended to be used, or could at some time reasonably be expected to be used, for more than 1 appliance.\n- (a) under the Land Act 1994 , as a lessee, or personal representative of a deceased lessee, of the land; or\n- (b) under the Land Title Act 1994 , as an owner, or the personal representative of an owner, of the land.\n- (a) under the Land Act 1994 , as a lessee, or personal representative of a deceased lessee, of the land; or\n- (b) under the Land Title Act 1994 , as an owner, or the personal representative of an owner, of the land.\n- (a) if, immediately before the transfer day for the residential land, there is a mortgagee in possession of the land—the mortgagee in possession; or\n- (b) otherwise—the person registered, immediately before the transfer day for the land— (i) under the Land Act 1994 , as a lessee, or personal representative of a deceased lessee, of the land; or (ii) under the Land Title Act 1994 , as an owner, or the personal representative of an owner, of the land.\n- (i) under the Land Act 1994 , as a lessee, or personal representative of a deceased lessee, of the land; or\n- (ii) under the Land Title Act 1994 , as an owner, or the personal representative of an owner, of the land.\n- (i) under the Land Act 1994 , as a lessee, or personal representative of a deceased lessee, of the land; or\n- (ii) under the Land Title Act 1994 , as an owner, or the personal representative of an owner, of the land.","sortOrder":34},{"sectionNumber":"sec.26","sectionType":"section","heading":"Notice to transferee about approved safety switch","content":"### sec.26 Notice to transferee about approved safety switch\n\nThe transferor of residential land must, on or before the possession day for the land, give the transferee of the land written notice of whether an approved safety switch has been installed for the general purpose socket-outlets installed in the domestic residence on the land.\nMaximum penalty—15 penalty units.","sortOrder":35},{"sectionNumber":"sec.27","sectionType":"section","heading":"Notice to regulator about approved safety switch and other matters","content":"### sec.27 Notice to regulator about approved safety switch and other matters\n\nThe transferor of residential land must, within 90 days after the possession day for the land, give the regulator a written notice stating all of the following information ( transfer and safety switch information )—\nthe full names of the transferor and transferee;\nthe addresses of the transferor and transferee immediately after the possession day for the land;\nthe property details of the land;\nthe current use of the land;\nif there is an agreement for the transfer of the land—the date of the agreement;\nthe possession day for the land;\nwhether an approved safety switch has been installed for the general purpose socket-outlets installed in the domestic residence on the land;\nwhether the transferor has given the transferee written notice of whether an approved safety switch has been installed for the general purpose socket-outlets installed in the domestic residence on the land.\nMaximum penalty—15 penalty units.\nHowever, the transferor is not required to comply with subsection&#160;(1) if a properly completed combined form, together with an application for registration, is given to—\nfor an application for registration under the Land Act 1994 —the chief executive (land); or\nfor an application for registration under the Land Title Act 1994 —the registrar.\nIf a combined form is given under subsection&#160;(2) , the regulator may use only the transfer and safety switch information stated on the form.\nIn this section—\nchief executive (land) means the chief executive of the department in which the Land Act 1994 is administered.\ncombined form means a form that—\ngives transfer and safety switch information and information about a change of ownership required under other Acts; and\nmay be given to the chief executive (land) or the registrar.\nregistrar see the Land Title Act 1994 , schedule&#160;2 .\n(sec.27-ssec.1) The transferor of residential land must, within 90 days after the possession day for the land, give the regulator a written notice stating all of the following information ( transfer and safety switch information )— the full names of the transferor and transferee; the addresses of the transferor and transferee immediately after the possession day for the land; the property details of the land; the current use of the land; if there is an agreement for the transfer of the land—the date of the agreement; the possession day for the land; whether an approved safety switch has been installed for the general purpose socket-outlets installed in the domestic residence on the land; whether the transferor has given the transferee written notice of whether an approved safety switch has been installed for the general purpose socket-outlets installed in the domestic residence on the land. Maximum penalty—15 penalty units.\n(sec.27-ssec.2) However, the transferor is not required to comply with subsection&#160;(1) if a properly completed combined form, together with an application for registration, is given to— for an application for registration under the Land Act 1994 —the chief executive (land); or for an application for registration under the Land Title Act 1994 —the registrar.\n(sec.27-ssec.3) If a combined form is given under subsection&#160;(2) , the regulator may use only the transfer and safety switch information stated on the form.\n(sec.27-ssec.4) In this section— chief executive (land) means the chief executive of the department in which the Land Act 1994 is administered. combined form means a form that— gives transfer and safety switch information and information about a change of ownership required under other Acts; and may be given to the chief executive (land) or the registrar. registrar see the Land Title Act 1994 , schedule&#160;2 .\n- (a) the full names of the transferor and transferee;\n- (b) the addresses of the transferor and transferee immediately after the possession day for the land;\n- (c) the property details of the land;\n- (d) the current use of the land;\n- (e) if there is an agreement for the transfer of the land—the date of the agreement;\n- (f) the possession day for the land;\n- (g) whether an approved safety switch has been installed for the general purpose socket-outlets installed in the domestic residence on the land;\n- (h) whether the transferor has given the transferee written notice of whether an approved safety switch has been installed for the general purpose socket-outlets installed in the domestic residence on the land.\n- (a) for an application for registration under the Land Act 1994 —the chief executive (land); or\n- (b) for an application for registration under the Land Title Act 1994 —the registrar.\n- (a) gives transfer and safety switch information and information about a change of ownership required under other Acts; and\n- (b) may be given to the chief executive (land) or the registrar.","sortOrder":36},{"sectionNumber":"sec.28","sectionType":"section","heading":"Installation of approved safety switch in domestic residences","content":"### sec.28 Installation of approved safety switch in domestic residences\n\nAn owner of residential land must ensure that, within 90 days after the possession day, an approved safety switch is installed for any general purpose socket-outlet installed in the domestic residence on the land.\nMaximum penalty—15 penalty units.","sortOrder":37},{"sectionNumber":"sec.29","sectionType":"section","heading":"Installation of approved safety switch if residential tenancy agreement entered into","content":"### sec.29 Installation of approved safety switch if residential tenancy agreement entered into\n\nThis section applies if—\nafter the possession day for residential land, a residential tenancy agreement for the residential land is entered into; and\nthe tenancy starts under the residential tenancy agreement; and\na general purpose socket-outlet is installed in the domestic residence on the land; and\nan approved safety switch is not installed for the general purpose socket-outlet.\nThe owner of the land must ensure, within 90 days after the day the tenancy starts under the residential tenancy agreement, that an approved safety switch is installed for any general purpose socket-outlet installed in the domestic residence on the land.\nMaximum penalty—15 penalty units.\nIn this section—\nresidential tenancy agreement see the Residential Tenancies and Rooming Accommodation Act 2008 , section&#160;12 .\n(sec.29-ssec.1) This section applies if— after the possession day for residential land, a residential tenancy agreement for the residential land is entered into; and the tenancy starts under the residential tenancy agreement; and a general purpose socket-outlet is installed in the domestic residence on the land; and an approved safety switch is not installed for the general purpose socket-outlet.\n(sec.29-ssec.2) The owner of the land must ensure, within 90 days after the day the tenancy starts under the residential tenancy agreement, that an approved safety switch is installed for any general purpose socket-outlet installed in the domestic residence on the land. Maximum penalty—15 penalty units.\n(sec.29-ssec.3) In this section— residential tenancy agreement see the Residential Tenancies and Rooming Accommodation Act 2008 , section&#160;12 .\n- (a) after the possession day for residential land, a residential tenancy agreement for the residential land is entered into; and\n- (b) the tenancy starts under the residential tenancy agreement; and\n- (c) a general purpose socket-outlet is installed in the domestic residence on the land; and\n- (d) an approved safety switch is not installed for the general purpose socket-outlet.","sortOrder":38},{"sectionNumber":"sec.30","sectionType":"section","heading":"Performing electrical installation work for domestic residences","content":"### sec.30 Performing electrical installation work for domestic residences\n\nA licensed electrical worker or a licensed electrical contractor must not perform electrical installation work on an electrical installation installed in a domestic residence unless—\nan approved safety switch has been installed for the general purpose socket-outlets installed in the residence; or\nif an approved safety switch has not been installed for the general purpose socket-outlets installed in the residence—\nthe work is or includes the installation of an approved safety switch for the general purpose socket-outlets installed in the residence; or\nthe worker or contractor reasonably believes installation of an approved safety switch for the general purpose socket-outlets installed in the residence is not required under this regulation; or\nthe work is the connection of the residence to a source of electricity; or\nthe work is needed to be performed without delay in an emergency, to prevent an emergency from happening or for safety reasons.\nMaximum penalty—40 penalty units.\n- (a) an approved safety switch has been installed for the general purpose socket-outlets installed in the residence; or\n- (b) if an approved safety switch has not been installed for the general purpose socket-outlets installed in the residence— (i) the work is or includes the installation of an approved safety switch for the general purpose socket-outlets installed in the residence; or (ii) the worker or contractor reasonably believes installation of an approved safety switch for the general purpose socket-outlets installed in the residence is not required under this regulation; or (iii) the work is the connection of the residence to a source of electricity; or (iv) the work is needed to be performed without delay in an emergency, to prevent an emergency from happening or for safety reasons.\n- (i) the work is or includes the installation of an approved safety switch for the general purpose socket-outlets installed in the residence; or\n- (ii) the worker or contractor reasonably believes installation of an approved safety switch for the general purpose socket-outlets installed in the residence is not required under this regulation; or\n- (iii) the work is the connection of the residence to a source of electricity; or\n- (iv) the work is needed to be performed without delay in an emergency, to prevent an emergency from happening or for safety reasons.\n- (i) the work is or includes the installation of an approved safety switch for the general purpose socket-outlets installed in the residence; or\n- (ii) the worker or contractor reasonably believes installation of an approved safety switch for the general purpose socket-outlets installed in the residence is not required under this regulation; or\n- (iii) the work is the connection of the residence to a source of electricity; or\n- (iv) the work is needed to be performed without delay in an emergency, to prevent an emergency from happening or for safety reasons.","sortOrder":39},{"sectionNumber":"pt.3-div.3","sectionType":"division","heading":"Roof space work","content":"## Roof space work","sortOrder":40},{"sectionNumber":"sec.31","sectionType":"section","heading":"Definitions for division","content":"### sec.31 Definitions for division\n\nIn this division—\nbuilding means a building classified under the Building Code of Australia as—\na class 1 building; or\na class 2 building; or\na class 10a building.\nBuilding Code of Australia has the meaning given by the Building Act 1975 , section&#160;12 .\nenter , in relation to a roof space, includes placing any part of a person’s body in the roof space.\nrelevant electrical installation , for a building, means—\nan electrical installation for the building that includes a switchboard for energising or de-energising the electrical installation or part of the electrical installation for the building; or\nif there is more than 1 electrical installation as mentioned in paragraph&#160;(a) for the building—all of the electrical installations for the building.\nroof space , of a building—\nmeans—\nthe space in the building immediately under the roof of the building; or\nif there is a ceiling under any part of the roof of the building—the space between the roof and the ceiling, including the ceiling structure; but\ndoes not include habitable areas of a space mentioned in paragraph&#160;(a) .\n- (a) a class 1 building; or\n- (b) a class 2 building; or\n- (c) a class 10a building.\n- (a) an electrical installation for the building that includes a switchboard for energising or de-energising the electrical installation or part of the electrical installation for the building; or\n- (b) if there is more than 1 electrical installation as mentioned in paragraph&#160;(a) for the building—all of the electrical installations for the building.\n- (a) means— (i) the space in the building immediately under the roof of the building; or (ii) if there is a ceiling under any part of the roof of the building—the space between the roof and the ceiling, including the ceiling structure; but\n- (i) the space in the building immediately under the roof of the building; or\n- (ii) if there is a ceiling under any part of the roof of the building—the space between the roof and the ceiling, including the ceiling structure; but\n- (b) does not include habitable areas of a space mentioned in paragraph&#160;(a) .\n- (i) the space in the building immediately under the roof of the building; or\n- (ii) if there is a ceiling under any part of the roof of the building—the space between the roof and the ceiling, including the ceiling structure; but","sortOrder":41},{"sectionNumber":"sec.32","sectionType":"section","heading":"Application of division","content":"### sec.32 Application of division\n\nThis division applies in relation to any work carried out in relation to a building, other than electrical work on or near energised electrical equipment to which part&#160;8 , division&#160;3 applies.","sortOrder":42},{"sectionNumber":"sec.33","sectionType":"section","heading":"Requirements for person conducting a business or undertaking","content":"### sec.33 Requirements for person conducting a business or undertaking\n\nA person conducting a business or undertaking must ensure, so far as is reasonably practicable, that a worker does not carry out work in the roof space of a building, or enter the roof space for the carrying out of work in another part of the building, unless—\nthe relevant electrical installation for the building is de-energised; or\neither of the circumstances mentioned in subsection&#160;(2) applies.\nMaximum penalty—60 penalty units.\nFor subsection&#160;(1) (b) , the circumstances are—\nit is not reasonably practicable to carry out the work or enter the roof space while the relevant electrical installation is de-energised; or\nit is necessary to test, service or commission a thing, other than electrical equipment, that is energised and located in, or accessible by, the roof space.\nIf either of the circumstances mentioned in subsection&#160;(2) applies, the person conducting the business or undertaking must ensure that—\na risk assessment is conducted for the work or entry; and\nthe person is satisfied—\nthe risks identified by the risk assessment are, or can be reduced to, as low as reasonably practicable; and\nthe work can be carried out, or the entry can be made, safely; and\na statement for the work or entry is prepared that—\nidentifies the work or entry; and\nstates the hazards associated with the work or entry and the risks associated with those hazards; and\ndescribes the measures to be implemented to control the risks; and\ndescribes how the measures are to be implemented, monitored and reviewed; and\nthe work is carried out or the entry is made in accordance with the statement.\nMaximum penalty—60 penalty units.\n(sec.33-ssec.1) A person conducting a business or undertaking must ensure, so far as is reasonably practicable, that a worker does not carry out work in the roof space of a building, or enter the roof space for the carrying out of work in another part of the building, unless— the relevant electrical installation for the building is de-energised; or either of the circumstances mentioned in subsection&#160;(2) applies. Maximum penalty—60 penalty units.\n(sec.33-ssec.2) For subsection&#160;(1) (b) , the circumstances are— it is not reasonably practicable to carry out the work or enter the roof space while the relevant electrical installation is de-energised; or it is necessary to test, service or commission a thing, other than electrical equipment, that is energised and located in, or accessible by, the roof space.\n(sec.33-ssec.3) If either of the circumstances mentioned in subsection&#160;(2) applies, the person conducting the business or undertaking must ensure that— a risk assessment is conducted for the work or entry; and the person is satisfied— the risks identified by the risk assessment are, or can be reduced to, as low as reasonably practicable; and the work can be carried out, or the entry can be made, safely; and a statement for the work or entry is prepared that— identifies the work or entry; and states the hazards associated with the work or entry and the risks associated with those hazards; and describes the measures to be implemented to control the risks; and describes how the measures are to be implemented, monitored and reviewed; and the work is carried out or the entry is made in accordance with the statement. Maximum penalty—60 penalty units.\n- (a) the relevant electrical installation for the building is de-energised; or\n- (b) either of the circumstances mentioned in subsection&#160;(2) applies.\n- (a) it is not reasonably practicable to carry out the work or enter the roof space while the relevant electrical installation is de-energised; or\n- (b) it is necessary to test, service or commission a thing, other than electrical equipment, that is energised and located in, or accessible by, the roof space.\n- (a) a risk assessment is conducted for the work or entry; and\n- (b) the person is satisfied— (i) the risks identified by the risk assessment are, or can be reduced to, as low as reasonably practicable; and (ii) the work can be carried out, or the entry can be made, safely; and\n- (i) the risks identified by the risk assessment are, or can be reduced to, as low as reasonably practicable; and\n- (ii) the work can be carried out, or the entry can be made, safely; and\n- (c) a statement for the work or entry is prepared that— (i) identifies the work or entry; and (ii) states the hazards associated with the work or entry and the risks associated with those hazards; and (iii) describes the measures to be implemented to control the risks; and (iv) describes how the measures are to be implemented, monitored and reviewed; and\n- (i) identifies the work or entry; and\n- (ii) states the hazards associated with the work or entry and the risks associated with those hazards; and\n- (iii) describes the measures to be implemented to control the risks; and\n- (iv) describes how the measures are to be implemented, monitored and reviewed; and\n- (d) the work is carried out or the entry is made in accordance with the statement.\n- (i) the risks identified by the risk assessment are, or can be reduced to, as low as reasonably practicable; and\n- (ii) the work can be carried out, or the entry can be made, safely; and\n- (i) identifies the work or entry; and\n- (ii) states the hazards associated with the work or entry and the risks associated with those hazards; and\n- (iii) describes the measures to be implemented to control the risks; and\n- (iv) describes how the measures are to be implemented, monitored and reviewed; and","sortOrder":43},{"sectionNumber":"sec.34","sectionType":"section","heading":"Requirements for worker","content":"### sec.34 Requirements for worker\n\nA worker must ensure, so far as is reasonably practicable, that the worker does not carry out work in the roof space of a building, or enter the roof space for the carrying out of work in another part of the building, unless—\nthe relevant electrical installation for the building is de-energised; or\na circumstance mentioned in section&#160;33 (2) applies.\nMaximum penalty—10 penalty units.\n- (a) the relevant electrical installation for the building is de-energised; or\n- (b) a circumstance mentioned in section&#160;33 (2) applies.","sortOrder":44},{"sectionNumber":"sec.35","sectionType":"section","heading":"Application of ss&#160;33 and 34 for isolated roof spaces","content":"### sec.35 Application of ss&#160;33 and 34 for isolated roof spaces\n\nThis section applies if—\na worker, for a person conducting a business or undertaking—\ncarries out work in a part of the roof space of a building that is separate from 1 or more other parts of the roof space of the same building (the isolated roof space ); or\nenters the isolated roof space for the carrying out of work in another part of the building; and\nthe isolated roof space can not be accessed from any other part of the building’s roof space; and\nthe isolated roof space has a relevant electrical installation for the building that is capable of being de-energised in isolation from any other relevant electrical installation in the building (the isolated electrical installation ).\nSections&#160;33 and 34 apply—\nas if a reference in those sections to the roof space of the building were a reference to the isolated roof space; and\nas if a reference in those sections to the relevant electrical installation for the building were a reference to the isolated electrical installation.\n(sec.35-ssec.1) This section applies if— a worker, for a person conducting a business or undertaking— carries out work in a part of the roof space of a building that is separate from 1 or more other parts of the roof space of the same building (the isolated roof space ); or enters the isolated roof space for the carrying out of work in another part of the building; and the isolated roof space can not be accessed from any other part of the building’s roof space; and the isolated roof space has a relevant electrical installation for the building that is capable of being de-energised in isolation from any other relevant electrical installation in the building (the isolated electrical installation ).\n(sec.35-ssec.2) Sections&#160;33 and 34 apply— as if a reference in those sections to the roof space of the building were a reference to the isolated roof space; and as if a reference in those sections to the relevant electrical installation for the building were a reference to the isolated electrical installation.\n- (a) a worker, for a person conducting a business or undertaking— (i) carries out work in a part of the roof space of a building that is separate from 1 or more other parts of the roof space of the same building (the isolated roof space ); or (ii) enters the isolated roof space for the carrying out of work in another part of the building; and\n- (i) carries out work in a part of the roof space of a building that is separate from 1 or more other parts of the roof space of the same building (the isolated roof space ); or\n- (ii) enters the isolated roof space for the carrying out of work in another part of the building; and\n- (b) the isolated roof space can not be accessed from any other part of the building’s roof space; and\n- (c) the isolated roof space has a relevant electrical installation for the building that is capable of being de-energised in isolation from any other relevant electrical installation in the building (the isolated electrical installation ).\n- (i) carries out work in a part of the roof space of a building that is separate from 1 or more other parts of the roof space of the same building (the isolated roof space ); or\n- (ii) enters the isolated roof space for the carrying out of work in another part of the building; and\n- (a) as if a reference in those sections to the roof space of the building were a reference to the isolated roof space; and\n- (b) as if a reference in those sections to the relevant electrical installation for the building were a reference to the isolated electrical installation.","sortOrder":45},{"sectionNumber":"sec.36","sectionType":"section","heading":"Record keeping","content":"### sec.36 Record keeping\n\nThis section applies if a person conducting a business or undertaking is responsible for ensuring—\na risk assessment is conducted under section&#160;33 (3) (a) ; and\na statement is prepared under section&#160;33 (3) (c) .\nThe person must keep—\na copy of the risk assessment until at least 28 days after the work or entry to which the risk assessment relates is completed or made; and\na copy of the statement until the work or entry to which the statement relates is completed or made.\nMaximum penalty—60 penalty units.\nHowever, if a serious electrical incident or dangerous electrical event occurs in connection with the work or entry to which the risk assessment or statement relates, the person must keep the risk assessment or statement for at least 2 years after the incident or event occurs.\nMaximum penalty—60 penalty units.\n(sec.36-ssec.1) This section applies if a person conducting a business or undertaking is responsible for ensuring— a risk assessment is conducted under section&#160;33 (3) (a) ; and a statement is prepared under section&#160;33 (3) (c) .\n(sec.36-ssec.2) The person must keep— a copy of the risk assessment until at least 28 days after the work or entry to which the risk assessment relates is completed or made; and a copy of the statement until the work or entry to which the statement relates is completed or made. Maximum penalty—60 penalty units.\n(sec.36-ssec.3) However, if a serious electrical incident or dangerous electrical event occurs in connection with the work or entry to which the risk assessment or statement relates, the person must keep the risk assessment or statement for at least 2 years after the incident or event occurs. Maximum penalty—60 penalty units.\n- (a) a risk assessment is conducted under section&#160;33 (3) (a) ; and\n- (b) a statement is prepared under section&#160;33 (3) (c) .\n- (a) a copy of the risk assessment until at least 28 days after the work or entry to which the risk assessment relates is completed or made; and\n- (b) a copy of the statement until the work or entry to which the statement relates is completed or made.","sortOrder":46},{"sectionNumber":"pt.3-div.4","sectionType":"division","heading":"Installation of ceiling insulation","content":"## Installation of ceiling insulation","sortOrder":47},{"sectionNumber":"sec.37","sectionType":"section","heading":"Application of subdivision","content":"### sec.37 Application of subdivision\n\nThis subdivision, other than section&#160;38 (2) , applies to a person conducting a business or undertaking that includes the installation of ceiling insulation.\nSection&#160;38 (2) applies to a worker who performs work that includes the installation of ceiling insulation.\n(sec.37-ssec.1) This subdivision, other than section&#160;38 (2) , applies to a person conducting a business or undertaking that includes the installation of ceiling insulation.\n(sec.37-ssec.2) Section&#160;38 (2) applies to a worker who performs work that includes the installation of ceiling insulation.","sortOrder":48},{"sectionNumber":"sec.38","sectionType":"section","heading":"Metal or other conductive fasteners not to be used to install ceiling insulation","content":"### sec.38 Metal or other conductive fasteners not to be used to install ceiling insulation\n\nThe person conducting the business or undertaking must ensure ceiling insulation is not fastened to the ceiling structure of a building with metal or any other form of conductive fastener.\nThe worker must not fasten ceiling insulation to the ceiling structure of a building with metal or any other form of conductive fastener.\nSubsection&#160;(1) is linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\nSubsection&#160;(2) is linked to the electrical safety duty in section&#160;39 of the Act (see section&#160;7 (2) ).\n(sec.38-ssec.1) The person conducting the business or undertaking must ensure ceiling insulation is not fastened to the ceiling structure of a building with metal or any other form of conductive fastener.\n(sec.38-ssec.2) The worker must not fasten ceiling insulation to the ceiling structure of a building with metal or any other form of conductive fastener. Subsection&#160;(1) is linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ). Subsection&#160;(2) is linked to the electrical safety duty in section&#160;39 of the Act (see section&#160;7 (2) ).\n- 1 Subsection&#160;(1) is linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n- 2 Subsection&#160;(2) is linked to the electrical safety duty in section&#160;39 of the Act (see section&#160;7 (2) ).","sortOrder":49},{"sectionNumber":"sec.39","sectionType":"section","heading":"Installation must comply with wiring rules, cl 4.5.2.3","content":"### sec.39 Installation must comply with wiring rules, cl 4.5.2.3\n\nThe person conducting the business or undertaking must ensure ceiling insulation is installed in a building in a way that complies with the wiring rules, clause 4.5.2.3, as in force from time to time.\nThe wiring rules, clause 4.5.2.3 deals with recessed luminaires and their auxiliary equipment.\nOn the commencement of this section, the wiring rules, clause 4.5.2.3 is available on the department’s website.\nThis section is linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n- 1 The wiring rules, clause 4.5.2.3 deals with recessed luminaires and their auxiliary equipment.\n- 2 On the commencement of this section, the wiring rules, clause 4.5.2.3 is available on the department’s website.\n- 3 This section is linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).","sortOrder":50},{"sectionNumber":"sec.40","sectionType":"section","heading":"Training for assessment of electrical risk","content":"### sec.40 Training for assessment of electrical risk\n\nThe person conducting the business or undertaking must ensure a worker for the business or undertaking who installs ceiling insulation in a building is trained in carrying out an assessment of the electrical risk from the installation of ceiling insulation.\nThis section is linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).","sortOrder":51},{"sectionNumber":"sec.41","sectionType":"section","heading":"Assessment of electrical risk","content":"### sec.41 Assessment of electrical risk\n\nThe person conducting the business or undertaking must ensure that, before the start of the installation in a building of ceiling insulation—\nan on-site operational assessment of the electrical risk from the installation of the ceiling insulation is conducted; and\nany control measures necessary to prevent a person’s exposure to the electrical risk are implemented.\nThe person conducting the business or undertaking must keep a record of the on-site operational assessment for at least 5 years after the assessment is conducted.\nMaximum penalty for subsection&#160;(2) —20 penalty units.\nSubsection&#160;(1) is linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n(sec.41-ssec.1) The person conducting the business or undertaking must ensure that, before the start of the installation in a building of ceiling insulation— an on-site operational assessment of the electrical risk from the installation of the ceiling insulation is conducted; and any control measures necessary to prevent a person’s exposure to the electrical risk are implemented.\n(sec.41-ssec.2) The person conducting the business or undertaking must keep a record of the on-site operational assessment for at least 5 years after the assessment is conducted. Maximum penalty for subsection&#160;(2) —20 penalty units.\n- (a) an on-site operational assessment of the electrical risk from the installation of the ceiling insulation is conducted; and\n- (b) any control measures necessary to prevent a person’s exposure to the electrical risk are implemented.","sortOrder":52},{"sectionNumber":"sec.42","sectionType":"section","heading":"Definitions for subdivision","content":"### sec.42 Definitions for subdivision\n\nIn this subdivision—\nelectrically conductive ceiling insulation —\nmeans a product used, or to be used, as ceiling insulation that is readily able to conduct electricity; but\ndoes not include metal foil batts.\nnon-capable circuit means an electrical circuit on which an approved safety switch is not capable of effective operation.\nconsumer main\nsubmain in particular circumstances\n- (a) means a product used, or to be used, as ceiling insulation that is readily able to conduct electricity; but\n- (b) does not include metal foil batts.\n- • consumer main\n- • submain in particular circumstances","sortOrder":53},{"sectionNumber":"sec.43","sectionType":"section","heading":"Application of subdivision","content":"### sec.43 Application of subdivision\n\nThis subdivision applies to a person conducting a business or undertaking that includes the installation of electrically conductive ceiling insulation.","sortOrder":54},{"sectionNumber":"sec.44","sectionType":"section","heading":"Requirement for electrical safety inspection and test","content":"### sec.44 Requirement for electrical safety inspection and test\n\nBefore starting to install electrically conductive ceiling insulation in a building, the person conducting the business or undertaking must obtain a certificate from a licensed electrical contractor stating that the contractor—\nhas inspected and tested the existing electrical installation in the ceiling structure of the building; and\nis satisfied that the existing electrical installation in the ceiling structure of the building is electrically safe.\nThe person conducting the business or undertaking must keep the certificate mentioned in subsection&#160;(1) for at least 5 years after the person is given the certificate.\nMaximum penalty for subsection&#160;(2) —20 penalty units.\nSubsection&#160;(1) is linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n(sec.44-ssec.1) Before starting to install electrically conductive ceiling insulation in a building, the person conducting the business or undertaking must obtain a certificate from a licensed electrical contractor stating that the contractor— has inspected and tested the existing electrical installation in the ceiling structure of the building; and is satisfied that the existing electrical installation in the ceiling structure of the building is electrically safe.\n(sec.44-ssec.2) The person conducting the business or undertaking must keep the certificate mentioned in subsection&#160;(1) for at least 5 years after the person is given the certificate. Maximum penalty for subsection&#160;(2) —20 penalty units.\n- (a) has inspected and tested the existing electrical installation in the ceiling structure of the building; and\n- (b) is satisfied that the existing electrical installation in the ceiling structure of the building is electrically safe.","sortOrder":55},{"sectionNumber":"sec.45","sectionType":"section","heading":"Requirement for approved safety switch or permanent marking for electrical circuits","content":"### sec.45 Requirement for approved safety switch or permanent marking for electrical circuits\n\nBefore starting to install electrically conductive ceiling insulation in a building, the person conducting the business or undertaking must obtain a certificate from a licensed electrical contractor stating that—\nan approved safety switch has been installed on each capable circuit located in the ceiling structure of the building; and\neach non-capable circuit located in the ceiling structure of the building is identified and clearly marked.\nFor subsection&#160;(1) (b) , a non-capable circuit is clearly marked only if the non-capable circuit is permanently marked—\nin a way that distinguishes the non-capable circuit from capable circuits located in the ceiling structure; and\nat intervals of not more than 1m, to the extent it is reasonably practicable.\nThe certificate mentioned in subsection&#160;(1) must explain the way in which non-capable circuits located in the ceiling structure have been permanently marked to distinguish them from capable circuits located in the ceiling structure.\nIf a non-capable circuit has been marked with durable high visibility tags, the certificate must explain this.\nThe person conducting the business or undertaking must keep the certificate mentioned in subsection&#160;(1) for at least 5 years after the person is given the certificate.\nMaximum penalty—20 penalty units.\nIn this section—\ncapable circuit means an electrical circuit on which an approved safety switch is capable of effective operation.\nSubsection&#160;(1) is linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n(sec.45-ssec.1) Before starting to install electrically conductive ceiling insulation in a building, the person conducting the business or undertaking must obtain a certificate from a licensed electrical contractor stating that— an approved safety switch has been installed on each capable circuit located in the ceiling structure of the building; and each non-capable circuit located in the ceiling structure of the building is identified and clearly marked.\n(sec.45-ssec.2) For subsection&#160;(1) (b) , a non-capable circuit is clearly marked only if the non-capable circuit is permanently marked— in a way that distinguishes the non-capable circuit from capable circuits located in the ceiling structure; and at intervals of not more than 1m, to the extent it is reasonably practicable.\n(sec.45-ssec.3) The certificate mentioned in subsection&#160;(1) must explain the way in which non-capable circuits located in the ceiling structure have been permanently marked to distinguish them from capable circuits located in the ceiling structure. If a non-capable circuit has been marked with durable high visibility tags, the certificate must explain this.\n(sec.45-ssec.4) The person conducting the business or undertaking must keep the certificate mentioned in subsection&#160;(1) for at least 5 years after the person is given the certificate. Maximum penalty—20 penalty units.\n(sec.45-ssec.5) In this section— capable circuit means an electrical circuit on which an approved safety switch is capable of effective operation.\n- (a) an approved safety switch has been installed on each capable circuit located in the ceiling structure of the building; and\n- (b) each non-capable circuit located in the ceiling structure of the building is identified and clearly marked.\n- (a) in a way that distinguishes the non-capable circuit from capable circuits located in the ceiling structure; and\n- (b) at intervals of not more than 1m, to the extent it is reasonably practicable.","sortOrder":56},{"sectionNumber":"sec.46","sectionType":"section","heading":"Installation requirements for non-capable circuits","content":"### sec.46 Installation requirements for non-capable circuits\n\nThe person conducting the business or undertaking must ensure electrically conductive ceiling insulation installed in a building—\ndoes not cover, in whole or in part, any non-capable circuit located in the ceiling structure of the building; and\nis installed at least 25mm away from any non-capable circuit located in the ceiling structure of the building.\nThis section is linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n- (a) does not cover, in whole or in part, any non-capable circuit located in the ceiling structure of the building; and\n- (b) is installed at least 25mm away from any non-capable circuit located in the ceiling structure of the building.","sortOrder":57},{"sectionNumber":"pt.3-div.5","sectionType":"division","heading":"Other requirements","content":"## Other requirements","sortOrder":58},{"sectionNumber":"sec.47","sectionType":"section","heading":"Requirement on person in control to fix defect","content":"### sec.47 Requirement on person in control to fix defect\n\nThis section applies if an inspector or an electricity entity reasonably believes a defect exists that affects the electrical safety of electrical equipment.\nThe inspector or electricity entity may, by notice, require the person in control of the electrical equipment to take all reasonable steps to ensure the defect is fixed within a stated period.\nThe person in control of the electrical equipment must comply with the notice unless the person has a reasonable excuse.\nMaximum penalty—40 penalty units.\n(sec.47-ssec.1) This section applies if an inspector or an electricity entity reasonably believes a defect exists that affects the electrical safety of electrical equipment.\n(sec.47-ssec.2) The inspector or electricity entity may, by notice, require the person in control of the electrical equipment to take all reasonable steps to ensure the defect is fixed within a stated period.\n(sec.47-ssec.3) The person in control of the electrical equipment must comply with the notice unless the person has a reasonable excuse.","sortOrder":59},{"sectionNumber":"sec.48","sectionType":"section","heading":"Earthing","content":"### sec.48 Earthing\n\nThis section applies if a low voltage electrical installation receives electricity distributed by an electricity entity.\nThe person in control of the low voltage electrical installation must not knowingly allow the earthing for the installation to be inconsistent with the requirements for systems of earthing applying to the electricity entity under section&#160;245 .\nMaximum penalty—40 penalty units.\n(sec.48-ssec.1) This section applies if a low voltage electrical installation receives electricity distributed by an electricity entity.\n(sec.48-ssec.2) The person in control of the low voltage electrical installation must not knowingly allow the earthing for the installation to be inconsistent with the requirements for systems of earthing applying to the electricity entity under section&#160;245 . Maximum penalty—40 penalty units.","sortOrder":60},{"sectionNumber":"pt.4","sectionType":"part","heading":"In-scope electrical equipment","content":"# In-scope electrical equipment","sortOrder":61},{"sectionNumber":"pt.4-div.1","sectionType":"division","heading":"Preliminary","content":"## Preliminary","sortOrder":62},{"sectionNumber":"sec.49","sectionType":"section","heading":"Application of part","content":"### sec.49 Application of part\n\nThis part prescribes matters for the purposes of part&#160;2A of the Act .","sortOrder":63},{"sectionNumber":"sec.50","sectionType":"section","heading":"Definitions for part","content":"### sec.50 Definitions for part\n\nIn this part—\ncertificate of conformity means a certificate—\nstating that a type of level 3 in-scope electrical equipment complies with the relevant standard for that type; and\nissued—\nunder division&#160;7 or under a recognised external certification scheme; or\nunder a corresponding law or a scheme provided for under that law; and\ncomplying with the requirements relating to issuing a certificate under the equipment safety rules.\ncertificate of suitability means a certificate—\nstating that a type of level 1 or 2 in-scope electrical equipment complies with the relevant standard for the type of in-scope electrical equipment; and\nissued under any 1 of the following—\na declared scheme under section&#160;96 ;\na program established under section&#160;116 ;\na corresponding law;\na scheme under a corresponding law that substantially corresponds to a declared scheme under section&#160;96 ; and\ncomplying with the requirements relating to issuing a certificate under the equipment safety rules.\ndate of registration , for registration of a responsible supplier of in-scope electrical equipment or of equipment as a type of level 2 or 3 in-scope electrical equipment, means the date shown in the national register as the date of registration of the responsible supplier or type.\ndefining standard means AS/NZS 4417 (Regulatory compliance mark for electrical and electronic equipment).\nfalse declaration includes an incorrect or misleading declaration.\nfalse information includes incorrect or misleading information.\nfamily , of a type of level 1, 2 or 3 in-scope electrical equipment, means items of the type that—\nhave the same basic electrical characteristics and material composition but may differ in dimension, colour or other aspects; and\nhaving regard to the relevant standard for the type, are able to be covered by a single test report.\nlevel 1 , for in-scope electrical equipment, see section&#160;54 (1) .\nlevel 2 , for in-scope electrical equipment, see section&#160;54 (2) .\nlevel 3 , for in-scope electrical equipment, see section&#160;54 (3) .\nmeets , a relevant standard, means complies with the safety requirements, electrical or otherwise, of the standard.\nRCM means the regulatory compliance mark under the defining standard.\nregistered see section&#160;52 .\nregistered responsible supplier means a responsible supplier of in-scope electrical equipment who is registered.\nrelevant person means—\nan individual who resides in Queensland; or\na corporation whose—\nregistered office under the Corporations Act is in Queensland; or\nprincipal place of business is in Queensland.\nrelevant responsible supplier , of in-scope electrical equipment, means—\nif the responsible supplier of the in-scope electrical equipment is an individual—an individual who resides in Queensland; or\nif the responsible supplier of the in-scope electrical equipment is a corporation—a corporation whose—\nregistered office under the Corporations Act is in Queensland; or\nprincipal place of business is in Queensland.\nrelevant standard —\nfor a type of level 1 in-scope electrical equipment, see section&#160;55 (1) ; or\nfor a type of level 2 or level 3 in-scope electrical equipment, see section&#160;56 (1) .\nsecond-hand dealer see the Second-hand Dealers and Pawnbrokers Act 2003 , schedule&#160;3 .\nsecond-hand item means an item of level 1, 2 or 3 in-scope electrical equipment that has previously been sold, other than electrical equipment—\npreviously sold by wholesale; or\nacquired by a person for the production or manufacture of another item of electrical equipment; or\nacquired by a person, other than a second-hand dealer, for the purpose of resupply of the electrical equipment; or\nthe resupply of electrical equipment by sale, exchange, lease, hire, hire-purchase or other arrangement\nreturned to a supplier for refund or exchange.\ntest report means a document that presents test results and other information relevant to the test.\n- (a) stating that a type of level 3 in-scope electrical equipment complies with the relevant standard for that type; and\n- (b) issued— (i) under division&#160;7 or under a recognised external certification scheme; or (ii) under a corresponding law or a scheme provided for under that law; and\n- (i) under division&#160;7 or under a recognised external certification scheme; or\n- (ii) under a corresponding law or a scheme provided for under that law; and\n- (c) complying with the requirements relating to issuing a certificate under the equipment safety rules.\n- (i) under division&#160;7 or under a recognised external certification scheme; or\n- (ii) under a corresponding law or a scheme provided for under that law; and\n- (a) stating that a type of level 1 or 2 in-scope electrical equipment complies with the relevant standard for the type of in-scope electrical equipment; and\n- (b) issued under any 1 of the following— (i) a declared scheme under section&#160;96 ; (ii) a program established under section&#160;116 ; (iii) a corresponding law; (iv) a scheme under a corresponding law that substantially corresponds to a declared scheme under section&#160;96 ; and\n- (i) a declared scheme under section&#160;96 ;\n- (ii) a program established under section&#160;116 ;\n- (iii) a corresponding law;\n- (iv) a scheme under a corresponding law that substantially corresponds to a declared scheme under section&#160;96 ; and\n- (c) complying with the requirements relating to issuing a certificate under the equipment safety rules.\n- (i) a declared scheme under section&#160;96 ;\n- (ii) a program established under section&#160;116 ;\n- (iii) a corresponding law;\n- (iv) a scheme under a corresponding law that substantially corresponds to a declared scheme under section&#160;96 ; and\n- (a) have the same basic electrical characteristics and material composition but may differ in dimension, colour or other aspects; and\n- (b) having regard to the relevant standard for the type, are able to be covered by a single test report.\n- (a) an individual who resides in Queensland; or\n- (b) a corporation whose— (i) registered office under the Corporations Act is in Queensland; or (ii) principal place of business is in Queensland.\n- (i) registered office under the Corporations Act is in Queensland; or\n- (ii) principal place of business is in Queensland.\n- (i) registered office under the Corporations Act is in Queensland; or\n- (ii) principal place of business is in Queensland.\n- (a) if the responsible supplier of the in-scope electrical equipment is an individual—an individual who resides in Queensland; or\n- (b) if the responsible supplier of the in-scope electrical equipment is a corporation—a corporation whose— (i) registered office under the Corporations Act is in Queensland; or (ii) principal place of business is in Queensland.\n- (i) registered office under the Corporations Act is in Queensland; or\n- (ii) principal place of business is in Queensland.\n- (i) registered office under the Corporations Act is in Queensland; or\n- (ii) principal place of business is in Queensland.\n- (a) for a type of level 1 in-scope electrical equipment, see section&#160;55 (1) ; or\n- (b) for a type of level 2 or level 3 in-scope electrical equipment, see section&#160;56 (1) .\n- (a) previously sold by wholesale; or\n- (b) acquired by a person for the production or manufacture of another item of electrical equipment; or\n- (c) acquired by a person, other than a second-hand dealer, for the purpose of resupply of the electrical equipment; or Examples of resupply of electrical equipment— the resupply of electrical equipment by sale, exchange, lease, hire, hire-purchase or other arrangement\n- (d) returned to a supplier for refund or exchange.","sortOrder":64},{"sectionNumber":"sec.51","sectionType":"section","heading":"Voltage range for in-scope electrical equipment— Act , s&#160;48B","content":"### sec.51 Voltage range for in-scope electrical equipment— Act , s&#160;48B\n\nFor section&#160;48B (1) (a) of the Act , the voltage range is low voltage.","sortOrder":65},{"sectionNumber":"sec.52","sectionType":"section","heading":"Registration for particular purposes","content":"### sec.52 Registration for particular purposes\n\nA responsible supplier is registered if the supplier is recorded in the part of the national register that records registered responsible suppliers.\nElectrical equipment is registered as a type of level 2 or 3 in-scope electrical equipment if the equipment is recorded, in relation to a registered responsible supplier, as equipment of that type in the part of the national register that records registered in-scope electrical equipment of that type.\nLevel 1 in-scope electrical equipment is not required to be registered under this part.\nIn-scope electrical equipment of a particular type is registered in relation to a particular registered responsible supplier if it is registered as mentioned in subsection&#160;(2) in relation to the responsible supplier.\n(sec.52-ssec.1) A responsible supplier is registered if the supplier is recorded in the part of the national register that records registered responsible suppliers.\n(sec.52-ssec.2) Electrical equipment is registered as a type of level 2 or 3 in-scope electrical equipment if the equipment is recorded, in relation to a registered responsible supplier, as equipment of that type in the part of the national register that records registered in-scope electrical equipment of that type. Level 1 in-scope electrical equipment is not required to be registered under this part.\n(sec.52-ssec.3) In-scope electrical equipment of a particular type is registered in relation to a particular registered responsible supplier if it is registered as mentioned in subsection&#160;(2) in relation to the responsible supplier.","sortOrder":66},{"sectionNumber":"sec.53","sectionType":"section","heading":"Component is not a separate item","content":"### sec.53 Component is not a separate item\n\nThis section applies if an item of a type of in-scope electrical equipment includes 2 or more components of types of in-scope electrical equipment that are permanently attached to the item.\nThe components are not separate items of types of in-scope electrical equipment for the purposes of registration under section&#160;52 .\nA type of in-scope electrical equipment, being a refrigerator, includes a number of components each of which, taken separately, is itself an item of a type of in-scope electrical equipment. If a refrigerator of the type is sold, the item sold is the refrigerator. There is not a separate sale of each of the components.\n(sec.53-ssec.1) This section applies if an item of a type of in-scope electrical equipment includes 2 or more components of types of in-scope electrical equipment that are permanently attached to the item.\n(sec.53-ssec.2) The components are not separate items of types of in-scope electrical equipment for the purposes of registration under section&#160;52 . A type of in-scope electrical equipment, being a refrigerator, includes a number of components each of which, taken separately, is itself an item of a type of in-scope electrical equipment. If a refrigerator of the type is sold, the item sold is the refrigerator. There is not a separate sale of each of the components.","sortOrder":67},{"sectionNumber":"sec.54","sectionType":"section","heading":"Meanings of level 1 , level 2 and level 3 in-scope electrical equipment","content":"### sec.54 Meanings of level 1 , level 2 and level 3 in-scope electrical equipment\n\nElectrical equipment is level 1 in-scope electrical equipment if it is a type of in-scope electrical equipment that is not classified under the defining standard as level 2 or level 3.\nElectrical equipment is level 2 in-scope electrical equipment if it is a type of in-scope electrical equipment classified as level 2 under the defining standard.\nElectrical equipment is level 3 in-scope electrical equipment if it is a type of in-scope electrical equipment classified as level 3 under the defining standard.\nAlso, if a type of in-scope electrical equipment is level 1, 2 or 3 in-scope electrical equipment, each item of the family of the type is also level 1, 2 or 3 in-scope electrical equipment.\n(sec.54-ssec.1) Electrical equipment is level 1 in-scope electrical equipment if it is a type of in-scope electrical equipment that is not classified under the defining standard as level 2 or level 3.\n(sec.54-ssec.2) Electrical equipment is level 2 in-scope electrical equipment if it is a type of in-scope electrical equipment classified as level 2 under the defining standard.\n(sec.54-ssec.3) Electrical equipment is level 3 in-scope electrical equipment if it is a type of in-scope electrical equipment classified as level 3 under the defining standard.\n(sec.54-ssec.4) Also, if a type of in-scope electrical equipment is level 1, 2 or 3 in-scope electrical equipment, each item of the family of the type is also level 1, 2 or 3 in-scope electrical equipment.","sortOrder":68},{"sectionNumber":"sec.55","sectionType":"section","heading":"Meaning of relevant standard for level 1 in-scope electrical equipment","content":"### sec.55 Meaning of relevant standard for level 1 in-scope electrical equipment\n\nThe relevant standard for a type of level 1 in-scope electrical equipment is—\nif there is a Standards Australia or joint Standards Australia and Standards New Zealand standard that applies specifically to the type—that standard together with AS/NZS 3820 (Essential safety requirements for electrical equipment); or\nif there is not a Standards Australia or joint Standards Australia and Standards New Zealand standard that applies specifically to the type and there is an IEC standard that applies specifically to the type—the IEC standard together with AS/NZS 3820; or\nif neither paragraph&#160;(a) nor (b) applies—AS/NZS 3820.\nIn this section—\nIEC standard means an International Electrotechnical Commission standard.\n(sec.55-ssec.1) The relevant standard for a type of level 1 in-scope electrical equipment is— if there is a Standards Australia or joint Standards Australia and Standards New Zealand standard that applies specifically to the type—that standard together with AS/NZS 3820 (Essential safety requirements for electrical equipment); or if there is not a Standards Australia or joint Standards Australia and Standards New Zealand standard that applies specifically to the type and there is an IEC standard that applies specifically to the type—the IEC standard together with AS/NZS 3820; or if neither paragraph&#160;(a) nor (b) applies—AS/NZS 3820.\n(sec.55-ssec.2) In this section— IEC standard means an International Electrotechnical Commission standard.\n- (a) if there is a Standards Australia or joint Standards Australia and Standards New Zealand standard that applies specifically to the type—that standard together with AS/NZS 3820 (Essential safety requirements for electrical equipment); or\n- (b) if there is not a Standards Australia or joint Standards Australia and Standards New Zealand standard that applies specifically to the type and there is an IEC standard that applies specifically to the type—the IEC standard together with AS/NZS 3820; or\n- (c) if neither paragraph&#160;(a) nor (b) applies—AS/NZS 3820.","sortOrder":69},{"sectionNumber":"sec.56","sectionType":"section","heading":"Meaning of relevant standard for level 2 or 3 in-scope electrical equipment","content":"### sec.56 Meaning of relevant standard for level 2 or 3 in-scope electrical equipment\n\nA standard is a relevant standard for a type of level 2 or level 3 in-scope electrical equipment if it is a standard—\nshown in the defining standard as the relevant standard for the type, and the standard can be readily applied to the type; or\naccepted by the regulator as a standard that can be readily applied to the type; or\naccepted under a corresponding law as a standard that can be readily applied to the type.\nThe acceptance of a standard under subsection&#160;(1) (b) or (c) has effect subject to compliance with any requirements stated—\nfor subsection&#160;(1) (b) —by the regulator as part of the regulator’s acceptance of the standard; or\nfor subsection&#160;(1) (c) —as part of the acceptance of the standard under the corresponding law.\n(sec.56-ssec.1) A standard is a relevant standard for a type of level 2 or level 3 in-scope electrical equipment if it is a standard— shown in the defining standard as the relevant standard for the type, and the standard can be readily applied to the type; or accepted by the regulator as a standard that can be readily applied to the type; or accepted under a corresponding law as a standard that can be readily applied to the type.\n(sec.56-ssec.2) The acceptance of a standard under subsection&#160;(1) (b) or (c) has effect subject to compliance with any requirements stated— for subsection&#160;(1) (b) —by the regulator as part of the regulator’s acceptance of the standard; or for subsection&#160;(1) (c) —as part of the acceptance of the standard under the corresponding law.\n- (a) shown in the defining standard as the relevant standard for the type, and the standard can be readily applied to the type; or\n- (b) accepted by the regulator as a standard that can be readily applied to the type; or\n- (c) accepted under a corresponding law as a standard that can be readily applied to the type.\n- (a) for subsection&#160;(1) (b) —by the regulator as part of the regulator’s acceptance of the standard; or\n- (b) for subsection&#160;(1) (c) —as part of the acceptance of the standard under the corresponding law.","sortOrder":70},{"sectionNumber":"pt.4-div.2","sectionType":"division","heading":"Registration of responsible suppliers and levels 2 and 3 in-scope electrical equipment","content":"## Registration of responsible suppliers and levels 2 and 3 in-scope electrical equipment","sortOrder":71},{"sectionNumber":"sec.57","sectionType":"section","heading":"Responsible supplier may register","content":"### sec.57 Responsible supplier may register\n\nA responsible supplier of in-scope electrical equipment may register as a responsible supplier of the in-scope electrical equipment.\nHowever, the responsible supplier is not eligible to register if the responsible supplier—\ndoes not have an ABN or an IRD; or\nis ineligible to register under section&#160;70 (2) .\nAs part of the registration process, the responsible supplier must—\nmake the responsible supplier’s declaration as required by the equipment safety rules; and\npay the registration fee.\nThe declaration required by the equipment safety rules must include the information mentioned in schedule&#160;3 , part&#160;1 .\nA relevant person must not, in registering or purporting to register as a responsible supplier, give false information or make a false declaration.\nMaximum penalty—40 penalty units.\nIn this section—\nABN (short for ‘Australian Business Number’) has the meaning given by the A New Tax System (Australian Business Number) Act 1999 (Cwlth) , section&#160;41 .\nIRD means a tax file number within the meaning of the Income Tax Act 2007 (NZ) , section YA1.\n(sec.57-ssec.1) A responsible supplier of in-scope electrical equipment may register as a responsible supplier of the in-scope electrical equipment.\n(sec.57-ssec.2) However, the responsible supplier is not eligible to register if the responsible supplier— does not have an ABN or an IRD; or is ineligible to register under section&#160;70 (2) .\n(sec.57-ssec.3) As part of the registration process, the responsible supplier must— make the responsible supplier’s declaration as required by the equipment safety rules; and pay the registration fee.\n(sec.57-ssec.4) The declaration required by the equipment safety rules must include the information mentioned in schedule&#160;3 , part&#160;1 .\n(sec.57-ssec.5) A relevant person must not, in registering or purporting to register as a responsible supplier, give false information or make a false declaration. Maximum penalty—40 penalty units.\n(sec.57-ssec.6) In this section— ABN (short for ‘Australian Business Number’) has the meaning given by the A New Tax System (Australian Business Number) Act 1999 (Cwlth) , section&#160;41 . IRD means a tax file number within the meaning of the Income Tax Act 2007 (NZ) , section YA1.\n- (a) does not have an ABN or an IRD; or\n- (b) is ineligible to register under section&#160;70 (2) .\n- (a) make the responsible supplier’s declaration as required by the equipment safety rules; and\n- (b) pay the registration fee.","sortOrder":72},{"sectionNumber":"sec.58","sectionType":"section","heading":"Term of registration","content":"### sec.58 Term of registration\n\nRegistration of a responsible supplier of in-scope electrical equipment is for the term of 1 year starting on the date of registration unless sooner cancelled.","sortOrder":73},{"sectionNumber":"sec.59","sectionType":"section","heading":"Renewal of registration","content":"### sec.59 Renewal of registration\n\nA responsible supplier of in-scope electrical equipment may renew the supplier’s registration from time to time by registering again under section&#160;57 .","sortOrder":74},{"sectionNumber":"sec.60","sectionType":"section","heading":"Responsible supplier must ensure details in national register are current","content":"### sec.60 Responsible supplier must ensure details in national register are current\n\nThis section applies if the details of any matter entered by a relevant responsible supplier of in-scope electrical equipment in the national register relating to the registration of any matter change during the term of registration.\nWithin 30 days after the change, the relevant responsible supplier must correct the details in the national register.\nMaximum penalty—40 penalty units.\n(sec.60-ssec.1) This section applies if the details of any matter entered by a relevant responsible supplier of in-scope electrical equipment in the national register relating to the registration of any matter change during the term of registration.\n(sec.60-ssec.2) Within 30 days after the change, the relevant responsible supplier must correct the details in the national register. Maximum penalty—40 penalty units.","sortOrder":75},{"sectionNumber":"sec.61","sectionType":"section","heading":"Registration","content":"### sec.61 Registration\n\nA registered responsible supplier of a type of level 2 in-scope electrical equipment may register the type as level 2 in-scope electrical equipment.\nHowever, the registered responsible supplier is not eligible to register the electrical equipment if the responsible supplier is ineligible to do so under section&#160;70 (3) .\nEach registration must relate only to a single type of level 2 in-scope electrical equipment.\nAs part of the registration process, the registered responsible supplier must—\nmake the responsible supplier’s level 2 in-scope electrical equipment declaration under the equipment safety rules; and\nif the compliance folder required to be kept for the type of level 2 in-scope electrical equipment under section&#160;77 is not available in the national register—state the address where it is kept; and\npay the registration fee.\nThe declaration under the equipment safety rules must include the information mentioned in schedule&#160;3 , part&#160;2 .\nA relevant person must not, in registering or purporting to register a type of level 2 in-scope electrical equipment, give false information or make a false declaration.\nMaximum penalty for subsection&#160;(6) —40 penalty units.\n(sec.61-ssec.1) A registered responsible supplier of a type of level 2 in-scope electrical equipment may register the type as level 2 in-scope electrical equipment.\n(sec.61-ssec.2) However, the registered responsible supplier is not eligible to register the electrical equipment if the responsible supplier is ineligible to do so under section&#160;70 (3) .\n(sec.61-ssec.3) Each registration must relate only to a single type of level 2 in-scope electrical equipment.\n(sec.61-ssec.4) As part of the registration process, the registered responsible supplier must— make the responsible supplier’s level 2 in-scope electrical equipment declaration under the equipment safety rules; and if the compliance folder required to be kept for the type of level 2 in-scope electrical equipment under section&#160;77 is not available in the national register—state the address where it is kept; and pay the registration fee.\n(sec.61-ssec.5) The declaration under the equipment safety rules must include the information mentioned in schedule&#160;3 , part&#160;2 .\n(sec.61-ssec.6) A relevant person must not, in registering or purporting to register a type of level 2 in-scope electrical equipment, give false information or make a false declaration. Maximum penalty for subsection&#160;(6) —40 penalty units.\n- (a) make the responsible supplier’s level 2 in-scope electrical equipment declaration under the equipment safety rules; and\n- (b) if the compliance folder required to be kept for the type of level 2 in-scope electrical equipment under section&#160;77 is not available in the national register—state the address where it is kept; and\n- (c) pay the registration fee.","sortOrder":76},{"sectionNumber":"sec.62","sectionType":"section","heading":"Term of registration","content":"### sec.62 Term of registration\n\nRegistration of a type of level 2 in-scope electrical equipment is for the term of 1, 2 or 5 years starting on the date of registration unless it is sooner cancelled.\nSubsection&#160;(3) applies if the responsible supplier’s registration lapses for a period during the term of the electrical equipment’s registration.\nThe electrical equipment’s registration is suspended during that period.\n(sec.62-ssec.1) Registration of a type of level 2 in-scope electrical equipment is for the term of 1, 2 or 5 years starting on the date of registration unless it is sooner cancelled.\n(sec.62-ssec.2) Subsection&#160;(3) applies if the responsible supplier’s registration lapses for a period during the term of the electrical equipment’s registration.\n(sec.62-ssec.3) The electrical equipment’s registration is suspended during that period.","sortOrder":77},{"sectionNumber":"sec.63","sectionType":"section","heading":"Renewal of registration","content":"### sec.63 Renewal of registration\n\nA registered responsible supplier may renew the registration of a type of level 2 in-scope electrical equipment from time to time by registering it again under section&#160;61 .","sortOrder":78},{"sectionNumber":"sec.64","sectionType":"section","heading":"Registration","content":"### sec.64 Registration\n\nA registered responsible supplier of a type of level 3 in-scope electrical equipment may register the type as level 3 in-scope electrical equipment.\nHowever, the registered responsible supplier is not eligible to carry out the registration if the responsible supplier is ineligible to do so under section&#160;70 (3) .\nEach registration must relate only to a single type of level 3 in-scope electrical equipment.\nAs part of the registration process, the registered responsible supplier must—\nidentify a certificate of conformity applicable to the type of level 3 in-scope electrical equipment; and\nmake the responsible supplier’s level 3 in-scope electrical equipment declaration under the equipment safety rules; and\npay the registration fee.\nThe declaration under the equipment safety rules must include the information mentioned in schedule&#160;3 , part&#160;3 .\nA relevant person must not, in registering or purporting to register a type of level 3 in-scope electrical equipment, give false information or make a false declaration.\nMaximum penalty for subsection&#160;(6) —40 penalty units.\n(sec.64-ssec.1) A registered responsible supplier of a type of level 3 in-scope electrical equipment may register the type as level 3 in-scope electrical equipment.\n(sec.64-ssec.2) However, the registered responsible supplier is not eligible to carry out the registration if the responsible supplier is ineligible to do so under section&#160;70 (3) .\n(sec.64-ssec.3) Each registration must relate only to a single type of level 3 in-scope electrical equipment.\n(sec.64-ssec.4) As part of the registration process, the registered responsible supplier must— identify a certificate of conformity applicable to the type of level 3 in-scope electrical equipment; and make the responsible supplier’s level 3 in-scope electrical equipment declaration under the equipment safety rules; and pay the registration fee.\n(sec.64-ssec.5) The declaration under the equipment safety rules must include the information mentioned in schedule&#160;3 , part&#160;3 .\n(sec.64-ssec.6) A relevant person must not, in registering or purporting to register a type of level 3 in-scope electrical equipment, give false information or make a false declaration. Maximum penalty for subsection&#160;(6) —40 penalty units.\n- (a) identify a certificate of conformity applicable to the type of level 3 in-scope electrical equipment; and\n- (b) make the responsible supplier’s level 3 in-scope electrical equipment declaration under the equipment safety rules; and\n- (c) pay the registration fee.","sortOrder":79},{"sectionNumber":"sec.65","sectionType":"section","heading":"Term of registration","content":"### sec.65 Term of registration\n\nRegistration of a type of level 3 in-scope electrical equipment is for the term of 1, 2 or 5 years starting on the date of registration unless it is sooner cancelled.\nHowever, the term of registration must not be longer than the term for which the certificate of conformity applying to the type and identified under section&#160;64 (4) (a) is current at the time of registration.\nAlso, if the certificate of conformity is cancelled the term of registration ends.\nSubsection&#160;(5) applies if the responsible supplier’s registration lapses for a period during the term of the electrical equipment’s registration.\nThe electrical equipment’s registration is suspended during that period.\n(sec.65-ssec.1) Registration of a type of level 3 in-scope electrical equipment is for the term of 1, 2 or 5 years starting on the date of registration unless it is sooner cancelled.\n(sec.65-ssec.2) However, the term of registration must not be longer than the term for which the certificate of conformity applying to the type and identified under section&#160;64 (4) (a) is current at the time of registration.\n(sec.65-ssec.3) Also, if the certificate of conformity is cancelled the term of registration ends.\n(sec.65-ssec.4) Subsection&#160;(5) applies if the responsible supplier’s registration lapses for a period during the term of the electrical equipment’s registration.\n(sec.65-ssec.5) The electrical equipment’s registration is suspended during that period.","sortOrder":80},{"sectionNumber":"sec.66","sectionType":"section","heading":"Renewal of registration","content":"### sec.66 Renewal of registration\n\nA registered responsible supplier may renew the registration of a type of level 3 in-scope electrical equipment from time to time by registering it again under section&#160;64 .","sortOrder":81},{"sectionNumber":"sec.67","sectionType":"section","heading":"Relevant person may be punished only once","content":"### sec.67 Relevant person may be punished only once\n\nThis section applies if—\nan act or omission of a relevant person is an offence against section&#160;57 (5) , 60 (2) , 61 (6) or 64 (6) and also under a corresponding law; and\nthe relevant person is punished for the offence under the corresponding law.\nThe relevant person must not be punished for the same offence under this regulation.\n(sec.67-ssec.1) This section applies if— an act or omission of a relevant person is an offence against section&#160;57 (5) , 60 (2) , 61 (6) or 64 (6) and also under a corresponding law; and the relevant person is punished for the offence under the corresponding law.\n(sec.67-ssec.2) The relevant person must not be punished for the same offence under this regulation.\n- (a) an act or omission of a relevant person is an offence against section&#160;57 (5) , 60 (2) , 61 (6) or 64 (6) and also under a corresponding law; and\n- (b) the relevant person is punished for the offence under the corresponding law.","sortOrder":82},{"sectionNumber":"sec.68","sectionType":"section","heading":"Grounds for cancelling registration of responsible supplier or level 2 or 3 in-scope electrical equipment","content":"### sec.68 Grounds for cancelling registration of responsible supplier or level 2 or 3 in-scope electrical equipment\n\nThe following are grounds for cancelling the registration of a responsible supplier’s in-scope electrical equipment—\nthe responsible supplier commits an offence against the Act or this regulation;\nthe responsible supplier contravenes a requirement of a recall order;\nthe responsible supplier is a relevant responsible supplier and the registration was obtained by giving false information or making a false declaration;\nthe registration of a type of level 2 or 3 in-scope electrical equipment registered in relation to the responsible supplier is cancelled under section&#160;71 .\nThe following are grounds for cancelling the registration in relation to a registered responsible supplier of a type of level 2 or 3 in-scope electrical equipment—\nthe responsible supplier commits an offence against the Act or this regulation in relation to the type;\nthe responsible supplier contravenes a requirement of a recall order relating to the type;\nthe responsible supplier is a relevant responsible supplier and—\nelectrical equipment of the type does not meet the relevant standard that was the relevant standard for the type at the time the type was registered; or\nthe relevant standard for the type changed after the type was registered because of safety concerns relating to the type and the type does not meet the current relevant standard for the type; or\nan item of electrical equipment of the type is, or is likely to be or to become, dangerous in normal use; or\nthe registration was obtained by giving false information or making a false declaration.\n(sec.68-ssec.1) The following are grounds for cancelling the registration of a responsible supplier’s in-scope electrical equipment— the responsible supplier commits an offence against the Act or this regulation; the responsible supplier contravenes a requirement of a recall order; the responsible supplier is a relevant responsible supplier and the registration was obtained by giving false information or making a false declaration; the registration of a type of level 2 or 3 in-scope electrical equipment registered in relation to the responsible supplier is cancelled under section&#160;71 .\n(sec.68-ssec.2) The following are grounds for cancelling the registration in relation to a registered responsible supplier of a type of level 2 or 3 in-scope electrical equipment— the responsible supplier commits an offence against the Act or this regulation in relation to the type; the responsible supplier contravenes a requirement of a recall order relating to the type; the responsible supplier is a relevant responsible supplier and— electrical equipment of the type does not meet the relevant standard that was the relevant standard for the type at the time the type was registered; or the relevant standard for the type changed after the type was registered because of safety concerns relating to the type and the type does not meet the current relevant standard for the type; or an item of electrical equipment of the type is, or is likely to be or to become, dangerous in normal use; or the registration was obtained by giving false information or making a false declaration.\n- (a) the responsible supplier commits an offence against the Act or this regulation;\n- (b) the responsible supplier contravenes a requirement of a recall order;\n- (c) the responsible supplier is a relevant responsible supplier and the registration was obtained by giving false information or making a false declaration;\n- (d) the registration of a type of level 2 or 3 in-scope electrical equipment registered in relation to the responsible supplier is cancelled under section&#160;71 .\n- (a) the responsible supplier commits an offence against the Act or this regulation in relation to the type;\n- (b) the responsible supplier contravenes a requirement of a recall order relating to the type;\n- (c) the responsible supplier is a relevant responsible supplier and— (i) electrical equipment of the type does not meet the relevant standard that was the relevant standard for the type at the time the type was registered; or (ii) the relevant standard for the type changed after the type was registered because of safety concerns relating to the type and the type does not meet the current relevant standard for the type; or (iii) an item of electrical equipment of the type is, or is likely to be or to become, dangerous in normal use; or (iv) the registration was obtained by giving false information or making a false declaration.\n- (i) electrical equipment of the type does not meet the relevant standard that was the relevant standard for the type at the time the type was registered; or\n- (ii) the relevant standard for the type changed after the type was registered because of safety concerns relating to the type and the type does not meet the current relevant standard for the type; or\n- (iii) an item of electrical equipment of the type is, or is likely to be or to become, dangerous in normal use; or\n- (iv) the registration was obtained by giving false information or making a false declaration.\n- (i) electrical equipment of the type does not meet the relevant standard that was the relevant standard for the type at the time the type was registered; or\n- (ii) the relevant standard for the type changed after the type was registered because of safety concerns relating to the type and the type does not meet the current relevant standard for the type; or\n- (iii) an item of electrical equipment of the type is, or is likely to be or to become, dangerous in normal use; or\n- (iv) the registration was obtained by giving false information or making a false declaration.","sortOrder":83},{"sectionNumber":"sec.69","sectionType":"section","heading":"Procedure before cancellation","content":"### sec.69 Procedure before cancellation\n\nThis section applies if the regulator considers a ground exists under section&#160;68 to cancel the registration of a matter.\nThe regulator must, before taking the action, give the responsible supplier of in-scope electrical equipment written notice—\nstating that the regulator is considering cancelling the registration; and\nstating each ground for the proposed cancellation; and\noutlining the facts and circumstances forming the basis for each ground; and\ninviting the responsible supplier to show, within a stated period of at least 28 days, why the registration should not be cancelled.\n(sec.69-ssec.1) This section applies if the regulator considers a ground exists under section&#160;68 to cancel the registration of a matter.\n(sec.69-ssec.2) The regulator must, before taking the action, give the responsible supplier of in-scope electrical equipment written notice— stating that the regulator is considering cancelling the registration; and stating each ground for the proposed cancellation; and outlining the facts and circumstances forming the basis for each ground; and inviting the responsible supplier to show, within a stated period of at least 28 days, why the registration should not be cancelled.\n- (a) stating that the regulator is considering cancelling the registration; and\n- (b) stating each ground for the proposed cancellation; and\n- (c) outlining the facts and circumstances forming the basis for each ground; and\n- (d) inviting the responsible supplier to show, within a stated period of at least 28 days, why the registration should not be cancelled.","sortOrder":84},{"sectionNumber":"sec.70","sectionType":"section","heading":"Cancellation","content":"### sec.70 Cancellation\n\nIf, after considering all written representations (if any) made by the responsible supplier of in-scope electrical equipment within the stated time, the regulator still considers a ground exists to cancel the registration, the regulator may cancel the registration.\nIf a responsible supplier’s registration is cancelled under this section, the responsible supplier is not eligible to register again for the period of 1 year starting on the day the registration is cancelled.\nIf the registration of a type of level 2 or 3 in-scope electrical equipment registered in relation to a registered responsible supplier is cancelled under this section, the responsible supplier is not eligible to again register the type for the period of 12 months starting on the date of cancellation.\nIf the regulator cancels a registration under this section, the regulator must—\nnotify the cancellation—\nby publishing notice of the cancellation in a newspaper circulating throughout Australia and, if New Zealand is a participating jurisdiction, in a newspaper circulating throughout New Zealand; and\nby recording notice of the cancellation in the national register; and\ngive the responsible supplier an information notice for the decision to cancel the registration.\nThe information notice must state the period for which the responsible supplier is not eligible to—\nregister; or\nregister the type of level 2 or 3 in-scope electrical equipment.\n(sec.70-ssec.1) If, after considering all written representations (if any) made by the responsible supplier of in-scope electrical equipment within the stated time, the regulator still considers a ground exists to cancel the registration, the regulator may cancel the registration.\n(sec.70-ssec.2) If a responsible supplier’s registration is cancelled under this section, the responsible supplier is not eligible to register again for the period of 1 year starting on the day the registration is cancelled.\n(sec.70-ssec.3) If the registration of a type of level 2 or 3 in-scope electrical equipment registered in relation to a registered responsible supplier is cancelled under this section, the responsible supplier is not eligible to again register the type for the period of 12 months starting on the date of cancellation.\n(sec.70-ssec.4) If the regulator cancels a registration under this section, the regulator must— notify the cancellation— by publishing notice of the cancellation in a newspaper circulating throughout Australia and, if New Zealand is a participating jurisdiction, in a newspaper circulating throughout New Zealand; and by recording notice of the cancellation in the national register; and give the responsible supplier an information notice for the decision to cancel the registration.\n(sec.70-ssec.5) The information notice must state the period for which the responsible supplier is not eligible to— register; or register the type of level 2 or 3 in-scope electrical equipment.\n- (a) notify the cancellation— (i) by publishing notice of the cancellation in a newspaper circulating throughout Australia and, if New Zealand is a participating jurisdiction, in a newspaper circulating throughout New Zealand; and (ii) by recording notice of the cancellation in the national register; and\n- (i) by publishing notice of the cancellation in a newspaper circulating throughout Australia and, if New Zealand is a participating jurisdiction, in a newspaper circulating throughout New Zealand; and\n- (ii) by recording notice of the cancellation in the national register; and\n- (b) give the responsible supplier an information notice for the decision to cancel the registration.\n- (i) by publishing notice of the cancellation in a newspaper circulating throughout Australia and, if New Zealand is a participating jurisdiction, in a newspaper circulating throughout New Zealand; and\n- (ii) by recording notice of the cancellation in the national register; and\n- (a) register; or\n- (b) register the type of level 2 or 3 in-scope electrical equipment.","sortOrder":85},{"sectionNumber":"sec.71","sectionType":"section","heading":"Cancellation at responsible supplier’s request","content":"### sec.71 Cancellation at responsible supplier’s request\n\nThe regulator must, by notice recorded in the national register, cancel the registration of a responsible supplier of in-scope electrical equipment, or the registration in relation to a responsible supplier of a type of level 2 or 3 in-scope electrical equipment, if asked to do so by the responsible supplier.","sortOrder":86},{"sectionNumber":"pt.4-div.3","sectionType":"division","heading":"Sales of in-scope electrical equipment","content":"## Sales of in-scope electrical equipment","sortOrder":87},{"sectionNumber":"sec.72","sectionType":"section","heading":"Sale of level 1 in-scope electrical equipment by responsible supplier","content":"### sec.72 Sale of level 1 in-scope electrical equipment by responsible supplier\n\nA responsible supplier of a type of level 1 in-scope electrical equipment must not sell an item of the type unless—\nthe responsible supplier is a registered responsible supplier; and\nthe item meets the relevant standard for the type as in force—\nif the responsible supplier is a manufacturer of the type—at the time the item was manufactured by the responsible supplier; or\nif the responsible supplier is an importer of the type—at the time the item was imported by the responsible supplier; and\nthe item is electrically safe.\nMaximum penalty—40 penalty units.\nIt is a defence for the responsible supplier to prove that the responsible supplier obtained the item from a registered responsible supplier.\nThis example assumes New Zealand is a participating jurisdiction.\nA New Zealand responsible supplier (company A) is a registered responsible supplier. Company A imports level 1 in-scope electrical equipment into New Zealand from the United Kingdom. Company B is an Australian company that purchases the level 1 in-scope electrical equipment from company A and imports it into Australia. Company B, although a responsible supplier, is not a registered responsible supplier.\nIf company B were charged with an offence against subsection&#160;(1) in relation to its sale of an item of the equipment, it would be a defence for company B to prove that it obtained the item from company A who is a registered responsible supplier.\n(sec.72-ssec.1) A responsible supplier of a type of level 1 in-scope electrical equipment must not sell an item of the type unless— the responsible supplier is a registered responsible supplier; and the item meets the relevant standard for the type as in force— if the responsible supplier is a manufacturer of the type—at the time the item was manufactured by the responsible supplier; or if the responsible supplier is an importer of the type—at the time the item was imported by the responsible supplier; and the item is electrically safe. Maximum penalty—40 penalty units.\n(sec.72-ssec.2) It is a defence for the responsible supplier to prove that the responsible supplier obtained the item from a registered responsible supplier. This example assumes New Zealand is a participating jurisdiction. A New Zealand responsible supplier (company A) is a registered responsible supplier. Company A imports level 1 in-scope electrical equipment into New Zealand from the United Kingdom. Company B is an Australian company that purchases the level 1 in-scope electrical equipment from company A and imports it into Australia. Company B, although a responsible supplier, is not a registered responsible supplier. If company B were charged with an offence against subsection&#160;(1) in relation to its sale of an item of the equipment, it would be a defence for company B to prove that it obtained the item from company A who is a registered responsible supplier.\n- (a) the responsible supplier is a registered responsible supplier; and\n- (b) the item meets the relevant standard for the type as in force— (i) if the responsible supplier is a manufacturer of the type—at the time the item was manufactured by the responsible supplier; or (ii) if the responsible supplier is an importer of the type—at the time the item was imported by the responsible supplier; and\n- (i) if the responsible supplier is a manufacturer of the type—at the time the item was manufactured by the responsible supplier; or\n- (ii) if the responsible supplier is an importer of the type—at the time the item was imported by the responsible supplier; and\n- (c) the item is electrically safe.\n- (i) if the responsible supplier is a manufacturer of the type—at the time the item was manufactured by the responsible supplier; or\n- (ii) if the responsible supplier is an importer of the type—at the time the item was imported by the responsible supplier; and","sortOrder":88},{"sectionNumber":"sec.73","sectionType":"section","heading":"Sale of level 2 or 3 in-scope electrical equipment by responsible supplier","content":"### sec.73 Sale of level 2 or 3 in-scope electrical equipment by responsible supplier\n\nA responsible supplier of a type of level 2 or 3 in-scope electrical equipment must not sell an item of the type unless—\nthe responsible supplier is a registered responsible supplier; and\nthe type is registered in relation to the responsible supplier; and\nthe item meets the relevant standard for the type as at the time the type became registered as mentioned in paragraph&#160;(b) ; and\nthe item is electrically safe.\nMaximum penalty—40 penalty units.\nIt is a defence for the responsible supplier to prove—\nthat—\nthe responsible supplier obtained the item from a registered responsible supplier; and\nthe type of in-scope electrical equipment to which the item belongs was, at the time of the alleged offence, registered in relation to the registered responsible supplier; or\nthat, at the time of the alleged offence—\nthe responsible supplier was, under the Corporations Act , a related body corporate of a New Zealand registered responsible supplier; and\nthe type of in-scope electrical equipment to which the item belongs was registered in relation to the New Zealand registered responsible supplier.\nIn this section—\nNew Zealand registered responsible supplier means a registered responsible supplier that is, under the Companies Act 1993 (NZ) —\na company; or\nan overseas company carrying on business in New Zealand.\nThis example assumes New Zealand is a participating jurisdiction.\nA New Zealand responsible supplier (company A) is a registered responsible supplier and a type of level 2 in-scope electrical equipment is registered in the national register in relation to company A. Company A imports level 2 in-scope electrical equipment of that type into New Zealand from the United Kingdom. Company B is an Australian company that purchases the level 2 in-scope electrical equipment from company A and imports it into Australia. Company B, although a responsible supplier, is not a registered responsible supplier.\nIf company B were charged with an offence against subsection&#160;(1) in relation to its sale of an item of the equipment, it would be a defence for company B to prove that it obtained the item from company A who is a registered responsible supplier and that the type of in-scope electrical equipment to which the item belonged was, at the time of the alleged offence, registered in the national register in relation to company A.\n(sec.73-ssec.1) A responsible supplier of a type of level 2 or 3 in-scope electrical equipment must not sell an item of the type unless— the responsible supplier is a registered responsible supplier; and the type is registered in relation to the responsible supplier; and the item meets the relevant standard for the type as at the time the type became registered as mentioned in paragraph&#160;(b) ; and the item is electrically safe. Maximum penalty—40 penalty units.\n(sec.73-ssec.2) It is a defence for the responsible supplier to prove— that— the responsible supplier obtained the item from a registered responsible supplier; and the type of in-scope electrical equipment to which the item belongs was, at the time of the alleged offence, registered in relation to the registered responsible supplier; or that, at the time of the alleged offence— the responsible supplier was, under the Corporations Act , a related body corporate of a New Zealand registered responsible supplier; and the type of in-scope electrical equipment to which the item belongs was registered in relation to the New Zealand registered responsible supplier.\n(sec.73-ssec.3) In this section— New Zealand registered responsible supplier means a registered responsible supplier that is, under the Companies Act 1993 (NZ) — a company; or an overseas company carrying on business in New Zealand. This example assumes New Zealand is a participating jurisdiction. A New Zealand responsible supplier (company A) is a registered responsible supplier and a type of level 2 in-scope electrical equipment is registered in the national register in relation to company A. Company A imports level 2 in-scope electrical equipment of that type into New Zealand from the United Kingdom. Company B is an Australian company that purchases the level 2 in-scope electrical equipment from company A and imports it into Australia. Company B, although a responsible supplier, is not a registered responsible supplier. If company B were charged with an offence against subsection&#160;(1) in relation to its sale of an item of the equipment, it would be a defence for company B to prove that it obtained the item from company A who is a registered responsible supplier and that the type of in-scope electrical equipment to which the item belonged was, at the time of the alleged offence, registered in the national register in relation to company A.\n- (a) the responsible supplier is a registered responsible supplier; and\n- (b) the type is registered in relation to the responsible supplier; and\n- (c) the item meets the relevant standard for the type as at the time the type became registered as mentioned in paragraph&#160;(b) ; and\n- (d) the item is electrically safe.\n- (a) that— (i) the responsible supplier obtained the item from a registered responsible supplier; and (ii) the type of in-scope electrical equipment to which the item belongs was, at the time of the alleged offence, registered in relation to the registered responsible supplier; or\n- (i) the responsible supplier obtained the item from a registered responsible supplier; and\n- (ii) the type of in-scope electrical equipment to which the item belongs was, at the time of the alleged offence, registered in relation to the registered responsible supplier; or\n- (b) that, at the time of the alleged offence— (i) the responsible supplier was, under the Corporations Act , a related body corporate of a New Zealand registered responsible supplier; and (ii) the type of in-scope electrical equipment to which the item belongs was registered in relation to the New Zealand registered responsible supplier.\n- (i) the responsible supplier was, under the Corporations Act , a related body corporate of a New Zealand registered responsible supplier; and\n- (ii) the type of in-scope electrical equipment to which the item belongs was registered in relation to the New Zealand registered responsible supplier.\n- (i) the responsible supplier obtained the item from a registered responsible supplier; and\n- (ii) the type of in-scope electrical equipment to which the item belongs was, at the time of the alleged offence, registered in relation to the registered responsible supplier; or\n- (i) the responsible supplier was, under the Corporations Act , a related body corporate of a New Zealand registered responsible supplier; and\n- (ii) the type of in-scope electrical equipment to which the item belongs was registered in relation to the New Zealand registered responsible supplier.\n- (a) a company; or\n- (b) an overseas company carrying on business in New Zealand.","sortOrder":89},{"sectionNumber":"sec.74","sectionType":"section","heading":"Sale of in-scope electrical equipment—general","content":"### sec.74 Sale of in-scope electrical equipment—general\n\nA person must not sell an item of a type of level 1, 2 or 3 in-scope electrical equipment unless the item is marked with the RCM in compliance with the defining standard.\nMaximum penalty—20 penalty units.\nA person must not sell an item of a relevant type if—\nthe item was purchased by the person for the purpose of resale; and\nwhen the person purchased the item, the relevant type was not registered in relation to a registered responsible supplier.\nMaximum penalty—20 penalty units.\nSubsection&#160;(4) applies in relation to a prosecution of an offence against subsection&#160;(2) in which the issue is raised that the person had an honest and reasonable but mistaken belief that the type was registered in relation to a registered responsible supplier based on reasonable monitoring by the person of the national register.\nIn deciding whether the monitoring of the national register was reasonable, regard may be had to the nature of the item and the nature of the person’s business in relation to the item.\nFor subsection&#160;(1) , it is sufficient if the mark is on the item’s labelling or packaging in compliance with the defining standard.\nSubsection&#160;(1) or (2) does not apply if—\nthe person is a responsible supplier of the type of in-scope electrical equipment; or\nthe item is a second-hand item.\nIn this section—\nrelevant type means a type of level 2 or 3 in-scope electrical equipment that is manufactured in, or imported into, Australia or, if New Zealand is a participating jurisdiction, New Zealand.\n(sec.74-ssec.1) A person must not sell an item of a type of level 1, 2 or 3 in-scope electrical equipment unless the item is marked with the RCM in compliance with the defining standard. Maximum penalty—20 penalty units.\n(sec.74-ssec.2) A person must not sell an item of a relevant type if— the item was purchased by the person for the purpose of resale; and when the person purchased the item, the relevant type was not registered in relation to a registered responsible supplier. Maximum penalty—20 penalty units.\n(sec.74-ssec.3) Subsection&#160;(4) applies in relation to a prosecution of an offence against subsection&#160;(2) in which the issue is raised that the person had an honest and reasonable but mistaken belief that the type was registered in relation to a registered responsible supplier based on reasonable monitoring by the person of the national register.\n(sec.74-ssec.4) In deciding whether the monitoring of the national register was reasonable, regard may be had to the nature of the item and the nature of the person’s business in relation to the item.\n(sec.74-ssec.5) For subsection&#160;(1) , it is sufficient if the mark is on the item’s labelling or packaging in compliance with the defining standard.\n(sec.74-ssec.6) Subsection&#160;(1) or (2) does not apply if— the person is a responsible supplier of the type of in-scope electrical equipment; or the item is a second-hand item.\n(sec.74-ssec.7) In this section— relevant type means a type of level 2 or 3 in-scope electrical equipment that is manufactured in, or imported into, Australia or, if New Zealand is a participating jurisdiction, New Zealand.\n- (a) the item was purchased by the person for the purpose of resale; and\n- (b) when the person purchased the item, the relevant type was not registered in relation to a registered responsible supplier.\n- (a) the person is a responsible supplier of the type of in-scope electrical equipment; or\n- (b) the item is a second-hand item.","sortOrder":90},{"sectionNumber":"sec.75","sectionType":"section","heading":"Sale of plug etc. with level 1 or 2 in-scope electrical equipment","content":"### sec.75 Sale of plug etc. with level 1 or 2 in-scope electrical equipment\n\nThis section applies if—\na relevant item of a type of level 3 in-scope electrical equipment is sold for use with an item of a type of level 1 or 2 in-scope electrical equipment; and\nat the time of sale, there is a current certificate of conformity that applies to the relevant item recorded in the national register.\nFor the purpose of the sale, the type of level 3 in-scope electrical equipment is not required to be registered.\nSubsection&#160;(2) applies despite any other provision of this part.\nIn this section—\nrelevant item means a plug, flexible supply cord or appliance connector, as defined in the defining standard.\n(sec.75-ssec.1) This section applies if— a relevant item of a type of level 3 in-scope electrical equipment is sold for use with an item of a type of level 1 or 2 in-scope electrical equipment; and at the time of sale, there is a current certificate of conformity that applies to the relevant item recorded in the national register.\n(sec.75-ssec.2) For the purpose of the sale, the type of level 3 in-scope electrical equipment is not required to be registered.\n(sec.75-ssec.3) Subsection&#160;(2) applies despite any other provision of this part.\n(sec.75-ssec.4) In this section— relevant item means a plug, flexible supply cord or appliance connector, as defined in the defining standard.\n- (a) a relevant item of a type of level 3 in-scope electrical equipment is sold for use with an item of a type of level 1 or 2 in-scope electrical equipment; and\n- (b) at the time of sale, there is a current certificate of conformity that applies to the relevant item recorded in the national register.","sortOrder":91},{"sectionNumber":"pt.4-div.4","sectionType":"division","heading":"Evidence of compliance with relevant standards","content":"## Evidence of compliance with relevant standards","sortOrder":92},{"sectionNumber":"sec.76","sectionType":"section","heading":"Responsible supplier to keep evidence","content":"### sec.76 Responsible supplier to keep evidence\n\nThis section applies to a responsible supplier of a type of level 1 in-scope electrical equipment who sells an item of the type.\nThe responsible supplier must, for the prescribed period, keep documentary evidence, in English, proving that items of the type meet the relevant standard for the type as in force—\nif the responsible supplier is a manufacturer of the type—at the time the item was manufactured by the responsible supplier; or\nif the responsible supplier is an importer of the type—at the time the item was imported by the responsible supplier.\nMaximum penalty—40 penalty units.\nIt is the responsibility of the responsible supplier to ascertain the relevant standard applying to the type under section&#160;55 .\nIt is a defence for the responsible supplier to prove that the responsible supplier obtained the item from a registered responsible supplier.\nThis example assumes New Zealand is a participating jurisdiction.\nA New Zealand responsible supplier (company A) is a registered responsible supplier. Company A imports level 1 in-scope electrical equipment into New Zealand from the United Kingdom. Company B is an Australian company that purchases the level 1 in-scope electrical equipment from company A and imports it into Australia. Company B, although a responsible supplier, is not a registered responsible supplier. Also, company B does not keep the evidence mentioned in subsection&#160;(2) for items of the type.\nIf company B were charged with an offence against subsection&#160;(2) in relation to its sale of an item of the equipment, it would be a defence for company B to prove that it obtained the item from company A who is a registered responsible supplier.\nIn this section—\nkeep , documentary evidence, means hold the evidence or be able to access it within 10 business days.\nprescribed period means 5 years starting on the day the type is last manufactured or imported by the responsible supplier.\n(sec.76-ssec.1) This section applies to a responsible supplier of a type of level 1 in-scope electrical equipment who sells an item of the type.\n(sec.76-ssec.2) The responsible supplier must, for the prescribed period, keep documentary evidence, in English, proving that items of the type meet the relevant standard for the type as in force— if the responsible supplier is a manufacturer of the type—at the time the item was manufactured by the responsible supplier; or if the responsible supplier is an importer of the type—at the time the item was imported by the responsible supplier. Maximum penalty—40 penalty units. It is the responsibility of the responsible supplier to ascertain the relevant standard applying to the type under section&#160;55 .\n(sec.76-ssec.3) It is a defence for the responsible supplier to prove that the responsible supplier obtained the item from a registered responsible supplier. This example assumes New Zealand is a participating jurisdiction. A New Zealand responsible supplier (company A) is a registered responsible supplier. Company A imports level 1 in-scope electrical equipment into New Zealand from the United Kingdom. Company B is an Australian company that purchases the level 1 in-scope electrical equipment from company A and imports it into Australia. Company B, although a responsible supplier, is not a registered responsible supplier. Also, company B does not keep the evidence mentioned in subsection&#160;(2) for items of the type. If company B were charged with an offence against subsection&#160;(2) in relation to its sale of an item of the equipment, it would be a defence for company B to prove that it obtained the item from company A who is a registered responsible supplier.\n(sec.76-ssec.4) In this section— keep , documentary evidence, means hold the evidence or be able to access it within 10 business days. prescribed period means 5 years starting on the day the type is last manufactured or imported by the responsible supplier.\n- (a) if the responsible supplier is a manufacturer of the type—at the time the item was manufactured by the responsible supplier; or\n- (b) if the responsible supplier is an importer of the type—at the time the item was imported by the responsible supplier.","sortOrder":93},{"sectionNumber":"sec.77","sectionType":"section","heading":"Registered responsible supplier must keep compliance folder","content":"### sec.77 Registered responsible supplier must keep compliance folder\n\nThis section applies to a registered responsible supplier who sells items of a type of level 2 in-scope electrical equipment registered in relation to the responsible supplier.\nThe registered responsible supplier must, for the prescribed period, keep a compliance folder proving that the type meets the relevant standard as in force when the type was registered.\nMaximum penalty—40 penalty units.\nA compliance folder is a document recording evidence in English, that must include test reports completed by an approved testing entity or a suitably qualified person, confirming that the type meets the relevant standard mentioned in subsection&#160;(2) .\nA compliance folder may be kept in electronic form.\nIn this section—\nkeep , a compliance folder, means—\nhave the folder available in the national register; or\nhold the folder or be able to access it within 10 business days.\nprescribed period means the term of the registration of the type of level 2 in-scope electrical equipment plus 5 years.\nsuitably qualified person means an individual who has—\na degree qualification in electrical engineering and at least 2 years experience in the use of electrical equipment safety standards for regulatory purposes; or\nan advanced diploma or equivalent qualification in an electrical discipline and at least 3 years experience in the use of electrical equipment safety standards for regulatory purposes; or\na trade qualification in an electrical discipline and at least 4 years experience in the use of electrical equipment safety standards for regulatory purposes.\n(sec.77-ssec.1) This section applies to a registered responsible supplier who sells items of a type of level 2 in-scope electrical equipment registered in relation to the responsible supplier.\n(sec.77-ssec.2) The registered responsible supplier must, for the prescribed period, keep a compliance folder proving that the type meets the relevant standard as in force when the type was registered. Maximum penalty—40 penalty units.\n(sec.77-ssec.3) A compliance folder is a document recording evidence in English, that must include test reports completed by an approved testing entity or a suitably qualified person, confirming that the type meets the relevant standard mentioned in subsection&#160;(2) .\n(sec.77-ssec.4) A compliance folder may be kept in electronic form.\n(sec.77-ssec.5) In this section— keep , a compliance folder, means— have the folder available in the national register; or hold the folder or be able to access it within 10 business days. prescribed period means the term of the registration of the type of level 2 in-scope electrical equipment plus 5 years. suitably qualified person means an individual who has— a degree qualification in electrical engineering and at least 2 years experience in the use of electrical equipment safety standards for regulatory purposes; or an advanced diploma or equivalent qualification in an electrical discipline and at least 3 years experience in the use of electrical equipment safety standards for regulatory purposes; or a trade qualification in an electrical discipline and at least 4 years experience in the use of electrical equipment safety standards for regulatory purposes.\n- (a) have the folder available in the national register; or\n- (b) hold the folder or be able to access it within 10 business days.\n- (a) a degree qualification in electrical engineering and at least 2 years experience in the use of electrical equipment safety standards for regulatory purposes; or\n- (b) an advanced diploma or equivalent qualification in an electrical discipline and at least 3 years experience in the use of electrical equipment safety standards for regulatory purposes; or\n- (c) a trade qualification in an electrical discipline and at least 4 years experience in the use of electrical equipment safety standards for regulatory purposes.","sortOrder":94},{"sectionNumber":"sec.78","sectionType":"section","heading":"Registered responsible supplier must keep certificate of conformity","content":"### sec.78 Registered responsible supplier must keep certificate of conformity\n\nThis section applies to a registered responsible supplier who sells a type of level 3 in-scope electrical equipment that is registered in relation to the responsible supplier.\nThe responsible supplier must keep a current certificate of conformity for the type.\nMaximum penalty—40 penalty units.\nIn this section—\nkeep , a current certificate of conformity, means hold the certificate or be able to access it within 10 business days.\n(sec.78-ssec.1) This section applies to a registered responsible supplier who sells a type of level 3 in-scope electrical equipment that is registered in relation to the responsible supplier.\n(sec.78-ssec.2) The responsible supplier must keep a current certificate of conformity for the type. Maximum penalty—40 penalty units.\n(sec.78-ssec.3) In this section— keep , a current certificate of conformity, means hold the certificate or be able to access it within 10 business days.","sortOrder":95},{"sectionNumber":"pt.4-div.5","sectionType":"division","heading":"Effect of reclassification of in-scope electrical equipment","content":"## Effect of reclassification of in-scope electrical equipment","sortOrder":96},{"sectionNumber":"sec.79","sectionType":"section","heading":"Effect of reclassification","content":"### sec.79 Effect of reclassification\n\nThis section applies if—\na type of level 1 or 2 in-scope electrical equipment is reclassified to a higher level; and\nimmediately before the reclassification happens, a responsible supplier of that type was selling items of the type.\nFor the period of 1 year starting on the day the reclassification has effect, divisions&#160;3 and 4 apply to the sale by the responsible supplier of items of that type as if the reclassification had not happened.\nIn this section—\nreclassified to a higher level —\nfor a type of level 1 in-scope electrical equipment, means that type is classified by the defining standard as level 2 or 3; or\nfor a type of level 2 in-scope electrical equipment, means that type is reclassified by the defining standard from level 2 to level 3.\n(sec.79-ssec.1) This section applies if— a type of level 1 or 2 in-scope electrical equipment is reclassified to a higher level; and immediately before the reclassification happens, a responsible supplier of that type was selling items of the type.\n(sec.79-ssec.2) For the period of 1 year starting on the day the reclassification has effect, divisions&#160;3 and 4 apply to the sale by the responsible supplier of items of that type as if the reclassification had not happened.\n(sec.79-ssec.3) In this section— reclassified to a higher level — for a type of level 1 in-scope electrical equipment, means that type is classified by the defining standard as level 2 or 3; or for a type of level 2 in-scope electrical equipment, means that type is reclassified by the defining standard from level 2 to level 3.\n- (a) a type of level 1 or 2 in-scope electrical equipment is reclassified to a higher level; and\n- (b) immediately before the reclassification happens, a responsible supplier of that type was selling items of the type.\n- (a) for a type of level 1 in-scope electrical equipment, means that type is classified by the defining standard as level 2 or 3; or\n- (b) for a type of level 2 in-scope electrical equipment, means that type is reclassified by the defining standard from level 2 to level 3.","sortOrder":97},{"sectionNumber":"pt.4-div.6","sectionType":"division","heading":"Marking of in-scope electrical equipment","content":"## Marking of in-scope electrical equipment","sortOrder":98},{"sectionNumber":"sec.80","sectionType":"section","heading":"Responsible supplier must not sell unmarked item of in-scope electrical equipment","content":"### sec.80 Responsible supplier must not sell unmarked item of in-scope electrical equipment\n\nA responsible supplier of a type of level 1, 2 or 3 in-scope electrical equipment must not sell an item of the type unless the item is marked with the RCM in compliance with the defining standard.\nMaximum penalty—40 penalty units.\nFor subsection&#160;(1) , it is sufficient if the mark is on the item’s labelling or packaging in compliance with the defining standard.\n(sec.80-ssec.1) A responsible supplier of a type of level 1, 2 or 3 in-scope electrical equipment must not sell an item of the type unless the item is marked with the RCM in compliance with the defining standard. Maximum penalty—40 penalty units.\n(sec.80-ssec.2) For subsection&#160;(1) , it is sufficient if the mark is on the item’s labelling or packaging in compliance with the defining standard.","sortOrder":99},{"sectionNumber":"sec.81","sectionType":"section","heading":"Person must not mark in-scope electrical equipment that does not meet relevant standard","content":"### sec.81 Person must not mark in-scope electrical equipment that does not meet relevant standard\n\nA person must not mark an item of a type of level 1, 2 or 3 in-scope electrical equipment with the RCM unless the item meets the relevant standard for the type.\nMaximum penalty—40 penalty units.\nIn this section—\nmark , an item of a type of level 1, 2 or 3 in-scope electrical equipment, includes mark the item’s labelling or packaging.\n(sec.81-ssec.1) A person must not mark an item of a type of level 1, 2 or 3 in-scope electrical equipment with the RCM unless the item meets the relevant standard for the type. Maximum penalty—40 penalty units.\n(sec.81-ssec.2) In this section— mark , an item of a type of level 1, 2 or 3 in-scope electrical equipment, includes mark the item’s labelling or packaging.","sortOrder":100},{"sectionNumber":"sec.82","sectionType":"section","heading":"Mark for use in exceptional circumstances","content":"### sec.82 Mark for use in exceptional circumstances\n\nThe regulator may approve a mark, other than the RCM, for use in exceptional circumstances.\nA person does not commit an offence under section&#160;74 (1) or 80 (1) in relation to the sale of an item of a type of in-scope electrical equipment if the item is marked as required by the approval given under subsection&#160;(1) .\nAlso, a person does not commit an offence under section&#160;74 (1) or 80 (1) in relation to the sale of an item of a type of in-scope electrical equipment if—\nthe item is marked with a mark, other than the RCM, approved under a corresponding law for use in exceptional circumstances; and\nthe item is marked as required by that approval.\n(sec.82-ssec.1) The regulator may approve a mark, other than the RCM, for use in exceptional circumstances.\n(sec.82-ssec.2) A person does not commit an offence under section&#160;74 (1) or 80 (1) in relation to the sale of an item of a type of in-scope electrical equipment if the item is marked as required by the approval given under subsection&#160;(1) .\n(sec.82-ssec.3) Also, a person does not commit an offence under section&#160;74 (1) or 80 (1) in relation to the sale of an item of a type of in-scope electrical equipment if— the item is marked with a mark, other than the RCM, approved under a corresponding law for use in exceptional circumstances; and the item is marked as required by that approval.\n- (a) the item is marked with a mark, other than the RCM, approved under a corresponding law for use in exceptional circumstances; and\n- (b) the item is marked as required by that approval.","sortOrder":101},{"sectionNumber":"pt.4-div.7","sectionType":"division","heading":"Certificates of conformity issued by regulator","content":"## Certificates of conformity issued by regulator","sortOrder":102},{"sectionNumber":"sec.83","sectionType":"section","heading":"Application for certificate of conformity","content":"### sec.83 Application for certificate of conformity\n\nA person may apply to the regulator for a certificate of conformity for a type of level 3 in-scope electrical equipment.\nThe application must be—\nin the approved form; and\naccompanied by—\na test report from an approved testing entity; and\nan item of the type or colour images showing the internal and external construction of an item of the type; and\ntechnical documentation which adequately describes the type; and\naccompanied by the fee for the application.\nThe regulator may require the applicant to provide—\nan item of the type if colour images provided are not adequate; or\nadditional information about the type.\nThe regulator may exempt the applicant from the requirement to provide any of the items referred to in subsection&#160;(2) (b) if—\nthe regulator has previously issued a certificate of conformity to another person in relation to the type; or\nin the circumstances the regulator is of the reasonable opinion that it is not necessary for any of those items to be provided.\n(sec.83-ssec.1) A person may apply to the regulator for a certificate of conformity for a type of level 3 in-scope electrical equipment.\n(sec.83-ssec.2) The application must be— in the approved form; and accompanied by— a test report from an approved testing entity; and an item of the type or colour images showing the internal and external construction of an item of the type; and technical documentation which adequately describes the type; and accompanied by the fee for the application.\n(sec.83-ssec.3) The regulator may require the applicant to provide— an item of the type if colour images provided are not adequate; or additional information about the type.\n(sec.83-ssec.4) The regulator may exempt the applicant from the requirement to provide any of the items referred to in subsection&#160;(2) (b) if— the regulator has previously issued a certificate of conformity to another person in relation to the type; or in the circumstances the regulator is of the reasonable opinion that it is not necessary for any of those items to be provided.\n- (a) in the approved form; and\n- (b) accompanied by— (i) a test report from an approved testing entity; and (ii) an item of the type or colour images showing the internal and external construction of an item of the type; and (iii) technical documentation which adequately describes the type; and\n- (i) a test report from an approved testing entity; and\n- (ii) an item of the type or colour images showing the internal and external construction of an item of the type; and\n- (iii) technical documentation which adequately describes the type; and\n- (c) accompanied by the fee for the application.\n- (i) a test report from an approved testing entity; and\n- (ii) an item of the type or colour images showing the internal and external construction of an item of the type; and\n- (iii) technical documentation which adequately describes the type; and\n- (a) an item of the type if colour images provided are not adequate; or\n- (b) additional information about the type.\n- (a) the regulator has previously issued a certificate of conformity to another person in relation to the type; or\n- (b) in the circumstances the regulator is of the reasonable opinion that it is not necessary for any of those items to be provided.","sortOrder":103},{"sectionNumber":"sec.84","sectionType":"section","heading":"Regulator may issue certificate of conformity","content":"### sec.84 Regulator may issue certificate of conformity\n\nIf the regulator approves the application, the regulator may issue a certificate of conformity for the type of level 3 in-scope electrical equipment.\nIf the regulator refuses to approve the application, the regulator must give the applicant an information notice for the decision to refuse.\n(sec.84-ssec.1) If the regulator approves the application, the regulator may issue a certificate of conformity for the type of level 3 in-scope electrical equipment.\n(sec.84-ssec.2) If the regulator refuses to approve the application, the regulator must give the applicant an information notice for the decision to refuse.","sortOrder":104},{"sectionNumber":"sec.85","sectionType":"section","heading":"Term of certificate","content":"### sec.85 Term of certificate\n\nA certificate of conformity issued under this division remains in force for the period stated in the certificate, that is not more than 5 years, unless it is sooner cancelled.","sortOrder":105},{"sectionNumber":"sec.86","sectionType":"section","heading":"Modification of certificate of conformity—change of name or model","content":"### sec.86 Modification of certificate of conformity—change of name or model\n\nThis section applies if the holder of a certificate of conformity for a type of level 3 in-scope electrical equipment issued under this division proposes to vary the brand name or model designation that is specified on the certificate for the type.\nThe holder may apply to the regulator for modification of the certificate.\nThe application must be—\nin the approved form; and\naccompanied by the fee for the application.\nThe regulator may require the applicant to provide—\nan item of the type or colour images showing the internal and external construction of an item of the type; or\ndocumentation that adequately describes the proposed variation.\nThe regulator may modify a certificate of conformity and issue a modified certificate if satisfied the variation does not affect the compliance of the type with the relevant standard to which the type was tested.\nIf the regulator refuses to modify the certificate, the regulator must give the applicant an information notice for the decision to refuse.\n(sec.86-ssec.1) This section applies if the holder of a certificate of conformity for a type of level 3 in-scope electrical equipment issued under this division proposes to vary the brand name or model designation that is specified on the certificate for the type.\n(sec.86-ssec.2) The holder may apply to the regulator for modification of the certificate.\n(sec.86-ssec.3) The application must be— in the approved form; and accompanied by the fee for the application.\n(sec.86-ssec.4) The regulator may require the applicant to provide— an item of the type or colour images showing the internal and external construction of an item of the type; or documentation that adequately describes the proposed variation.\n(sec.86-ssec.5) The regulator may modify a certificate of conformity and issue a modified certificate if satisfied the variation does not affect the compliance of the type with the relevant standard to which the type was tested.\n(sec.86-ssec.6) If the regulator refuses to modify the certificate, the regulator must give the applicant an information notice for the decision to refuse.\n- (a) in the approved form; and\n- (b) accompanied by the fee for the application.\n- (a) an item of the type or colour images showing the internal and external construction of an item of the type; or\n- (b) documentation that adequately describes the proposed variation.","sortOrder":106},{"sectionNumber":"sec.87","sectionType":"section","heading":"Modification of certificate of conformity—other than a change of name or model","content":"### sec.87 Modification of certificate of conformity—other than a change of name or model\n\nThis section applies if the holder of a certificate of conformity for a type of level 3 in-scope electrical equipment issued under this division proposes to make any modification to the equipment, other than a modification described in section&#160;86 , that would not result in the creation of a new type of equipment.\nThe holder may apply to the regulator for the modification of the certificate.\nThe application must be—\nin the approved form; and\naccompanied by—\na test report relating to the modified in-scope electrical equipment from an approved testing entity; and\nan item of the type or colour images showing the internal and external construction of an item of the type; and\ntechnical documentation that adequately describes the modified in-scope electrical equipment; and\naccompanied by the fee for the application.\nThe regulator may require the applicant to provide—\nan item of the type if colour images provided are not adequate; or\nadditional information about the modified electrical equipment.\nThe regulator may exempt the applicant from the requirement to provide a test report under subsection&#160;(3) (b) (i) if the regulator is satisfied the modification will not affect the safety of the type.\nThe regulator may waive or rebate the payment of the fee for the modification of the certificate if the regulator, under subsection&#160;(5) , exempts the applicant from the requirement to provide a test report.\nThe regulator may modify a certificate of conformity and issue a modified certificate if satisfied the modification to the type would not result in the creation of a new type of in-scope electrical equipment.\nIf the regulator refuses to modify the certificate, the regulator must give the applicant an information notice for the decision to refuse.\n(sec.87-ssec.1) This section applies if the holder of a certificate of conformity for a type of level 3 in-scope electrical equipment issued under this division proposes to make any modification to the equipment, other than a modification described in section&#160;86 , that would not result in the creation of a new type of equipment.\n(sec.87-ssec.2) The holder may apply to the regulator for the modification of the certificate.\n(sec.87-ssec.3) The application must be— in the approved form; and accompanied by— a test report relating to the modified in-scope electrical equipment from an approved testing entity; and an item of the type or colour images showing the internal and external construction of an item of the type; and technical documentation that adequately describes the modified in-scope electrical equipment; and accompanied by the fee for the application.\n(sec.87-ssec.4) The regulator may require the applicant to provide— an item of the type if colour images provided are not adequate; or additional information about the modified electrical equipment.\n(sec.87-ssec.5) The regulator may exempt the applicant from the requirement to provide a test report under subsection&#160;(3) (b) (i) if the regulator is satisfied the modification will not affect the safety of the type.\n(sec.87-ssec.6) The regulator may waive or rebate the payment of the fee for the modification of the certificate if the regulator, under subsection&#160;(5) , exempts the applicant from the requirement to provide a test report.\n(sec.87-ssec.7) The regulator may modify a certificate of conformity and issue a modified certificate if satisfied the modification to the type would not result in the creation of a new type of in-scope electrical equipment.\n(sec.87-ssec.8) If the regulator refuses to modify the certificate, the regulator must give the applicant an information notice for the decision to refuse.\n- (a) in the approved form; and\n- (b) accompanied by— (i) a test report relating to the modified in-scope electrical equipment from an approved testing entity; and (ii) an item of the type or colour images showing the internal and external construction of an item of the type; and (iii) technical documentation that adequately describes the modified in-scope electrical equipment; and\n- (i) a test report relating to the modified in-scope electrical equipment from an approved testing entity; and\n- (ii) an item of the type or colour images showing the internal and external construction of an item of the type; and\n- (iii) technical documentation that adequately describes the modified in-scope electrical equipment; and\n- (c) accompanied by the fee for the application.\n- (i) a test report relating to the modified in-scope electrical equipment from an approved testing entity; and\n- (ii) an item of the type or colour images showing the internal and external construction of an item of the type; and\n- (iii) technical documentation that adequately describes the modified in-scope electrical equipment; and\n- (a) an item of the type if colour images provided are not adequate; or\n- (b) additional information about the modified electrical equipment.","sortOrder":107},{"sectionNumber":"sec.88","sectionType":"section","heading":"Renewal of certificate of conformity","content":"### sec.88 Renewal of certificate of conformity\n\nA person who holds a certificate of conformity issued under this division may apply to the regulator for renewal of the certificate and the issue of a new certificate.\nThe application must be—\nin the approved form; and\naccompanied by a declaration by the applicant, or a person authorised by the applicant, stating whether or not—\nthe type of level 3 in-scope electrical equipment to which the current certificate relates has been modified since the certificate was issued or modified; and\nthe relevant standard to which the type was tested has changed since the current certificate was issued or modified; and\naccompanied by the fee for the application.\nThe regulator may renew the certificate and issue a new certificate of conformity if satisfied—\nthe type of level 3 in-scope electrical equipment has not been modified; and\nthe relevant standard to which that type was tested has not changed since the current certificate was issued or the certificate relating to that type was modified.\nIf the regulator refuses to renew the certificate, the regulator must give the applicant an information notice for the decision to refuse.\n(sec.88-ssec.1) A person who holds a certificate of conformity issued under this division may apply to the regulator for renewal of the certificate and the issue of a new certificate.\n(sec.88-ssec.2) The application must be— in the approved form; and accompanied by a declaration by the applicant, or a person authorised by the applicant, stating whether or not— the type of level 3 in-scope electrical equipment to which the current certificate relates has been modified since the certificate was issued or modified; and the relevant standard to which the type was tested has changed since the current certificate was issued or modified; and accompanied by the fee for the application.\n(sec.88-ssec.3) The regulator may renew the certificate and issue a new certificate of conformity if satisfied— the type of level 3 in-scope electrical equipment has not been modified; and the relevant standard to which that type was tested has not changed since the current certificate was issued or the certificate relating to that type was modified.\n(sec.88-ssec.4) If the regulator refuses to renew the certificate, the regulator must give the applicant an information notice for the decision to refuse.\n- (a) in the approved form; and\n- (b) accompanied by a declaration by the applicant, or a person authorised by the applicant, stating whether or not— (i) the type of level 3 in-scope electrical equipment to which the current certificate relates has been modified since the certificate was issued or modified; and (ii) the relevant standard to which the type was tested has changed since the current certificate was issued or modified; and\n- (i) the type of level 3 in-scope electrical equipment to which the current certificate relates has been modified since the certificate was issued or modified; and\n- (ii) the relevant standard to which the type was tested has changed since the current certificate was issued or modified; and\n- (c) accompanied by the fee for the application.\n- (i) the type of level 3 in-scope electrical equipment to which the current certificate relates has been modified since the certificate was issued or modified; and\n- (ii) the relevant standard to which the type was tested has changed since the current certificate was issued or modified; and\n- (a) the type of level 3 in-scope electrical equipment has not been modified; and\n- (b) the relevant standard to which that type was tested has not changed since the current certificate was issued or the certificate relating to that type was modified.","sortOrder":108},{"sectionNumber":"sec.89","sectionType":"section","heading":"Transfer of certificate","content":"### sec.89 Transfer of certificate\n\nThe holder of a certificate of conformity issued under this division who proposes to transfer the certificate to another person may apply to the regulator to have the certificate amended to refer to the name of the person to whom the certificate is to be transferred (the transferee ).\nThe application must be—\nin the approved form; and\naccompanied by—\nthe certificate to be transferred; and\na statement, signed by the transferee, that the transferee consents to the transfer; and\nthe fee for the application.\nThe regulator may issue a certificate of conformity to the transferee if the holder complies with the requirements under subsection&#160;(2) .\nIf the regulator refuses to grant the application, the regulator must give the applicant an information notice for the decision to refuse.\n(sec.89-ssec.1) The holder of a certificate of conformity issued under this division who proposes to transfer the certificate to another person may apply to the regulator to have the certificate amended to refer to the name of the person to whom the certificate is to be transferred (the transferee ).\n(sec.89-ssec.2) The application must be— in the approved form; and accompanied by— the certificate to be transferred; and a statement, signed by the transferee, that the transferee consents to the transfer; and the fee for the application.\n(sec.89-ssec.3) The regulator may issue a certificate of conformity to the transferee if the holder complies with the requirements under subsection&#160;(2) .\n(sec.89-ssec.4) If the regulator refuses to grant the application, the regulator must give the applicant an information notice for the decision to refuse.\n- (a) in the approved form; and\n- (b) accompanied by— (i) the certificate to be transferred; and (ii) a statement, signed by the transferee, that the transferee consents to the transfer; and (iii) the fee for the application.\n- (i) the certificate to be transferred; and\n- (ii) a statement, signed by the transferee, that the transferee consents to the transfer; and\n- (iii) the fee for the application.\n- (i) the certificate to be transferred; and\n- (ii) a statement, signed by the transferee, that the transferee consents to the transfer; and\n- (iii) the fee for the application.","sortOrder":109},{"sectionNumber":"sec.90","sectionType":"section","heading":"Grounds for cancelling certificate of conformity","content":"### sec.90 Grounds for cancelling certificate of conformity\n\nEach of the following is a ground for cancelling a certificate of conformity for a type of level 3 in-scope electrical equipment issued under this division—\nan item of the type does not meet the relevant standard for the type;\nan item of the type is, or is likely to be or to become, dangerous in normal use;\nthe certificate was obtained by misleading information;\nan item of the type, or purportedly of the type, is found, on examination by the regulator, to be substantially different from the type as described in—\nthe certificate; or\na test report forming the basis for the issuing of the certificate;\nthe holder of the certificate contravenes the Act or this regulation.\n- (a) an item of the type does not meet the relevant standard for the type;\n- (b) an item of the type is, or is likely to be or to become, dangerous in normal use;\n- (c) the certificate was obtained by misleading information;\n- (d) an item of the type, or purportedly of the type, is found, on examination by the regulator, to be substantially different from the type as described in— (i) the certificate; or (ii) a test report forming the basis for the issuing of the certificate;\n- (i) the certificate; or\n- (ii) a test report forming the basis for the issuing of the certificate;\n- (e) the holder of the certificate contravenes the Act or this regulation.\n- (i) the certificate; or\n- (ii) a test report forming the basis for the issuing of the certificate;","sortOrder":110},{"sectionNumber":"sec.91","sectionType":"section","heading":"Procedure before cancellation","content":"### sec.91 Procedure before cancellation\n\nIf the regulator considers a ground exists under section&#160;90 to cancel the certificate of conformity for a type of level 3 in-scope electrical equipment, the regulator must, before taking the action, give the holder of the certificate written notice—\nstating that the regulator is considering cancelling the certificate; and\nstating each ground for the proposed cancellation; and\noutlining the facts and circumstances forming the basis for each ground; and\ninviting the holder to show, within a stated period of at least 28 days, why the certificate should not be cancelled.\nIf, after considering all written representations made by the holder of the certificate within the stated time, the regulator still considers a ground exists to cancel the certificate, the regulator may cancel the certificate.\nIf the regulator cancels the certificate, the regulator must—\ngive the holder of the certificate an information notice for the decision to cancel; and\nnotify the cancellation by gazette notice stating the day of cancellation.\n(sec.91-ssec.1) If the regulator considers a ground exists under section&#160;90 to cancel the certificate of conformity for a type of level 3 in-scope electrical equipment, the regulator must, before taking the action, give the holder of the certificate written notice— stating that the regulator is considering cancelling the certificate; and stating each ground for the proposed cancellation; and outlining the facts and circumstances forming the basis for each ground; and inviting the holder to show, within a stated period of at least 28 days, why the certificate should not be cancelled.\n(sec.91-ssec.2) If, after considering all written representations made by the holder of the certificate within the stated time, the regulator still considers a ground exists to cancel the certificate, the regulator may cancel the certificate.\n(sec.91-ssec.3) If the regulator cancels the certificate, the regulator must— give the holder of the certificate an information notice for the decision to cancel; and notify the cancellation by gazette notice stating the day of cancellation.\n- (a) stating that the regulator is considering cancelling the certificate; and\n- (b) stating each ground for the proposed cancellation; and\n- (c) outlining the facts and circumstances forming the basis for each ground; and\n- (d) inviting the holder to show, within a stated period of at least 28 days, why the certificate should not be cancelled.\n- (a) give the holder of the certificate an information notice for the decision to cancel; and\n- (b) notify the cancellation by gazette notice stating the day of cancellation.","sortOrder":111},{"sectionNumber":"sec.92","sectionType":"section","heading":"Cancellation at certificate holder’s request","content":"### sec.92 Cancellation at certificate holder’s request\n\nThe regulator must cancel a certificate of conformity for a type of level 3 in-scope electrical equipment issued under this division if the holder of the certificate asks the regulator to cancel it.","sortOrder":112},{"sectionNumber":"sec.93","sectionType":"section","heading":"Certificate of conformity holder to return certificate if cancelled","content":"### sec.93 Certificate of conformity holder to return certificate if cancelled\n\nWithin 14 days after receiving notice of cancellation of a certificate of conformity, the holder of the certificate must give the regulator the certificate of conformity unless the holder has a reasonable excuse.\nMaximum penalty—10 penalty units.","sortOrder":113},{"sectionNumber":"sec.94","sectionType":"section","heading":"Information to be recorded in national register","content":"### sec.94 Information to be recorded in national register\n\nThe regulator must ensure that, for each certificate of conformity issued under this division, or for each modification, renewal or transfer of a certificate of conformity under this division, the information required by the equipment safety rules is recorded in the national register.\nThe regulator must also ensure particulars of the cancellation of a certificate of conformity under this division are recorded in the national register.\n(sec.94-ssec.1) The regulator must ensure that, for each certificate of conformity issued under this division, or for each modification, renewal or transfer of a certificate of conformity under this division, the information required by the equipment safety rules is recorded in the national register.\n(sec.94-ssec.2) The regulator must also ensure particulars of the cancellation of a certificate of conformity under this division are recorded in the national register.","sortOrder":114},{"sectionNumber":"pt.4-div.8","sectionType":"division","heading":"Recognised external certification schemes— Act , section&#160;48J","content":"## Recognised external certification schemes— Act , section&#160;48J","sortOrder":115},{"sectionNumber":"sec.95","sectionType":"section","heading":"Definitions for division","content":"### sec.95 Definitions for division\n\nIn this division—\ndeclaration holder means the person who conducts a declared scheme.\ndeclared scheme see section&#160;96 (1) .","sortOrder":116},{"sectionNumber":"sec.96","sectionType":"section","heading":"Application for regulator’s declaration of scheme","content":"### sec.96 Application for regulator’s declaration of scheme\n\nA person who conducts a scheme for the certification of types of in-scope electrical equipment may apply to the regulator for the scheme to be declared a recognised external certification scheme under section&#160;48J of the Act (a declared scheme ).\nThe application must be—\nin the approved form; and\naccompanied by—\nthe fee for the application; and\nevidence that the applicant is—\naccredited by the Joint Accreditation System of Australia and New Zealand as competent to certify that types of level 1, 2 or 3 in-scope electrical equipment meet relevant standards; or\nappropriately designated, under a mutual recognition arrangement or a free trade agreement to which Australia is a party, as competent to certify that types of level 1, 2 or 3 in-scope electrical equipment meet relevant standards; and\nthe applicant’s written agreement that—\nwhen certifying types of level 1, 2 or 3 in-scope electrical equipment, the applicant will do so under the equipment safety rules; and\nthe applicant will issue a certificate of conformity or certificate of suitability for types of level 1, 2 or 3 in-scope electrical equipment that meet relevant standards; and\nthe other documents and information required by the regulator.\n(sec.96-ssec.1) A person who conducts a scheme for the certification of types of in-scope electrical equipment may apply to the regulator for the scheme to be declared a recognised external certification scheme under section&#160;48J of the Act (a declared scheme ).\n(sec.96-ssec.2) The application must be— in the approved form; and accompanied by— the fee for the application; and evidence that the applicant is— accredited by the Joint Accreditation System of Australia and New Zealand as competent to certify that types of level 1, 2 or 3 in-scope electrical equipment meet relevant standards; or appropriately designated, under a mutual recognition arrangement or a free trade agreement to which Australia is a party, as competent to certify that types of level 1, 2 or 3 in-scope electrical equipment meet relevant standards; and the applicant’s written agreement that— when certifying types of level 1, 2 or 3 in-scope electrical equipment, the applicant will do so under the equipment safety rules; and the applicant will issue a certificate of conformity or certificate of suitability for types of level 1, 2 or 3 in-scope electrical equipment that meet relevant standards; and the other documents and information required by the regulator.\n- (a) in the approved form; and\n- (b) accompanied by— (i) the fee for the application; and (ii) evidence that the applicant is— (A) accredited by the Joint Accreditation System of Australia and New Zealand as competent to certify that types of level 1, 2 or 3 in-scope electrical equipment meet relevant standards; or (B) appropriately designated, under a mutual recognition arrangement or a free trade agreement to which Australia is a party, as competent to certify that types of level 1, 2 or 3 in-scope electrical equipment meet relevant standards; and (iii) the applicant’s written agreement that— (A) when certifying types of level 1, 2 or 3 in-scope electrical equipment, the applicant will do so under the equipment safety rules; and (B) the applicant will issue a certificate of conformity or certificate of suitability for types of level 1, 2 or 3 in-scope electrical equipment that meet relevant standards; and (iv) the other documents and information required by the regulator.\n- (i) the fee for the application; and\n- (ii) evidence that the applicant is— (A) accredited by the Joint Accreditation System of Australia and New Zealand as competent to certify that types of level 1, 2 or 3 in-scope electrical equipment meet relevant standards; or (B) appropriately designated, under a mutual recognition arrangement or a free trade agreement to which Australia is a party, as competent to certify that types of level 1, 2 or 3 in-scope electrical equipment meet relevant standards; and\n- (A) accredited by the Joint Accreditation System of Australia and New Zealand as competent to certify that types of level 1, 2 or 3 in-scope electrical equipment meet relevant standards; or\n- (B) appropriately designated, under a mutual recognition arrangement or a free trade agreement to which Australia is a party, as competent to certify that types of level 1, 2 or 3 in-scope electrical equipment meet relevant standards; and\n- (iii) the applicant’s written agreement that— (A) when certifying types of level 1, 2 or 3 in-scope electrical equipment, the applicant will do so under the equipment safety rules; and (B) the applicant will issue a certificate of conformity or certificate of suitability for types of level 1, 2 or 3 in-scope electrical equipment that meet relevant standards; and\n- (A) when certifying types of level 1, 2 or 3 in-scope electrical equipment, the applicant will do so under the equipment safety rules; and\n- (B) the applicant will issue a certificate of conformity or certificate of suitability for types of level 1, 2 or 3 in-scope electrical equipment that meet relevant standards; and\n- (iv) the other documents and information required by the regulator.\n- (i) the fee for the application; and\n- (ii) evidence that the applicant is— (A) accredited by the Joint Accreditation System of Australia and New Zealand as competent to certify that types of level 1, 2 or 3 in-scope electrical equipment meet relevant standards; or (B) appropriately designated, under a mutual recognition arrangement or a free trade agreement to which Australia is a party, as competent to certify that types of level 1, 2 or 3 in-scope electrical equipment meet relevant standards; and\n- (A) accredited by the Joint Accreditation System of Australia and New Zealand as competent to certify that types of level 1, 2 or 3 in-scope electrical equipment meet relevant standards; or\n- (B) appropriately designated, under a mutual recognition arrangement or a free trade agreement to which Australia is a party, as competent to certify that types of level 1, 2 or 3 in-scope electrical equipment meet relevant standards; and\n- (iii) the applicant’s written agreement that— (A) when certifying types of level 1, 2 or 3 in-scope electrical equipment, the applicant will do so under the equipment safety rules; and (B) the applicant will issue a certificate of conformity or certificate of suitability for types of level 1, 2 or 3 in-scope electrical equipment that meet relevant standards; and\n- (A) when certifying types of level 1, 2 or 3 in-scope electrical equipment, the applicant will do so under the equipment safety rules; and\n- (B) the applicant will issue a certificate of conformity or certificate of suitability for types of level 1, 2 or 3 in-scope electrical equipment that meet relevant standards; and\n- (iv) the other documents and information required by the regulator.\n- (A) accredited by the Joint Accreditation System of Australia and New Zealand as competent to certify that types of level 1, 2 or 3 in-scope electrical equipment meet relevant standards; or\n- (B) appropriately designated, under a mutual recognition arrangement or a free trade agreement to which Australia is a party, as competent to certify that types of level 1, 2 or 3 in-scope electrical equipment meet relevant standards; and\n- (A) when certifying types of level 1, 2 or 3 in-scope electrical equipment, the applicant will do so under the equipment safety rules; and\n- (B) the applicant will issue a certificate of conformity or certificate of suitability for types of level 1, 2 or 3 in-scope electrical equipment that meet relevant standards; and","sortOrder":117},{"sectionNumber":"sec.97","sectionType":"section","heading":"Notice of proposed declaration","content":"### sec.97 Notice of proposed declaration\n\nThis section applies if the regulator is intending to grant the application.\nBefore deciding the application, the regulator—\nmust publish a notice of the proposed declaration on the department’s website; and\nmay publish the notice in another way the regulator considers is likely to come to the attention of a person who may be interested in making a submission about the proposed declaration.\nThe notice must state the regulator’s intention to declare the scheme to be a recognised external certification scheme.\nThe notice must state a period of at least 14 days during which written submissions may be made to the regulator about the proposed declaration.\nDuring the period stated in subsection&#160;(4) , a person may make a written submission to the regulator about the proposed declaration.\nThe regulator must consider all written submissions received under subsection&#160;(5) .\n(sec.97-ssec.1) This section applies if the regulator is intending to grant the application.\n(sec.97-ssec.2) Before deciding the application, the regulator— must publish a notice of the proposed declaration on the department’s website; and may publish the notice in another way the regulator considers is likely to come to the attention of a person who may be interested in making a submission about the proposed declaration.\n(sec.97-ssec.3) The notice must state the regulator’s intention to declare the scheme to be a recognised external certification scheme.\n(sec.97-ssec.4) The notice must state a period of at least 14 days during which written submissions may be made to the regulator about the proposed declaration.\n(sec.97-ssec.5) During the period stated in subsection&#160;(4) , a person may make a written submission to the regulator about the proposed declaration.\n(sec.97-ssec.6) The regulator must consider all written submissions received under subsection&#160;(5) .\n- (a) must publish a notice of the proposed declaration on the department’s website; and\n- (b) may publish the notice in another way the regulator considers is likely to come to the attention of a person who may be interested in making a submission about the proposed declaration.","sortOrder":118},{"sectionNumber":"sec.98","sectionType":"section","heading":"Decision about application","content":"### sec.98 Decision about application\n\nThe regulator may decide to grant or refuse to grant the application.\nIf the regulator grants the application, the regulator must, under section&#160;48J of the Act , declare the scheme to be a recognised external certification scheme.\nIf the regulator refuses to grant the application, or grants the application and imposes conditions on the declared scheme, the regulator must give the applicant an information notice for the decision to refuse or to impose conditions.\n(sec.98-ssec.1) The regulator may decide to grant or refuse to grant the application. If the regulator grants the application, the regulator must, under section&#160;48J of the Act , declare the scheme to be a recognised external certification scheme.\n(sec.98-ssec.2) If the regulator refuses to grant the application, or grants the application and imposes conditions on the declared scheme, the regulator must give the applicant an information notice for the decision to refuse or to impose conditions.","sortOrder":119},{"sectionNumber":"sec.99","sectionType":"section","heading":"Term of declared scheme","content":"### sec.99 Term of declared scheme\n\nThe term of a declared scheme is the period of not more than 5 years stated in the regulator’s declaration of the scheme.","sortOrder":120},{"sectionNumber":"sec.100","sectionType":"section","heading":"Regulator may impose conditions on declared scheme","content":"### sec.100 Regulator may impose conditions on declared scheme\n\nThe regulator may impose conditions on a declared scheme.\nWithout limiting subsection&#160;(1) , a condition may restrict the types of in-scope electrical equipment that may be certified under the scheme.\nConditions applying to a declared scheme under this section when the scheme is declared under section&#160;48J of the Act must be stated in the declaration.\n(sec.100-ssec.1) The regulator may impose conditions on a declared scheme.\n(sec.100-ssec.2) Without limiting subsection&#160;(1) , a condition may restrict the types of in-scope electrical equipment that may be certified under the scheme.\n(sec.100-ssec.3) Conditions applying to a declared scheme under this section when the scheme is declared under section&#160;48J of the Act must be stated in the declaration.","sortOrder":121},{"sectionNumber":"sec.101","sectionType":"section","heading":"Condition imposed by regulation","content":"### sec.101 Condition imposed by regulation\n\nIt is a condition of each declared scheme that the declaration holder must—\npay the annual fee for the declaration by each anniversary of the scheme’s declaration; and\nfor each certificate of conformity or certificate of suitability issued by the declaration holder, or for each modification, renewal or transfer of the issued certificate that is approved by the declaration holder—record the information required by the equipment safety rules in the national register within 3 business days after issuing the certificate or granting the approval; and\nfor each certificate of conformity or certificate of suitability cancelled by the declaration holder—record information about the cancellation in the national register within 3 business days after cancelling the certificate.\n- (a) pay the annual fee for the declaration by each anniversary of the scheme’s declaration; and\n- (b) for each certificate of conformity or certificate of suitability issued by the declaration holder, or for each modification, renewal or transfer of the issued certificate that is approved by the declaration holder—record the information required by the equipment safety rules in the national register within 3 business days after issuing the certificate or granting the approval; and\n- (c) for each certificate of conformity or certificate of suitability cancelled by the declaration holder—record information about the cancellation in the national register within 3 business days after cancelling the certificate.","sortOrder":122},{"sectionNumber":"sec.102","sectionType":"section","heading":"Amendment of conditions imposed by regulator","content":"### sec.102 Amendment of conditions imposed by regulator\n\nThe regulator may amend the conditions imposed on a declared scheme by the regulator by revoking or varying the conditions or imposing new conditions.\nThe regulator may act under subsection&#160;(1) on the regulator’s own initiative or at the request of the declaration holder.\nThe revocation of conditions, or the amendment of conditions at the request of the declaration holder, has effect when written notice of the amendment is given to the declaration holder.\nIf the regulator refuses to amend the conditions as requested by the declaration holder, the regulator must give the declaration holder an information notice for the decision to refuse.\n(sec.102-ssec.1) The regulator may amend the conditions imposed on a declared scheme by the regulator by revoking or varying the conditions or imposing new conditions.\n(sec.102-ssec.2) The regulator may act under subsection&#160;(1) on the regulator’s own initiative or at the request of the declaration holder.\n(sec.102-ssec.3) The revocation of conditions, or the amendment of conditions at the request of the declaration holder, has effect when written notice of the amendment is given to the declaration holder.\n(sec.102-ssec.4) If the regulator refuses to amend the conditions as requested by the declaration holder, the regulator must give the declaration holder an information notice for the decision to refuse.","sortOrder":123},{"sectionNumber":"sec.103","sectionType":"section","heading":"Acting on regulator’s own initiative—general","content":"### sec.103 Acting on regulator’s own initiative—general\n\nSubject to section&#160;104 , the regulator must not act, to amend the conditions by varying them or imposing new conditions, on the regulator’s own initiative without first giving the declaration holder a notice—\nstating details of the proposed amendment; and\ninviting the declaration holder to make written submissions about the proposal within a stated time of at least 7 days.\nThe regulator must consider all submissions received from the declaration holder under subsection&#160;(1) (b) .\nIf, after considering the submissions (if any), the regulator is of the opinion that the conditions of the declared scheme should be amended as mentioned in subsection&#160;(1) (a) , the regulator may amend the conditions by written notice given to the declaration holder.\nThe amendment has effect when the notice is given to the declaration holder.\nIf the regulator amends the conditions, the regulator must give the declaration holder an information notice for the decision to amend.\n(sec.103-ssec.1) Subject to section&#160;104 , the regulator must not act, to amend the conditions by varying them or imposing new conditions, on the regulator’s own initiative without first giving the declaration holder a notice— stating details of the proposed amendment; and inviting the declaration holder to make written submissions about the proposal within a stated time of at least 7 days.\n(sec.103-ssec.2) The regulator must consider all submissions received from the declaration holder under subsection&#160;(1) (b) .\n(sec.103-ssec.3) If, after considering the submissions (if any), the regulator is of the opinion that the conditions of the declared scheme should be amended as mentioned in subsection&#160;(1) (a) , the regulator may amend the conditions by written notice given to the declaration holder.\n(sec.103-ssec.4) The amendment has effect when the notice is given to the declaration holder.\n(sec.103-ssec.5) If the regulator amends the conditions, the regulator must give the declaration holder an information notice for the decision to amend.\n- (a) stating details of the proposed amendment; and\n- (b) inviting the declaration holder to make written submissions about the proposal within a stated time of at least 7 days.","sortOrder":124},{"sectionNumber":"sec.104","sectionType":"section","heading":"Acting on regulator’s own initiative—electrical risk","content":"### sec.104 Acting on regulator’s own initiative—electrical risk\n\nThis section applies if the regulator considers that a type of level 1, 2 or 3 in-scope electrical equipment certified by a declaration holder is placing, or will place, persons or property at electrical risk.\nThe regulator may amend the conditions applying to the declared scheme, other than the condition imposed under section&#160;101 , by written notice given to the declaration holder.\nThe amendment has effect when the notice is given to the declaration holder.\nIf the regulator amends the conditions, the regulator must give the declaration holder an information notice for the decision to amend.\n(sec.104-ssec.1) This section applies if the regulator considers that a type of level 1, 2 or 3 in-scope electrical equipment certified by a declaration holder is placing, or will place, persons or property at electrical risk.\n(sec.104-ssec.2) The regulator may amend the conditions applying to the declared scheme, other than the condition imposed under section&#160;101 , by written notice given to the declaration holder.\n(sec.104-ssec.3) The amendment has effect when the notice is given to the declaration holder.\n(sec.104-ssec.4) If the regulator amends the conditions, the regulator must give the declaration holder an information notice for the decision to amend.","sortOrder":125},{"sectionNumber":"sec.105","sectionType":"section","heading":"Grounds for cancelling declaration","content":"### sec.105 Grounds for cancelling declaration\n\nEach of the following is a ground for cancelling the declaration of a declared scheme—\nthe declaration holder contravened a condition of the declared scheme;\nthe declaration of the scheme was obtained by giving false information.\n- (a) the declaration holder contravened a condition of the declared scheme;\n- (b) the declaration of the scheme was obtained by giving false information.","sortOrder":126},{"sectionNumber":"sec.106","sectionType":"section","heading":"Procedure before cancellation","content":"### sec.106 Procedure before cancellation\n\nIf the regulator considers a ground exists under section&#160;105 to cancel the declaration of a declared scheme, the regulator must, before taking the action, give the declaration holder written notice—\nstating that the regulator is considering cancelling the declaration; and\nstating each ground for the proposed cancellation; and\noutlining the facts and circumstances forming the basis for each ground; and\ninviting the declaration holder to make written submissions, within a stated time of at least 7 days, as to why the declaration should not be cancelled.\nThe regulator must consider all submissions received from the declaration holder under subsection&#160;(1) (d) .\nIf, after considering the submissions (if any) the regulator still considers a ground exists to cancel the declaration, the regulator may cancel the declaration by written notice given to the declaration holder.\nThe cancellation takes effect on the day the notice is given to the declaration holder.\nIf the regulator cancels the declaration, the regulator must give the declaration holder an information notice for the decision to cancel.\n(sec.106-ssec.1) If the regulator considers a ground exists under section&#160;105 to cancel the declaration of a declared scheme, the regulator must, before taking the action, give the declaration holder written notice— stating that the regulator is considering cancelling the declaration; and stating each ground for the proposed cancellation; and outlining the facts and circumstances forming the basis for each ground; and inviting the declaration holder to make written submissions, within a stated time of at least 7 days, as to why the declaration should not be cancelled.\n(sec.106-ssec.2) The regulator must consider all submissions received from the declaration holder under subsection&#160;(1) (d) .\n(sec.106-ssec.3) If, after considering the submissions (if any) the regulator still considers a ground exists to cancel the declaration, the regulator may cancel the declaration by written notice given to the declaration holder.\n(sec.106-ssec.4) The cancellation takes effect on the day the notice is given to the declaration holder.\n(sec.106-ssec.5) If the regulator cancels the declaration, the regulator must give the declaration holder an information notice for the decision to cancel.\n- (a) stating that the regulator is considering cancelling the declaration; and\n- (b) stating each ground for the proposed cancellation; and\n- (c) outlining the facts and circumstances forming the basis for each ground; and\n- (d) inviting the declaration holder to make written submissions, within a stated time of at least 7 days, as to why the declaration should not be cancelled.","sortOrder":127},{"sectionNumber":"sec.107","sectionType":"section","heading":"Cancellation at declaration holder’s request","content":"### sec.107 Cancellation at declaration holder’s request\n\nThe regulator must cancel the declaration of a declared scheme if the declaration holder asks for the cancellation.","sortOrder":128},{"sectionNumber":"sec.108","sectionType":"section","heading":"Reporting requirements for declaration holder","content":"### sec.108 Reporting requirements for declaration holder\n\nThe regulator may, by written notice given to a declaration holder, require the holder to provide the regulator with any of the following—\nreports or particulars, about the number and nature of certificates given under the declared scheme, as stated in the notice and at the times stated in the notice;\nreports, particulars or other information about the level of compliance with the conditions imposed on the declared scheme under this division, as stated in the notice and at the times stated in the notice.\nThe declaration holder must comply with the notice.\nMaximum penalty for subsection&#160;(2) —40 penalty units.\n(sec.108-ssec.1) The regulator may, by written notice given to a declaration holder, require the holder to provide the regulator with any of the following— reports or particulars, about the number and nature of certificates given under the declared scheme, as stated in the notice and at the times stated in the notice; reports, particulars or other information about the level of compliance with the conditions imposed on the declared scheme under this division, as stated in the notice and at the times stated in the notice.\n(sec.108-ssec.2) The declaration holder must comply with the notice. Maximum penalty for subsection&#160;(2) —40 penalty units.\n- (a) reports or particulars, about the number and nature of certificates given under the declared scheme, as stated in the notice and at the times stated in the notice;\n- (b) reports, particulars or other information about the level of compliance with the conditions imposed on the declared scheme under this division, as stated in the notice and at the times stated in the notice.","sortOrder":129},{"sectionNumber":"sec.109","sectionType":"section","heading":"Declaration holder must comply with equipment safety rules","content":"### sec.109 Declaration holder must comply with equipment safety rules\n\nA declaration holder, in certifying a type of level 1, 2 or 3 in-scope electrical equipment under a declared scheme, must comply with the equipment safety rules.\nMaximum penalty—40 penalty units.","sortOrder":130},{"sectionNumber":"pt.4-div.9","sectionType":"division","heading":"Regulator may require testing of item of level 1, 2 or 3 in-scope electrical equipment","content":"## Regulator may require testing of item of level 1, 2 or 3 in-scope electrical equipment","sortOrder":131},{"sectionNumber":"sec.110","sectionType":"section","heading":"Regulator may require item of in-scope electrical equipment to be submitted","content":"### sec.110 Regulator may require item of in-scope electrical equipment to be submitted\n\nIf the regulator considers it necessary or appropriate for the maintenance of electrical safety, the regulator may decide to have an item of a type of level 1, 2 or 3 in-scope electrical equipment tested and examined to see whether it meets the relevant standard for the type.","sortOrder":132},{"sectionNumber":"sec.111","sectionType":"section","heading":"Procedure for obtaining item of in-scope electrical equipment for testing","content":"### sec.111 Procedure for obtaining item of in-scope electrical equipment for testing\n\nIf the regulator decides to have an item of a type of level 1, 2 or 3 in-scope electrical equipment tested and examined, the regulator may—\nfor an item of a type of level 2 or 3 in-scope electrical equipment—\nby written notice, require a registered responsible supplier in relation to whom the type is registered to give the regulator items of the type for testing and examining within a stated reasonable time; or\nrequire an inspector to select, for testing and examining, items of the type from a place where a registered responsible supplier in relation to whom the type is registered has them stored and give them to the regulator within a stated reasonable time; or\nin any case—buy, for testing and examining, items of the type at any place where they are offered for sale.\nIf the regulator makes a requirement under subsection&#160;(1) (a) (i) , the registered responsible supplier must take all steps that are reasonable in the circumstances to comply with the requirement.\nMaximum penalty—40 penalty units.\nIf the regulator makes a requirement under subsection&#160;(1) (a) (ii) , the registered responsible supplier must take all steps that are reasonable in the circumstances to ensure the inspector is able to comply with the requirement.\nMaximum penalty—40 penalty units.\n(sec.111-ssec.1) If the regulator decides to have an item of a type of level 1, 2 or 3 in-scope electrical equipment tested and examined, the regulator may— for an item of a type of level 2 or 3 in-scope electrical equipment— by written notice, require a registered responsible supplier in relation to whom the type is registered to give the regulator items of the type for testing and examining within a stated reasonable time; or require an inspector to select, for testing and examining, items of the type from a place where a registered responsible supplier in relation to whom the type is registered has them stored and give them to the regulator within a stated reasonable time; or in any case—buy, for testing and examining, items of the type at any place where they are offered for sale.\n(sec.111-ssec.2) If the regulator makes a requirement under subsection&#160;(1) (a) (i) , the registered responsible supplier must take all steps that are reasonable in the circumstances to comply with the requirement. Maximum penalty—40 penalty units.\n(sec.111-ssec.3) If the regulator makes a requirement under subsection&#160;(1) (a) (ii) , the registered responsible supplier must take all steps that are reasonable in the circumstances to ensure the inspector is able to comply with the requirement. Maximum penalty—40 penalty units.\n- (a) for an item of a type of level 2 or 3 in-scope electrical equipment— (i) by written notice, require a registered responsible supplier in relation to whom the type is registered to give the regulator items of the type for testing and examining within a stated reasonable time; or (ii) require an inspector to select, for testing and examining, items of the type from a place where a registered responsible supplier in relation to whom the type is registered has them stored and give them to the regulator within a stated reasonable time; or\n- (i) by written notice, require a registered responsible supplier in relation to whom the type is registered to give the regulator items of the type for testing and examining within a stated reasonable time; or\n- (ii) require an inspector to select, for testing and examining, items of the type from a place where a registered responsible supplier in relation to whom the type is registered has them stored and give them to the regulator within a stated reasonable time; or\n- (b) in any case—buy, for testing and examining, items of the type at any place where they are offered for sale.\n- (i) by written notice, require a registered responsible supplier in relation to whom the type is registered to give the regulator items of the type for testing and examining within a stated reasonable time; or\n- (ii) require an inspector to select, for testing and examining, items of the type from a place where a registered responsible supplier in relation to whom the type is registered has them stored and give them to the regulator within a stated reasonable time; or","sortOrder":133},{"sectionNumber":"sec.112","sectionType":"section","heading":"Identification of item of in-scope electrical equipment to be tested","content":"### sec.112 Identification of item of in-scope electrical equipment to be tested\n\nBefore the regulator gives an item of a type of level 2 or 3 in-scope electrical equipment to an approved testing entity for testing and examining, the regulator must—\ngive the registered responsible supplier from whom the item was obtained under section&#160;111 (1) (a) an opportunity to place an identifying mark on the item; and\nadvise the approved testing entity of the mark.\n- (a) give the registered responsible supplier from whom the item was obtained under section&#160;111 (1) (a) an opportunity to place an identifying mark on the item; and\n- (b) advise the approved testing entity of the mark.","sortOrder":134},{"sectionNumber":"sec.113","sectionType":"section","heading":"Cost of testing and examining and liability for damage","content":"### sec.113 Cost of testing and examining and liability for damage\n\nIf an item of a type of level 1, 2 or 3 in-scope electrical equipment is tested and examined under this division and is found to substantially meet the relevant standard for the type, the regulator must—\nbear the cost of the testing and examination; and\nif the item was obtained under section&#160;111 (1) (a) , compensate the registered responsible supplier for any damage done to the item.\nAn amount for which a registered responsible supplier is entitled to be compensated under subsection&#160;(1) (b) may be recovered from the regulator as a debt owing by the State to the person.\nIf an item of a type of level 2 or 3 in-scope electrical equipment is tested and examined under this division and is found not to substantially meet the relevant standard for the type, the registered responsible supplier from whom the item was obtained under section&#160;111 (1) (a) —\nmust reimburse the regulator for all costs incurred in obtaining and having the item of electrical equipment tested and examined; and\nis not entitled to compensation for damage necessarily caused to the item to enable it to be properly tested and examined.\nAn amount the regulator is entitled to be reimbursed under subsection&#160;(3) (a) may be recovered by the regulator as a debt owing to the State.\n(sec.113-ssec.1) If an item of a type of level 1, 2 or 3 in-scope electrical equipment is tested and examined under this division and is found to substantially meet the relevant standard for the type, the regulator must— bear the cost of the testing and examination; and if the item was obtained under section&#160;111 (1) (a) , compensate the registered responsible supplier for any damage done to the item.\n(sec.113-ssec.2) An amount for which a registered responsible supplier is entitled to be compensated under subsection&#160;(1) (b) may be recovered from the regulator as a debt owing by the State to the person.\n(sec.113-ssec.3) If an item of a type of level 2 or 3 in-scope electrical equipment is tested and examined under this division and is found not to substantially meet the relevant standard for the type, the registered responsible supplier from whom the item was obtained under section&#160;111 (1) (a) — must reimburse the regulator for all costs incurred in obtaining and having the item of electrical equipment tested and examined; and is not entitled to compensation for damage necessarily caused to the item to enable it to be properly tested and examined.\n(sec.113-ssec.4) An amount the regulator is entitled to be reimbursed under subsection&#160;(3) (a) may be recovered by the regulator as a debt owing to the State.\n- (a) bear the cost of the testing and examination; and\n- (b) if the item was obtained under section&#160;111 (1) (a) , compensate the registered responsible supplier for any damage done to the item.\n- (a) must reimburse the regulator for all costs incurred in obtaining and having the item of electrical equipment tested and examined; and\n- (b) is not entitled to compensation for damage necessarily caused to the item to enable it to be properly tested and examined.","sortOrder":135},{"sectionNumber":"pt.4-div.10","sectionType":"division","heading":"Return of in-scope electrical equipment given to regulator","content":"## Return of in-scope electrical equipment given to regulator","sortOrder":136},{"sectionNumber":"sec.114","sectionType":"section","heading":"Return of item of level 2 or 3 in-scope electrical equipment provided to regulator","content":"### sec.114 Return of item of level 2 or 3 in-scope electrical equipment provided to regulator\n\nThis section applies if a person provides the regulator with—\nan item of a type of level 3 in-scope electrical equipment under division&#160;7 ; or\nan item of a type of level 2 or 3 in-scope electrical equipment for testing and examination because of a requirement made by the regulator under division&#160;9 .\nThe regulator must notify the person of the item of in-scope electrical equipment being available for collection by the person at a stated place as soon as practicable after—\nif the item was provided under division&#160;7 —the regulator decides the application to which the item relates; or\nif the item was provided for testing and examination—\nif the regulator believes, on reasonable grounds, that the item is required as evidence in a prosecution for an offence—the prosecution and any appeal from the prosecution; or\nif subparagraph&#160;(i) does not apply—the testing and examination.\nDespite subsection&#160;(2) (b) (i) , the regulator must notify the person immediately after the earlier of the following—\nthe regulator decides the item of in-scope electrical equipment is not required as evidence;\na prosecution for an offence involving the item of in-scope electrical equipment is not started within 6 months from when the notice would have been given if subsection&#160;(2) (b) (i) had not applied.\nIf, at the end of 6 months after the giving of notice, the item of in-scope electrical equipment has not been collected, the regulator may dispose of the item as the regulator considers appropriate and the person is not entitled to claim for the item or any loss or damage to it.\nSubsection&#160;(2) does not apply if the item of in-scope electrical equipment was necessarily destroyed by testing.\n(sec.114-ssec.1) This section applies if a person provides the regulator with— an item of a type of level 3 in-scope electrical equipment under division&#160;7 ; or an item of a type of level 2 or 3 in-scope electrical equipment for testing and examination because of a requirement made by the regulator under division&#160;9 .\n(sec.114-ssec.2) The regulator must notify the person of the item of in-scope electrical equipment being available for collection by the person at a stated place as soon as practicable after— if the item was provided under division&#160;7 —the regulator decides the application to which the item relates; or if the item was provided for testing and examination— if the regulator believes, on reasonable grounds, that the item is required as evidence in a prosecution for an offence—the prosecution and any appeal from the prosecution; or if subparagraph&#160;(i) does not apply—the testing and examination.\n(sec.114-ssec.3) Despite subsection&#160;(2) (b) (i) , the regulator must notify the person immediately after the earlier of the following— the regulator decides the item of in-scope electrical equipment is not required as evidence; a prosecution for an offence involving the item of in-scope electrical equipment is not started within 6 months from when the notice would have been given if subsection&#160;(2) (b) (i) had not applied.\n(sec.114-ssec.4) If, at the end of 6 months after the giving of notice, the item of in-scope electrical equipment has not been collected, the regulator may dispose of the item as the regulator considers appropriate and the person is not entitled to claim for the item or any loss or damage to it.\n(sec.114-ssec.5) Subsection&#160;(2) does not apply if the item of in-scope electrical equipment was necessarily destroyed by testing.\n- (a) an item of a type of level 3 in-scope electrical equipment under division&#160;7 ; or\n- (b) an item of a type of level 2 or 3 in-scope electrical equipment for testing and examination because of a requirement made by the regulator under division&#160;9 .\n- (a) if the item was provided under division&#160;7 —the regulator decides the application to which the item relates; or\n- (b) if the item was provided for testing and examination— (i) if the regulator believes, on reasonable grounds, that the item is required as evidence in a prosecution for an offence—the prosecution and any appeal from the prosecution; or (ii) if subparagraph&#160;(i) does not apply—the testing and examination.\n- (i) if the regulator believes, on reasonable grounds, that the item is required as evidence in a prosecution for an offence—the prosecution and any appeal from the prosecution; or\n- (ii) if subparagraph&#160;(i) does not apply—the testing and examination.\n- (i) if the regulator believes, on reasonable grounds, that the item is required as evidence in a prosecution for an offence—the prosecution and any appeal from the prosecution; or\n- (ii) if subparagraph&#160;(i) does not apply—the testing and examination.\n- (a) the regulator decides the item of in-scope electrical equipment is not required as evidence;\n- (b) a prosecution for an offence involving the item of in-scope electrical equipment is not started within 6 months from when the notice would have been given if subsection&#160;(2) (b) (i) had not applied.","sortOrder":137},{"sectionNumber":"pt.4-div.11","sectionType":"division","heading":"Second-hand items","content":"## Second-hand items","sortOrder":138},{"sectionNumber":"sec.115","sectionType":"section","heading":"Limitation on offering to sell second-hand items","content":"### sec.115 Limitation on offering to sell second-hand items\n\nA seller who offers to sell a second-hand item to another person must give the other person information to the effect that the item has not been tested for electrical safety unless—\nthe item has been tested and found to be electrically safe by a qualified person and the seller gives the other person information about the test; or\nthe other person conducts a business or undertaking that includes dealing in, repairing or reconditioning second-hand items.\nMaximum penalty—40 penalty units.\nIn this section—\nqualified person , for testing a second-hand item, means a licensed electrical worker who is qualified to test the item.\nseller means a person who offers to sell a second-hand item, regardless of whether the offer to sell the item is for profit or gain.\nAn individual who offers to sell a second-hand item online.\nA volunteer of a volunteer association under section&#160;21 (8) of the Act who offers to sell a second-hand item as part of the work of the association.\n(sec.115-ssec.1) A seller who offers to sell a second-hand item to another person must give the other person information to the effect that the item has not been tested for electrical safety unless— the item has been tested and found to be electrically safe by a qualified person and the seller gives the other person information about the test; or the other person conducts a business or undertaking that includes dealing in, repairing or reconditioning second-hand items. Maximum penalty—40 penalty units.\n(sec.115-ssec.2) In this section— qualified person , for testing a second-hand item, means a licensed electrical worker who is qualified to test the item. seller means a person who offers to sell a second-hand item, regardless of whether the offer to sell the item is for profit or gain. An individual who offers to sell a second-hand item online. A volunteer of a volunteer association under section&#160;21 (8) of the Act who offers to sell a second-hand item as part of the work of the association.\n- (a) the item has been tested and found to be electrically safe by a qualified person and the seller gives the other person information about the test; or\n- (b) the other person conducts a business or undertaking that includes dealing in, repairing or reconditioning second-hand items.\n- 1 An individual who offers to sell a second-hand item online.\n- 2 A volunteer of a volunteer association under section&#160;21 (8) of the Act who offers to sell a second-hand item as part of the work of the association.","sortOrder":139},{"sectionNumber":"pt.4-div.12","sectionType":"division","heading":"Program for issuing certificates of suitability","content":"## Program for issuing certificates of suitability","sortOrder":140},{"sectionNumber":"sec.116","sectionType":"section","heading":"Regulator may establish program for issuing certificates of suitability","content":"### sec.116 Regulator may establish program for issuing certificates of suitability\n\nThe regulator may establish a program for the issuing of certificates of suitability for types of level 1 or 2 in-scope electrical equipment.\nThe program may include the charging of fees for the certificates.\nThe program can not require a person to take part in the program.\n(sec.116-ssec.1) The regulator may establish a program for the issuing of certificates of suitability for types of level 1 or 2 in-scope electrical equipment.\n(sec.116-ssec.2) The program may include the charging of fees for the certificates.\n(sec.116-ssec.3) The program can not require a person to take part in the program.","sortOrder":141},{"sectionNumber":"pt.4-div.13","sectionType":"division","heading":"Other matters","content":"## Other matters","sortOrder":142},{"sectionNumber":"sec.117","sectionType":"section","heading":"Corresponding laws— Act , s&#160;48A , definition corresponding law","content":"### sec.117 Corresponding laws— Act , s&#160;48A , definition corresponding law\n\nFor section&#160;48A of the Act , definition corresponding law , the Electricity Safety Act 1998 (Vic) is prescribed.","sortOrder":143},{"sectionNumber":"pt.5","sectionType":"part","heading":"Electrical equipment—general","content":"# Electrical equipment—general","sortOrder":144},{"sectionNumber":"pt.5-div.1","sectionType":"division","heading":"Requirement for warning sign for sale of particular electrical equipment","content":"## Requirement for warning sign for sale of particular electrical equipment","sortOrder":145},{"sectionNumber":"sec.118","sectionType":"section","heading":"Definition for division","content":"### sec.118 Definition for division\n\nIn this division—\nparticular electrical equipment means electrical equipment the installation, removal, addition, testing, replacement, repair, alteration, or maintenance of which is electrical work required under the Act to be performed by a licensed electrical contractor or licensed electrical worker.\nfixed-wired electrical equipment, including, for example, air conditioners, stoves, ovens, electric hot water systems, ceiling fans, light fittings\nelectrical accessories, including, for example, socket-outlets, light switches, electrical cable, wall switches, plugs and cord extension sockets\nelectrical parts, including, for example, electrical motors, switches, solenoids, elements\n- • fixed-wired electrical equipment, including, for example, air conditioners, stoves, ovens, electric hot water systems, ceiling fans, light fittings\n- • electrical accessories, including, for example, socket-outlets, light switches, electrical cable, wall switches, plugs and cord extension sockets\n- • electrical parts, including, for example, electrical motors, switches, solenoids, elements","sortOrder":146},{"sectionNumber":"sec.119","sectionType":"section","heading":"Application of division","content":"### sec.119 Application of division\n\nThis division applies to a person who conducts a business or undertaking that involves the sale of particular electrical equipment to the public.","sortOrder":147},{"sectionNumber":"sec.120","sectionType":"section","heading":"Requirement to display DIY warning sign","content":"### sec.120 Requirement to display DIY warning sign\n\nThe person conducting the business or undertaking must not sell an item of particular electrical equipment unless a DIY warning sign is displayed for the item.\nMaximum penalty—40 penalty units.\nFor subsection&#160;(1) , a DIY warning sign is displayed for an item of particular electrical equipment if the sign is displayed—\nin close proximity to the point of display of the item; or\nas part of the price tag of the item; or\non a label attached to the packaging of the item; or\nas part of the packaging of the item; or\non a label attached to the item.\nHowever, for an item displayed in an online shop, a DIY warning sign is displayed for the item if the sign is displayed at the point of display.\nIn this section—\nDIY warning sign means a sign that—\ncontains a symbol in the form of a red circle and a red diagonal line over the letters ‘DIY’ in black letters; and\neither—\nfor a sign displayed in the way mentioned in subsection&#160;(2) (a) or (3) —contains the words ‘ALL ELECTRICAL WORK MUST BE PERFORMED BY A LICENSED ELECTRICIAN’ in upper case black letters; or\nfor a sign displayed in the way mentioned in subsection&#160;(2) (b) , (c) , (d) or (e) —contains the words ‘MUST BE INSTALLED BY A LICENSED ELECTRICIAN’ in upper case black letters; and\nhas a white background; and\nis unambiguous and clearly legible.\npoint of display , of an item, means—\nfor an item displayed in a shop, warehouse or other physical space—the place where the item is displayed in the shop, warehouse or other physical space; or\nfor an item displayed in an online shop—the place where the item is displayed on the online shop’s website.\n(sec.120-ssec.1) The person conducting the business or undertaking must not sell an item of particular electrical equipment unless a DIY warning sign is displayed for the item. Maximum penalty—40 penalty units.\n(sec.120-ssec.2) For subsection&#160;(1) , a DIY warning sign is displayed for an item of particular electrical equipment if the sign is displayed— in close proximity to the point of display of the item; or as part of the price tag of the item; or on a label attached to the packaging of the item; or as part of the packaging of the item; or on a label attached to the item.\n(sec.120-ssec.3) However, for an item displayed in an online shop, a DIY warning sign is displayed for the item if the sign is displayed at the point of display.\n(sec.120-ssec.4) In this section— DIY warning sign means a sign that— contains a symbol in the form of a red circle and a red diagonal line over the letters ‘DIY’ in black letters; and either— for a sign displayed in the way mentioned in subsection&#160;(2) (a) or (3) —contains the words ‘ALL ELECTRICAL WORK MUST BE PERFORMED BY A LICENSED ELECTRICIAN’ in upper case black letters; or for a sign displayed in the way mentioned in subsection&#160;(2) (b) , (c) , (d) or (e) —contains the words ‘MUST BE INSTALLED BY A LICENSED ELECTRICIAN’ in upper case black letters; and has a white background; and is unambiguous and clearly legible. point of display , of an item, means— for an item displayed in a shop, warehouse or other physical space—the place where the item is displayed in the shop, warehouse or other physical space; or for an item displayed in an online shop—the place where the item is displayed on the online shop’s website.\n- (a) in close proximity to the point of display of the item; or\n- (b) as part of the price tag of the item; or\n- (c) on a label attached to the packaging of the item; or\n- (d) as part of the packaging of the item; or\n- (e) on a label attached to the item.\n- (a) contains a symbol in the form of a red circle and a red diagonal line over the letters ‘DIY’ in black letters; and\n- (b) either— (i) for a sign displayed in the way mentioned in subsection&#160;(2) (a) or (3) —contains the words ‘ALL ELECTRICAL WORK MUST BE PERFORMED BY A LICENSED ELECTRICIAN’ in upper case black letters; or (ii) for a sign displayed in the way mentioned in subsection&#160;(2) (b) , (c) , (d) or (e) —contains the words ‘MUST BE INSTALLED BY A LICENSED ELECTRICIAN’ in upper case black letters; and\n- (i) for a sign displayed in the way mentioned in subsection&#160;(2) (a) or (3) —contains the words ‘ALL ELECTRICAL WORK MUST BE PERFORMED BY A LICENSED ELECTRICIAN’ in upper case black letters; or\n- (ii) for a sign displayed in the way mentioned in subsection&#160;(2) (b) , (c) , (d) or (e) —contains the words ‘MUST BE INSTALLED BY A LICENSED ELECTRICIAN’ in upper case black letters; and\n- (c) has a white background; and\n- (d) is unambiguous and clearly legible.\n- (i) for a sign displayed in the way mentioned in subsection&#160;(2) (a) or (3) —contains the words ‘ALL ELECTRICAL WORK MUST BE PERFORMED BY A LICENSED ELECTRICIAN’ in upper case black letters; or\n- (ii) for a sign displayed in the way mentioned in subsection&#160;(2) (b) , (c) , (d) or (e) —contains the words ‘MUST BE INSTALLED BY A LICENSED ELECTRICIAN’ in upper case black letters; and\n- (a) for an item displayed in a shop, warehouse or other physical space—the place where the item is displayed in the shop, warehouse or other physical space; or\n- (b) for an item displayed in an online shop—the place where the item is displayed on the online shop’s website.","sortOrder":148},{"sectionNumber":"pt.5-div.2","sectionType":"division","heading":"Prohibition on sale of electrical equipment","content":"## Prohibition on sale of electrical equipment","sortOrder":149},{"sectionNumber":"sec.121","sectionType":"section","heading":"Sale of unsafe electrical equipment prohibited","content":"### sec.121 Sale of unsafe electrical equipment prohibited\n\nA person must not sell an item of electrical equipment, other than high voltage equipment, unless the item complies with the safety criteria in AS/NZS 3820 (Essential safety requirements for electrical equipment) as in effect when the item was manufactured or imported.\nMaximum penalty—40 penalty units.","sortOrder":150},{"sectionNumber":"pt.5-div.3","sectionType":"division","heading":"Labelling and inspection of electrical equipment","content":"## Labelling and inspection of electrical equipment","sortOrder":151},{"sectionNumber":"sec.122","sectionType":"section","heading":"Labelling faulty portable electrical equipment","content":"### sec.122 Labelling faulty portable electrical equipment\n\nThis section applies if a person acting under the authority of a distribution entity finds, at a place occupied by a consumer, an item of portable electrical equipment that has a serious defect.\nThe distribution entity must ensure a label is attached to the item of electrical equipment stating that the item is electrically unsafe.\nMaximum penalty—40 penalty units.\nA person must not take the label off the item of electrical equipment or connect a source of electricity to the item unless the item—\nhas been repaired by a licensed electrical worker qualified to repair it; or\nhas been repaired by a person who, because of the operation of section&#160;18 (2) (d) of the Act , was not performing electrical work in repairing the equipment.\nMaximum penalty—40 penalty units.\n(sec.122-ssec.1) This section applies if a person acting under the authority of a distribution entity finds, at a place occupied by a consumer, an item of portable electrical equipment that has a serious defect.\n(sec.122-ssec.2) The distribution entity must ensure a label is attached to the item of electrical equipment stating that the item is electrically unsafe. Maximum penalty—40 penalty units.\n(sec.122-ssec.3) A person must not take the label off the item of electrical equipment or connect a source of electricity to the item unless the item— has been repaired by a licensed electrical worker qualified to repair it; or has been repaired by a person who, because of the operation of section&#160;18 (2) (d) of the Act , was not performing electrical work in repairing the equipment. Maximum penalty—40 penalty units.\n- (a) has been repaired by a licensed electrical worker qualified to repair it; or\n- (b) has been repaired by a person who, because of the operation of section&#160;18 (2) (d) of the Act , was not performing electrical work in repairing the equipment.","sortOrder":152},{"sectionNumber":"pt.6","sectionType":"part","heading":"Workplace electrical equipment","content":"# Workplace electrical equipment","sortOrder":153},{"sectionNumber":"pt.6-div.1","sectionType":"division","heading":"Preliminary","content":"## Preliminary","sortOrder":154},{"sectionNumber":"sec.123","sectionType":"section","heading":"Definitions for part","content":"### sec.123 Definitions for part\n\nIn this part—\namusement device means an amusement device as defined in AS 3533.3 (Amusement rides and devices).\namusement ride means an amusement ride as defined in AS 3533.3 (Amusement rides and devices).\namusement work means work, other than work performed by a non-profit organisation, to assemble, operate or disassemble any of the following on the site on which it is used, intended to be used or has been used—\nan amusement device or amusement ride;\na thing used to provide amusement activities, including side show activities, associated with—\ncarnivals, fairs or shows; or\namusement arcades or similar places;\nproviding hamburgers, fairy floss or massages in a side show\na thing used to provide entertainment or advertising activities, in temporary sites, associated with shows, fairs or carnivals.\nconstruction work means—\nconstruction work within the meaning of the WHS Regulation , section&#160;289 , other than amusement work or rural industry work; or\nwork done in conjunction with construction work mentioned in paragraph&#160;(a) .\ninstallation of plumbing in a house under construction\nelectrical portable outlet device has the meaning given by AS/NZS 3105 (Approval and test specification—Electrical portable outlet devices).\nmanufacturing work means the work of assembly, disassembly, fabrication, installation, maintenance, manufacturing, refurbishment or repair, but does not include amusement work, construction work or rural industry work.\nassembly or fabrication in a welding workshop\nmaintenance or repair of vehicles in a mechanic’s workshop\nmanufacturing work associated with the sorting, processing and packing of food products\nrepairing leaking pipes\nnon-profit organisation means an organisation that is not carried on for the profit or gain of its individual members.\ncharities, churches, clubs, environment protection societies\noffice work means work of an administrative or professional nature carried out in a part of a workplace used as an office.\nprescribed details , for equipment that has been inspected and tested or reinspected and retested, means the following details—\nat least 1 of the following—\nthe date of the testing or retesting;\nthe day by which the equipment must be reinspected and retested;\nif the individual who performed the test or retest of the equipment is employed or engaged by a corporation, at least 1 of the following—\nthe name of the individual;\nthe individual’s electrical contractor licence number;\nthe name of the corporation;\nthe corporation’s electrical contractor licence number;\nif paragraph&#160;(b) does not apply, at least 1 of the following details of the individual who performed the test or retest of the equipment—\nthe name of the individual;\nthe individual’s electrical contractor licence number;\nthe electrical contractor licence number of the individual’s employer;\nthe individual’s electrical worker licence number.\nrural industry work see section&#160;125 .\nsafety switch means a type 1 safety switch or a type 2 safety switch.\nservice work means work that—\ninvolves providing a service; and\nis not amusement work, construction work, manufacturing work, office work or rural industry work.\ncleaning a motel\ncooking in a restaurant\nproviding health services at a health facility\nselling goods from a shop\nteaching at an education facility\ncaring for children at a child care centre\nspecified electrical equipment means—\nfor the performance of amusement work, manufacturing work or rural industry work, the following equipment (other than an amusement device or amusement ride)—\na cord extension set with a current rating of not more than 20A;\nan electrical portable outlet device with a current rating of not more than 20A;\nelectrical equipment, other than a portable safety switch, that—\nhas a current rating of not more than 20A; and\nis connected by a flexible cord and plug to low voltage supply; or\nfor the performance of office work or service work—\na cord extension set with a current rating of not more than 20A; or\nan electrical portable outlet device with a current rating of not more than 20A; or\nelectrical equipment, other than a portable safety switch, that—\nhas a current rating of not more than 20A; and\nis connected by a flexible cord and plug to low voltage supply; and\nis moved during its normal use for the purpose of its use.\ntype 1 safety switch means a residual current device, whether or not portable, with a rated residual current of not more than 10mA.\ntype 2 safety switch means a residual current device, whether or not portable, with a rated residual current of more than 10mA but not more than 30mA.\n- (a) an amusement device or amusement ride;\n- (b) a thing used to provide amusement activities, including side show activities, associated with— (i) carnivals, fairs or shows; or (ii) amusement arcades or similar places; Example of side show activities— providing hamburgers, fairy floss or massages in a side show\n- (i) carnivals, fairs or shows; or\n- (ii) amusement arcades or similar places; Example of side show activities— providing hamburgers, fairy floss or massages in a side show\n- (c) a thing used to provide entertainment or advertising activities, in temporary sites, associated with shows, fairs or carnivals.\n- (i) carnivals, fairs or shows; or\n- (ii) amusement arcades or similar places; Example of side show activities— providing hamburgers, fairy floss or massages in a side show\n- (a) construction work within the meaning of the WHS Regulation , section&#160;289 , other than amusement work or rural industry work; or\n- (b) work done in conjunction with construction work mentioned in paragraph&#160;(a) . Example of paragraph&#160;(b) — installation of plumbing in a house under construction\n- • assembly or fabrication in a welding workshop\n- • maintenance or repair of vehicles in a mechanic’s workshop\n- • manufacturing work associated with the sorting, processing and packing of food products\n- • repairing leaking pipes\n- (a) at least 1 of the following— (i) the date of the testing or retesting; (ii) the day by which the equipment must be reinspected and retested;\n- (i) the date of the testing or retesting;\n- (ii) the day by which the equipment must be reinspected and retested;\n- (b) if the individual who performed the test or retest of the equipment is employed or engaged by a corporation, at least 1 of the following— (i) the name of the individual; (ii) the individual’s electrical contractor licence number; (iii) the name of the corporation; (iv) the corporation’s electrical contractor licence number;\n- (i) the name of the individual;\n- (ii) the individual’s electrical contractor licence number;\n- (iii) the name of the corporation;\n- (iv) the corporation’s electrical contractor licence number;\n- (c) if paragraph&#160;(b) does not apply, at least 1 of the following details of the individual who performed the test or retest of the equipment— (i) the name of the individual; (ii) the individual’s electrical contractor licence number; (iii) the electrical contractor licence number of the individual’s employer; (iv) the individual’s electrical worker licence number.\n- (i) the name of the individual;\n- (ii) the individual’s electrical contractor licence number;\n- (iii) the electrical contractor licence number of the individual’s employer;\n- (iv) the individual’s electrical worker licence number.\n- (i) the date of the testing or retesting;\n- (ii) the day by which the equipment must be reinspected and retested;\n- (i) the name of the individual;\n- (ii) the individual’s electrical contractor licence number;\n- (iii) the name of the corporation;\n- (iv) the corporation’s electrical contractor licence number;\n- (i) the name of the individual;\n- (ii) the individual’s electrical contractor licence number;\n- (iii) the electrical contractor licence number of the individual’s employer;\n- (iv) the individual’s electrical worker licence number.\n- (a) involves providing a service; and\n- (b) is not amusement work, construction work, manufacturing work, office work or rural industry work.\n- • cleaning a motel\n- • cooking in a restaurant\n- • providing health services at a health facility\n- • selling goods from a shop\n- • teaching at an education facility\n- • caring for children at a child care centre\n- (a) for the performance of amusement work, manufacturing work or rural industry work, the following equipment (other than an amusement device or amusement ride)— (i) a cord extension set with a current rating of not more than 20A; (ii) an electrical portable outlet device with a current rating of not more than 20A; (iii) electrical equipment, other than a portable safety switch, that— (A) has a current rating of not more than 20A; and (B) is connected by a flexible cord and plug to low voltage supply; or\n- (i) a cord extension set with a current rating of not more than 20A;\n- (ii) an electrical portable outlet device with a current rating of not more than 20A;\n- (iii) electrical equipment, other than a portable safety switch, that— (A) has a current rating of not more than 20A; and (B) is connected by a flexible cord and plug to low voltage supply; or\n- (A) has a current rating of not more than 20A; and\n- (B) is connected by a flexible cord and plug to low voltage supply; or\n- (b) for the performance of office work or service work— (i) a cord extension set with a current rating of not more than 20A; or (ii) an electrical portable outlet device with a current rating of not more than 20A; or (iii) electrical equipment, other than a portable safety switch, that— (A) has a current rating of not more than 20A; and (B) is connected by a flexible cord and plug to low voltage supply; and (C) is moved during its normal use for the purpose of its use.\n- (i) a cord extension set with a current rating of not more than 20A; or\n- (ii) an electrical portable outlet device with a current rating of not more than 20A; or\n- (iii) electrical equipment, other than a portable safety switch, that— (A) has a current rating of not more than 20A; and (B) is connected by a flexible cord and plug to low voltage supply; and (C) is moved during its normal use for the purpose of its use.\n- (A) has a current rating of not more than 20A; and\n- (B) is connected by a flexible cord and plug to low voltage supply; and\n- (C) is moved during its normal use for the purpose of its use.\n- (i) a cord extension set with a current rating of not more than 20A;\n- (ii) an electrical portable outlet device with a current rating of not more than 20A;\n- (iii) electrical equipment, other than a portable safety switch, that— (A) has a current rating of not more than 20A; and (B) is connected by a flexible cord and plug to low voltage supply; or\n- (A) has a current rating of not more than 20A; and\n- (B) is connected by a flexible cord and plug to low voltage supply; or\n- (A) has a current rating of not more than 20A; and\n- (B) is connected by a flexible cord and plug to low voltage supply; or\n- (i) a cord extension set with a current rating of not more than 20A; or\n- (ii) an electrical portable outlet device with a current rating of not more than 20A; or\n- (iii) electrical equipment, other than a portable safety switch, that— (A) has a current rating of not more than 20A; and (B) is connected by a flexible cord and plug to low voltage supply; and (C) is moved during its normal use for the purpose of its use.\n- (A) has a current rating of not more than 20A; and\n- (B) is connected by a flexible cord and plug to low voltage supply; and\n- (C) is moved during its normal use for the purpose of its use.\n- (A) has a current rating of not more than 20A; and\n- (B) is connected by a flexible cord and plug to low voltage supply; and\n- (C) is moved during its normal use for the purpose of its use.","sortOrder":155},{"sectionNumber":"sec.124","sectionType":"section","heading":"References to electrical equipment for part","content":"### sec.124 References to electrical equipment for part\n\nIn this part, a reference to electrical equipment in relation to a person conducting a business or undertaking is a reference to electrical equipment that is under the person’s management or control.","sortOrder":156},{"sectionNumber":"sec.125","sectionType":"section","heading":"Meaning of rural industry work","content":"### sec.125 Meaning of rural industry work\n\nRural industry work is work—\nin the cultivation of any agricultural crop or product whether or not grown for food; or\nin the rearing and management of farm animals; or\nlivestock, bees, worms\nin the classing, scouring, sorting or pressing of wool; or\nthat is aquaculture; or\nin flower or vegetable market gardens; or\nfor clearing, fencing, trenching, draining or otherwise preparing land for anything stated in paragraph&#160;(a) , (b) , (d) or (e) .\nRural industry work includes work that is construction work, manufacturing work or office work performed for the purposes of an activity mentioned in subsection&#160;(1) if—\nthe work is performed by a person conducting a business or undertaking, or a worker for the person; and\nthe product of the work is to be used in the business or undertaking; and\nthe work is performed at premises at which the product of the work is to be used.\nrepairing farm machinery, including, for example, tractors and implements\nmaking farm machinery, including, for example, cattle crushes, spray booms or fruit picking booms\nbuilding sheds\nRural industry work does not include work to which an activity mentioned in subsection&#160;(1) is only incidental.\nwork in carrying on a farm stay\nwork in conducting a tour associated with rural industry work\n(sec.125-ssec.1) Rural industry work is work— in the cultivation of any agricultural crop or product whether or not grown for food; or in the rearing and management of farm animals; or livestock, bees, worms in the classing, scouring, sorting or pressing of wool; or that is aquaculture; or in flower or vegetable market gardens; or for clearing, fencing, trenching, draining or otherwise preparing land for anything stated in paragraph&#160;(a) , (b) , (d) or (e) .\n(sec.125-ssec.2) Rural industry work includes work that is construction work, manufacturing work or office work performed for the purposes of an activity mentioned in subsection&#160;(1) if— the work is performed by a person conducting a business or undertaking, or a worker for the person; and the product of the work is to be used in the business or undertaking; and the work is performed at premises at which the product of the work is to be used. repairing farm machinery, including, for example, tractors and implements making farm machinery, including, for example, cattle crushes, spray booms or fruit picking booms building sheds\n(sec.125-ssec.3) Rural industry work does not include work to which an activity mentioned in subsection&#160;(1) is only incidental. work in carrying on a farm stay work in conducting a tour associated with rural industry work\n- (a) in the cultivation of any agricultural crop or product whether or not grown for food; or\n- (b) in the rearing and management of farm animals; or Examples of farm animals— livestock, bees, worms\n- (c) in the classing, scouring, sorting or pressing of wool; or\n- (d) that is aquaculture; or\n- (e) in flower or vegetable market gardens; or\n- (f) for clearing, fencing, trenching, draining or otherwise preparing land for anything stated in paragraph&#160;(a) , (b) , (d) or (e) .\n- (a) the work is performed by a person conducting a business or undertaking, or a worker for the person; and\n- (b) the product of the work is to be used in the business or undertaking; and\n- (c) the work is performed at premises at which the product of the work is to be used.\n- • repairing farm machinery, including, for example, tractors and implements\n- • making farm machinery, including, for example, cattle crushes, spray booms or fruit picking booms\n- • building sheds\n- • work in carrying on a farm stay\n- • work in conducting a tour associated with rural industry work","sortOrder":157},{"sectionNumber":"pt.6-div.2","sectionType":"division","heading":"Amusement work","content":"## Amusement work","sortOrder":158},{"sectionNumber":"sec.126","sectionType":"section","heading":"Application of division","content":"### sec.126 Application of division\n\nThis division applies to a person conducting a business or undertaking that involves amusement work performed at a workplace.","sortOrder":159},{"sectionNumber":"sec.127","sectionType":"section","heading":"Double adaptors and piggyback plugs prohibited","content":"### sec.127 Double adaptors and piggyback plugs prohibited\n\nThe person conducting the business or undertaking must ensure that workers performing the amusement work for the person do not use a double adaptor or piggyback plug.\nThis section is linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).","sortOrder":160},{"sectionNumber":"sec.128","sectionType":"section","heading":"Specified electrical equipment","content":"### sec.128 Specified electrical equipment\n\nThe person conducting the business or undertaking must ensure specified electrical equipment of the person is not used to perform the amusement work unless the equipment is—\ninspected and tested by a competent person—\nif the equipment is double insulated—at least once every year; or\nif the equipment is not double insulated—at least once every 6 months; and\nconnected to a safety switch.\nIf, after inspecting and testing the equipment under subsection&#160;(1) (a) the competent person decides the equipment is safe to use, the person conducting the business or undertaking must ensure the competent person immediately attaches a durable tag to the equipment that states the prescribed details for the equipment.\nIf, after inspecting and testing the equipment under subsection&#160;(1) (a) the competent person decides the equipment is not safe to use, the person conducting the business or undertaking must ensure—\nthe competent person immediately attaches a durable tag to the equipment that warns people not to use the equipment; and\nthe equipment is immediately withdrawn from use.\nThe person conducting the business or undertaking must ensure that, for the purposes of the business or undertaking, a tag is not attached to the equipment under subsection&#160;(2) unless—\nthe equipment is new; or\nboth of the following apply—\nthe equipment has been inspected and tested by a competent person;\nthe tag was attached by the competent person.\nSubsections&#160;(1) to (4) are linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n(sec.128-ssec.1) The person conducting the business or undertaking must ensure specified electrical equipment of the person is not used to perform the amusement work unless the equipment is— inspected and tested by a competent person— if the equipment is double insulated—at least once every year; or if the equipment is not double insulated—at least once every 6 months; and connected to a safety switch.\n(sec.128-ssec.2) If, after inspecting and testing the equipment under subsection&#160;(1) (a) the competent person decides the equipment is safe to use, the person conducting the business or undertaking must ensure the competent person immediately attaches a durable tag to the equipment that states the prescribed details for the equipment.\n(sec.128-ssec.3) If, after inspecting and testing the equipment under subsection&#160;(1) (a) the competent person decides the equipment is not safe to use, the person conducting the business or undertaking must ensure— the competent person immediately attaches a durable tag to the equipment that warns people not to use the equipment; and the equipment is immediately withdrawn from use.\n(sec.128-ssec.4) The person conducting the business or undertaking must ensure that, for the purposes of the business or undertaking, a tag is not attached to the equipment under subsection&#160;(2) unless— the equipment is new; or both of the following apply— the equipment has been inspected and tested by a competent person; the tag was attached by the competent person. Subsections&#160;(1) to (4) are linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n- (a) inspected and tested by a competent person— (i) if the equipment is double insulated—at least once every year; or (ii) if the equipment is not double insulated—at least once every 6 months; and\n- (i) if the equipment is double insulated—at least once every year; or\n- (ii) if the equipment is not double insulated—at least once every 6 months; and\n- (b) connected to a safety switch.\n- (i) if the equipment is double insulated—at least once every year; or\n- (ii) if the equipment is not double insulated—at least once every 6 months; and\n- (a) the competent person immediately attaches a durable tag to the equipment that warns people not to use the equipment; and\n- (b) the equipment is immediately withdrawn from use.\n- (a) the equipment is new; or\n- (b) both of the following apply— (i) the equipment has been inspected and tested by a competent person; (ii) the tag was attached by the competent person.\n- (i) the equipment has been inspected and tested by a competent person;\n- (ii) the tag was attached by the competent person.\n- (i) the equipment has been inspected and tested by a competent person;\n- (ii) the tag was attached by the competent person.","sortOrder":161},{"sectionNumber":"sec.129","sectionType":"section","heading":"Amusement devices and amusement rides","content":"### sec.129 Amusement devices and amusement rides\n\nThe person conducting the business or undertaking must ensure all or part of an amusement device or amusement ride at the workplace, that is electrical equipment connected to the electricity supply by a plug, is not used to perform amusement work unless—\nthe equipment is inspected and tested by a competent person—\neach time it is assembled on the site where it is intended to be used; and\nin any event at least once every 6 months; and\nfor a device or ride with a current rating of not more than 20A—the equipment is connected to a safety switch.\nAn inspection and test under subsection&#160;(1) (a) must include the competent person—\ndeciding the safety of earthing, insulation and connections; and\ndeciding whether any safety switch complies with AS/NZS 3760 (In-service safety inspection and testing of electrical equipment and RCDs) when tested; and\nmaking a visual examination to decide the safety of the items of electrical equipment of the device or ride, including cabling, plugs, sockets, light fittings, enclosures and motors.\nIf, after inspecting and testing the equipment under subsection&#160;(1) (a) , the competent person decides the equipment is safe to use, the person conducting the business or undertaking must ensure the competent person immediately makes a written record of—\ndetails of the test; and\nthe prescribed details for the equipment.\nIf, after inspecting and testing the equipment under subsection&#160;(1) (a) , the competent person decides the equipment is not safe to use, the person conducting the business or undertaking must ensure—\nthe competent person immediately—\nattaches a durable, conspicuous sign to the equipment that warns people not to use the equipment; and\nmakes a written record of details of the test; and\nthe equipment is immediately withdrawn from use.\nThe person conducting the business or undertaking must ensure a written record of the day by which the equipment must be reinspected and retested is not made with the authority of the person unless the equipment has been inspected and tested by a competent person.\nSubsections&#160;(1) to (5) are linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n(sec.129-ssec.1) The person conducting the business or undertaking must ensure all or part of an amusement device or amusement ride at the workplace, that is electrical equipment connected to the electricity supply by a plug, is not used to perform amusement work unless— the equipment is inspected and tested by a competent person— each time it is assembled on the site where it is intended to be used; and in any event at least once every 6 months; and for a device or ride with a current rating of not more than 20A—the equipment is connected to a safety switch.\n(sec.129-ssec.2) An inspection and test under subsection&#160;(1) (a) must include the competent person— deciding the safety of earthing, insulation and connections; and deciding whether any safety switch complies with AS/NZS 3760 (In-service safety inspection and testing of electrical equipment and RCDs) when tested; and making a visual examination to decide the safety of the items of electrical equipment of the device or ride, including cabling, plugs, sockets, light fittings, enclosures and motors.\n(sec.129-ssec.3) If, after inspecting and testing the equipment under subsection&#160;(1) (a) , the competent person decides the equipment is safe to use, the person conducting the business or undertaking must ensure the competent person immediately makes a written record of— details of the test; and the prescribed details for the equipment.\n(sec.129-ssec.4) If, after inspecting and testing the equipment under subsection&#160;(1) (a) , the competent person decides the equipment is not safe to use, the person conducting the business or undertaking must ensure— the competent person immediately— attaches a durable, conspicuous sign to the equipment that warns people not to use the equipment; and makes a written record of details of the test; and the equipment is immediately withdrawn from use.\n(sec.129-ssec.5) The person conducting the business or undertaking must ensure a written record of the day by which the equipment must be reinspected and retested is not made with the authority of the person unless the equipment has been inspected and tested by a competent person. Subsections&#160;(1) to (5) are linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n- (a) the equipment is inspected and tested by a competent person— (i) each time it is assembled on the site where it is intended to be used; and (ii) in any event at least once every 6 months; and\n- (i) each time it is assembled on the site where it is intended to be used; and\n- (ii) in any event at least once every 6 months; and\n- (b) for a device or ride with a current rating of not more than 20A—the equipment is connected to a safety switch.\n- (i) each time it is assembled on the site where it is intended to be used; and\n- (ii) in any event at least once every 6 months; and\n- (a) deciding the safety of earthing, insulation and connections; and\n- (b) deciding whether any safety switch complies with AS/NZS 3760 (In-service safety inspection and testing of electrical equipment and RCDs) when tested; and\n- (c) making a visual examination to decide the safety of the items of electrical equipment of the device or ride, including cabling, plugs, sockets, light fittings, enclosures and motors.\n- (a) details of the test; and\n- (b) the prescribed details for the equipment.\n- (a) the competent person immediately— (i) attaches a durable, conspicuous sign to the equipment that warns people not to use the equipment; and (ii) makes a written record of details of the test; and\n- (i) attaches a durable, conspicuous sign to the equipment that warns people not to use the equipment; and\n- (ii) makes a written record of details of the test; and\n- (b) the equipment is immediately withdrawn from use.\n- (i) attaches a durable, conspicuous sign to the equipment that warns people not to use the equipment; and\n- (ii) makes a written record of details of the test; and","sortOrder":162},{"sectionNumber":"sec.130","sectionType":"section","heading":"Safety switches, including portable safety switches","content":"### sec.130 Safety switches, including portable safety switches\n\nThe person conducting the business or undertaking must not use, or allow to be used, a safety switch unless it complies with AS/NZS 3760 (In-service safety inspection and testing of electrical equipment and RCDs) when tested.\nThe person conducting the business or undertaking must ensure each safety switch, other than a portable safety switch, at the workplace—\nis tested by a competent person in accordance with AS/NZS 3760 immediately after it is connected; and\nis tested in accordance with, and at the intervals stated in, AS/NZS 3760.\nThe person conducting the business or undertaking must ensure each portable safety switch at the workplace—\nis tested by pushing the test button on the safety switch immediately after it is connected; and\nis tested in accordance with, and at the intervals stated in, AS/NZS 3760.\nIf a safety switch is not working properly, the person conducting the business or undertaking must ensure—\na durable tag is immediately attached to the safety switch that warns people not to use the safety switch; and\nthe safety switch is immediately withdrawn from use.\nSubsections&#160;(1) to (4) are linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n(sec.130-ssec.1) The person conducting the business or undertaking must not use, or allow to be used, a safety switch unless it complies with AS/NZS 3760 (In-service safety inspection and testing of electrical equipment and RCDs) when tested.\n(sec.130-ssec.2) The person conducting the business or undertaking must ensure each safety switch, other than a portable safety switch, at the workplace— is tested by a competent person in accordance with AS/NZS 3760 immediately after it is connected; and is tested in accordance with, and at the intervals stated in, AS/NZS 3760.\n(sec.130-ssec.3) The person conducting the business or undertaking must ensure each portable safety switch at the workplace— is tested by pushing the test button on the safety switch immediately after it is connected; and is tested in accordance with, and at the intervals stated in, AS/NZS 3760.\n(sec.130-ssec.4) If a safety switch is not working properly, the person conducting the business or undertaking must ensure— a durable tag is immediately attached to the safety switch that warns people not to use the safety switch; and the safety switch is immediately withdrawn from use. Subsections&#160;(1) to (4) are linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n- (a) is tested by a competent person in accordance with AS/NZS 3760 immediately after it is connected; and\n- (b) is tested in accordance with, and at the intervals stated in, AS/NZS 3760.\n- (a) is tested by pushing the test button on the safety switch immediately after it is connected; and\n- (b) is tested in accordance with, and at the intervals stated in, AS/NZS 3760.\n- (a) a durable tag is immediately attached to the safety switch that warns people not to use the safety switch; and\n- (b) the safety switch is immediately withdrawn from use.","sortOrder":163},{"sectionNumber":"pt.6-div.3","sectionType":"division","heading":"Manufacturing work","content":"## Manufacturing work","sortOrder":164},{"sectionNumber":"sec.131","sectionType":"section","heading":"Application of division","content":"### sec.131 Application of division\n\nThis division applies to a person conducting a business or undertaking that involves manufacturing work performed at a workplace.","sortOrder":165},{"sectionNumber":"sec.132","sectionType":"section","heading":"Double adaptors and piggyback plugs prohibited","content":"### sec.132 Double adaptors and piggyback plugs prohibited\n\nThe person conducting the business or undertaking must ensure a worker performing the manufacturing work for the person does not use a double adaptor or piggyback plug.\nThis section is linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).","sortOrder":166},{"sectionNumber":"sec.133","sectionType":"section","heading":"Specified electrical equipment","content":"### sec.133 Specified electrical equipment\n\nThe person conducting the business or undertaking must ensure specified electrical equipment of the person at the workplace is not used to perform the manufacturing work unless the equipment is inspected and tested by a competent person—\nif the equipment is double insulated—at least once every year; or\nif the equipment is not double insulated—at least once every 6 months.\na hand held grinder plugged into a socket-outlet\na hand held electric drill plugged into a socket-outlet that is used for drilling holes in steelwork in a light engineering workshop\nAlso, the person conducting the business or undertaking must ensure specified electrical equipment of the person is not used to perform the manufacturing work unless the equipment is connected to a socket-outlet for which 1 of the following safety switches has been installed—\nif the socket-outlet is in a permanent workplace under the control of the person—a safety switch that is not portable;\nif the socket-outlet is not in a permanent workplace under the control of the person—a safety switch.\nHowever, subsection&#160;(2) does not apply to the person in relation to a socket-outlet that is—\nmentioned in subsection&#160;(2) (a) if—\nthe person is exempt under section&#160;135 ; and\nthe socket-outlet has a safety switch installed; or\nboth—\nmore than 2.3m above the floor; and\nprovided for the purpose of supplying electricity to a luminaire or to electrical equipment with a power rating of not more than 150W.\nIf, after inspecting and testing the equipment under subsection&#160;(1) , the competent person decides the equipment is safe to use, the person conducting the business or undertaking must ensure the competent person immediately attaches a durable tag to the equipment that states the prescribed details for the equipment.\nIf, after inspecting and testing the equipment under subsection&#160;(1) , the competent person decides the equipment is not safe to use, the person conducting the business or undertaking must ensure—\nthe competent person immediately attaches a durable tag to the equipment that warns people not to use the equipment; and\nthe equipment is immediately withdrawn from use.\nThe person conducting the business or undertaking must ensure that, for the purposes of the business or undertaking, a tag is not attached to specified electrical equipment under subsection&#160;(4) unless—\nthe equipment is new; or\nboth of the following apply—\nthe equipment has been inspected and tested by a competent person;\nthe tag was attached by the competent person.\nSubsections&#160;(1) to (6) are linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n(sec.133-ssec.1) The person conducting the business or undertaking must ensure specified electrical equipment of the person at the workplace is not used to perform the manufacturing work unless the equipment is inspected and tested by a competent person— if the equipment is double insulated—at least once every year; or if the equipment is not double insulated—at least once every 6 months. a hand held grinder plugged into a socket-outlet a hand held electric drill plugged into a socket-outlet that is used for drilling holes in steelwork in a light engineering workshop\n(sec.133-ssec.2) Also, the person conducting the business or undertaking must ensure specified electrical equipment of the person is not used to perform the manufacturing work unless the equipment is connected to a socket-outlet for which 1 of the following safety switches has been installed— if the socket-outlet is in a permanent workplace under the control of the person—a safety switch that is not portable; if the socket-outlet is not in a permanent workplace under the control of the person—a safety switch.\n(sec.133-ssec.3) However, subsection&#160;(2) does not apply to the person in relation to a socket-outlet that is— mentioned in subsection&#160;(2) (a) if— the person is exempt under section&#160;135 ; and the socket-outlet has a safety switch installed; or both— more than 2.3m above the floor; and provided for the purpose of supplying electricity to a luminaire or to electrical equipment with a power rating of not more than 150W.\n(sec.133-ssec.4) If, after inspecting and testing the equipment under subsection&#160;(1) , the competent person decides the equipment is safe to use, the person conducting the business or undertaking must ensure the competent person immediately attaches a durable tag to the equipment that states the prescribed details for the equipment.\n(sec.133-ssec.5) If, after inspecting and testing the equipment under subsection&#160;(1) , the competent person decides the equipment is not safe to use, the person conducting the business or undertaking must ensure— the competent person immediately attaches a durable tag to the equipment that warns people not to use the equipment; and the equipment is immediately withdrawn from use.\n(sec.133-ssec.6) The person conducting the business or undertaking must ensure that, for the purposes of the business or undertaking, a tag is not attached to specified electrical equipment under subsection&#160;(4) unless— the equipment is new; or both of the following apply— the equipment has been inspected and tested by a competent person; the tag was attached by the competent person. Subsections&#160;(1) to (6) are linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n- (a) if the equipment is double insulated—at least once every year; or\n- (b) if the equipment is not double insulated—at least once every 6 months.\n- • a hand held grinder plugged into a socket-outlet\n- • a hand held electric drill plugged into a socket-outlet that is used for drilling holes in steelwork in a light engineering workshop\n- (a) if the socket-outlet is in a permanent workplace under the control of the person—a safety switch that is not portable;\n- (b) if the socket-outlet is not in a permanent workplace under the control of the person—a safety switch.\n- (a) mentioned in subsection&#160;(2) (a) if— (i) the person is exempt under section&#160;135 ; and (ii) the socket-outlet has a safety switch installed; or\n- (i) the person is exempt under section&#160;135 ; and\n- (ii) the socket-outlet has a safety switch installed; or\n- (b) both— (i) more than 2.3m above the floor; and (ii) provided for the purpose of supplying electricity to a luminaire or to electrical equipment with a power rating of not more than 150W.\n- (i) more than 2.3m above the floor; and\n- (ii) provided for the purpose of supplying electricity to a luminaire or to electrical equipment with a power rating of not more than 150W.\n- (i) the person is exempt under section&#160;135 ; and\n- (ii) the socket-outlet has a safety switch installed; or\n- (i) more than 2.3m above the floor; and\n- (ii) provided for the purpose of supplying electricity to a luminaire or to electrical equipment with a power rating of not more than 150W.\n- (a) the competent person immediately attaches a durable tag to the equipment that warns people not to use the equipment; and\n- (b) the equipment is immediately withdrawn from use.\n- (a) the equipment is new; or\n- (b) both of the following apply— (i) the equipment has been inspected and tested by a competent person; (ii) the tag was attached by the competent person.\n- (i) the equipment has been inspected and tested by a competent person;\n- (ii) the tag was attached by the competent person.\n- (i) the equipment has been inspected and tested by a competent person;\n- (ii) the tag was attached by the competent person.","sortOrder":167},{"sectionNumber":"sec.134","sectionType":"section","heading":"Manufacturing work—safety switch","content":"### sec.134 Manufacturing work—safety switch\n\nThis section applies if—\nmanufacturing work is the primary work performed at the workplace; and\na socket-outlet with a current rating of not more than 20A is installed and supplies electricity to the workplace; and\nthe socket-outlet is—\nnot more than 2.3m above the floor; and\nnot provided for the purpose of supplying electricity to a luminaire or to electrical equipment with a power rating of not more than 150W.\nBefore the manufacturing work is performed, the person conducting the business or undertaking must ensure a safety switch, that is not portable, is installed for the socket-outlet.\nMaximum penalty—15 penalty units.\nSubsection&#160;(2) does not apply if the person conducting the business or undertaking is exempt under section&#160;135 .\n(sec.134-ssec.1) This section applies if— manufacturing work is the primary work performed at the workplace; and a socket-outlet with a current rating of not more than 20A is installed and supplies electricity to the workplace; and the socket-outlet is— not more than 2.3m above the floor; and not provided for the purpose of supplying electricity to a luminaire or to electrical equipment with a power rating of not more than 150W.\n(sec.134-ssec.2) Before the manufacturing work is performed, the person conducting the business or undertaking must ensure a safety switch, that is not portable, is installed for the socket-outlet. Maximum penalty—15 penalty units.\n(sec.134-ssec.3) Subsection&#160;(2) does not apply if the person conducting the business or undertaking is exempt under section&#160;135 .\n- (a) manufacturing work is the primary work performed at the workplace; and\n- (b) a socket-outlet with a current rating of not more than 20A is installed and supplies electricity to the workplace; and\n- (c) the socket-outlet is— (i) not more than 2.3m above the floor; and (ii) not provided for the purpose of supplying electricity to a luminaire or to electrical equipment with a power rating of not more than 150W.\n- (i) not more than 2.3m above the floor; and\n- (ii) not provided for the purpose of supplying electricity to a luminaire or to electrical equipment with a power rating of not more than 150W.\n- (i) not more than 2.3m above the floor; and\n- (ii) not provided for the purpose of supplying electricity to a luminaire or to electrical equipment with a power rating of not more than 150W.","sortOrder":168},{"sectionNumber":"sec.135","sectionType":"section","heading":"Exemption for safety switches","content":"### sec.135 Exemption for safety switches\n\nThe person conducting the business or undertaking is exempt from complying with section&#160;133 (2) or 134 (2) if the person conducting the business or undertaking—\nis not the person in control of the electrical equipment to which the safety switch is to be installed to comply with the section; and\nhas been unable to obtain permission from the person in control of the electrical equipment for the installation of the safety switch.\n- (a) is not the person in control of the electrical equipment to which the safety switch is to be installed to comply with the section; and\n- (b) has been unable to obtain permission from the person in control of the electrical equipment for the installation of the safety switch.","sortOrder":169},{"sectionNumber":"sec.136","sectionType":"section","heading":"Safety switches, including portable safety switches","content":"### sec.136 Safety switches, including portable safety switches\n\nThe person conducting the business or undertaking must not use, or allow to be used, a safety switch unless it complies with AS/NZS 3760 (In-service safety inspection and testing of electrical equipment and RCDs) when tested.\nThe person conducting the business or undertaking must ensure each safety switch, other than a portable safety switch, at the workplace—\nis tested by a competent person immediately after it is connected; and\nis tested under, and at the intervals stated in, AS/NZS 3760.\nThe person conducting the business or undertaking must ensure each portable safety switch the person has at the workplace—\nis tested by pushing the test button on the safety switch immediately after it is connected; and\nis tested under, and at the intervals stated in, AS/NZS 3760.\nIf a safety switch is not working properly, the person conducting the business or undertaking must ensure—\na durable tag is immediately attached to the safety switch that warns people not to use the safety switch; and\nthe safety switch is immediately withdrawn from use.\nSubsections&#160;(1) to (4) are linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n(sec.136-ssec.1) The person conducting the business or undertaking must not use, or allow to be used, a safety switch unless it complies with AS/NZS 3760 (In-service safety inspection and testing of electrical equipment and RCDs) when tested.\n(sec.136-ssec.2) The person conducting the business or undertaking must ensure each safety switch, other than a portable safety switch, at the workplace— is tested by a competent person immediately after it is connected; and is tested under, and at the intervals stated in, AS/NZS 3760.\n(sec.136-ssec.3) The person conducting the business or undertaking must ensure each portable safety switch the person has at the workplace— is tested by pushing the test button on the safety switch immediately after it is connected; and is tested under, and at the intervals stated in, AS/NZS 3760.\n(sec.136-ssec.4) If a safety switch is not working properly, the person conducting the business or undertaking must ensure— a durable tag is immediately attached to the safety switch that warns people not to use the safety switch; and the safety switch is immediately withdrawn from use. Subsections&#160;(1) to (4) are linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n- (a) is tested by a competent person immediately after it is connected; and\n- (b) is tested under, and at the intervals stated in, AS/NZS 3760.\n- (a) is tested by pushing the test button on the safety switch immediately after it is connected; and\n- (b) is tested under, and at the intervals stated in, AS/NZS 3760.\n- (a) a durable tag is immediately attached to the safety switch that warns people not to use the safety switch; and\n- (b) the safety switch is immediately withdrawn from use.","sortOrder":170},{"sectionNumber":"pt.6-div.4","sectionType":"division","heading":"Service work or office work","content":"## Service work or office work","sortOrder":171},{"sectionNumber":"sec.137","sectionType":"section","heading":"Application of division","content":"### sec.137 Application of division\n\nThis division applies to a person conducting a business or undertaking that involves service work or office work performed at a workplace.","sortOrder":172},{"sectionNumber":"sec.138","sectionType":"section","heading":"Specified electrical equipment","content":"### sec.138 Specified electrical equipment\n\nThe person conducting the business or undertaking must ensure specified electrical equipment of the person at the workplace is not used to perform service work or office work unless the equipment is—\ninspected and tested by a competent person—\nif the equipment is used only for office work—at least once every 5 years; or\notherwise—at least once every year; or\nconnected to a safety switch.\na portable vacuum cleaner used in a hotel\na hand held blow dryer used in a hairdressing salon\na powerboard or extension lead used to supply power to office equipment\nIf, after inspecting and testing the equipment under subsection&#160;(1) (a) the competent person decides the equipment is safe to use, the person conducting the business or undertaking must ensure the competent person immediately attaches a durable tag to the equipment that states the prescribed details for the equipment.\nIf, after inspecting and testing the electrical equipment under subsection&#160;(1) (a) the competent person decides the equipment is not safe to use, the person conducting the business or undertaking must ensure—\nthe competent person immediately attaches a durable tag to the equipment that warns people not to use the equipment; and\nthe equipment is immediately withdrawn from use.\nThe person conducting the business or undertaking must ensure that, for the purposes of the business or undertaking, a tag is not attached to specified electrical equipment under subsection&#160;(2) unless—\nthe equipment is new; or\nboth of the following apply—\nthe equipment has been inspected and tested by a competent person;\nthe tag was attached by the competent person.\nSubsections&#160;(1) to (4) are linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n(sec.138-ssec.1) The person conducting the business or undertaking must ensure specified electrical equipment of the person at the workplace is not used to perform service work or office work unless the equipment is— inspected and tested by a competent person— if the equipment is used only for office work—at least once every 5 years; or otherwise—at least once every year; or connected to a safety switch. a portable vacuum cleaner used in a hotel a hand held blow dryer used in a hairdressing salon a powerboard or extension lead used to supply power to office equipment\n(sec.138-ssec.2) If, after inspecting and testing the equipment under subsection&#160;(1) (a) the competent person decides the equipment is safe to use, the person conducting the business or undertaking must ensure the competent person immediately attaches a durable tag to the equipment that states the prescribed details for the equipment.\n(sec.138-ssec.3) If, after inspecting and testing the electrical equipment under subsection&#160;(1) (a) the competent person decides the equipment is not safe to use, the person conducting the business or undertaking must ensure— the competent person immediately attaches a durable tag to the equipment that warns people not to use the equipment; and the equipment is immediately withdrawn from use.\n(sec.138-ssec.4) The person conducting the business or undertaking must ensure that, for the purposes of the business or undertaking, a tag is not attached to specified electrical equipment under subsection&#160;(2) unless— the equipment is new; or both of the following apply— the equipment has been inspected and tested by a competent person; the tag was attached by the competent person. Subsections&#160;(1) to (4) are linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n- (a) inspected and tested by a competent person— (i) if the equipment is used only for office work—at least once every 5 years; or (ii) otherwise—at least once every year; or\n- (i) if the equipment is used only for office work—at least once every 5 years; or\n- (ii) otherwise—at least once every year; or\n- (b) connected to a safety switch.\n- (i) if the equipment is used only for office work—at least once every 5 years; or\n- (ii) otherwise—at least once every year; or\n- • a portable vacuum cleaner used in a hotel\n- • a hand held blow dryer used in a hairdressing salon\n- (a) the competent person immediately attaches a durable tag to the equipment that warns people not to use the equipment; and\n- (b) the equipment is immediately withdrawn from use.\n- (a) the equipment is new; or\n- (b) both of the following apply— (i) the equipment has been inspected and tested by a competent person; (ii) the tag was attached by the competent person.\n- (i) the equipment has been inspected and tested by a competent person;\n- (ii) the tag was attached by the competent person.\n- (i) the equipment has been inspected and tested by a competent person;\n- (ii) the tag was attached by the competent person.","sortOrder":173},{"sectionNumber":"sec.139","sectionType":"section","heading":"Safety switches, including portable safety switches","content":"### sec.139 Safety switches, including portable safety switches\n\nThe person conducting the business or undertaking must not use, or allow to be used, a safety switch unless it complies with AS/NZS 3760 (In-service safety inspection and testing of electrical equipment and RCDs) when tested.\nThe person conducting the business or undertaking must ensure each safety switch, other than a portable safety switch, at the workplace—\nis tested by a competent person in accordance with AS/NZS 3760 immediately after it is connected; and\nis tested in accordance with, and at the intervals stated in, AS/NZS 3760.\nThe person conducting the business or undertaking must ensure each portable safety switch at the workplace—\nis tested by pushing the test button on the safety switch immediately after it is connected; and\nis tested in accordance with, and at the intervals stated in, AS/NZS 3760.\nIf a safety switch is not working properly, the person conducting the business or undertaking must ensure—\na durable tag is immediately attached to the safety switch that warns people not to use the safety switch; and\nthe safety switch is immediately withdrawn from use.\nSubsections&#160;(1) to (4) are linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n(sec.139-ssec.1) The person conducting the business or undertaking must not use, or allow to be used, a safety switch unless it complies with AS/NZS 3760 (In-service safety inspection and testing of electrical equipment and RCDs) when tested.\n(sec.139-ssec.2) The person conducting the business or undertaking must ensure each safety switch, other than a portable safety switch, at the workplace— is tested by a competent person in accordance with AS/NZS 3760 immediately after it is connected; and is tested in accordance with, and at the intervals stated in, AS/NZS 3760.\n(sec.139-ssec.3) The person conducting the business or undertaking must ensure each portable safety switch at the workplace— is tested by pushing the test button on the safety switch immediately after it is connected; and is tested in accordance with, and at the intervals stated in, AS/NZS 3760.\n(sec.139-ssec.4) If a safety switch is not working properly, the person conducting the business or undertaking must ensure— a durable tag is immediately attached to the safety switch that warns people not to use the safety switch; and the safety switch is immediately withdrawn from use. Subsections&#160;(1) to (4) are linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n- (a) is tested by a competent person in accordance with AS/NZS 3760 immediately after it is connected; and\n- (b) is tested in accordance with, and at the intervals stated in, AS/NZS 3760.\n- (a) is tested by pushing the test button on the safety switch immediately after it is connected; and\n- (b) is tested in accordance with, and at the intervals stated in, AS/NZS 3760.\n- (a) a durable tag is immediately attached to the safety switch that warns people not to use the safety switch; and\n- (b) the safety switch is immediately withdrawn from use.","sortOrder":174},{"sectionNumber":"pt.6-div.5","sectionType":"division","heading":"Requirements for particular industries","content":"## Requirements for particular industries","sortOrder":175},{"sectionNumber":"sec.140","sectionType":"section","heading":"Requirements for construction work","content":"### sec.140 Requirements for construction work\n\nThis section applies in relation to construction work performed at a workplace.\nA person conducting a business or undertaking must ensure all electrical equipment for the performance of construction work complies with the requirements of AS/NZS 3012 (Electrical installations—Construction and demolition sites).\nA person conducting a business or undertaking must ensure that, for the purposes of the business or undertaking, electrical equipment mentioned in AS/NZS 3012, clause 3.1 is not fitted with a tag that includes the test or retest date for the equipment unless—\nthe equipment is new; or\nboth of the following apply—\nthe equipment has been inspected and tested by a competent person and found to comply with the requirements of AS/NZS 3012;\nthe tag includes the day by which the equipment must be reinspected and retested and the information mentioned in subsection&#160;(4) .\nconstruction wiring, inverters, RCDs, switchboards, transportable structures\nFor subsection&#160;(3) (b) (ii) , the information is—\nif the individual who performed the test or retest is employed or engaged by a corporation—at least 1 of the following—\nthe name of the individual;\nthe individual’s electrical contractor licence number;\nthe name of the corporation;\nthe corporation’s electrical contractor licence number; or\nif paragraph&#160;(a) does not apply—at least 1 of the following details of the individual who performed the test or retest—\nthe name of the individual;\nthe individual’s electrical contractor licence number;\nthe electrical contractor licence number of the individual’s employer;\nthe individual’s electrical worker licence number.\nA person with management or control of the workplace must ensure all construction wiring at the workplace complies with the requirements of AS/NZS 3012.\nIn this section—\nconstruction wiring , at a workplace, means temporary electrical wiring by which electricity is supplied for use in, and for the period of, construction work, within the meaning of the WHS Regulation , section&#160;289 , at the workplace.\nSubsections&#160;(1) to (5) are linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n(sec.140-ssec.1) This section applies in relation to construction work performed at a workplace.\n(sec.140-ssec.2) A person conducting a business or undertaking must ensure all electrical equipment for the performance of construction work complies with the requirements of AS/NZS 3012 (Electrical installations—Construction and demolition sites).\n(sec.140-ssec.3) A person conducting a business or undertaking must ensure that, for the purposes of the business or undertaking, electrical equipment mentioned in AS/NZS 3012, clause 3.1 is not fitted with a tag that includes the test or retest date for the equipment unless— the equipment is new; or both of the following apply— the equipment has been inspected and tested by a competent person and found to comply with the requirements of AS/NZS 3012; the tag includes the day by which the equipment must be reinspected and retested and the information mentioned in subsection&#160;(4) . construction wiring, inverters, RCDs, switchboards, transportable structures\n(sec.140-ssec.4) For subsection&#160;(3) (b) (ii) , the information is— if the individual who performed the test or retest is employed or engaged by a corporation—at least 1 of the following— the name of the individual; the individual’s electrical contractor licence number; the name of the corporation; the corporation’s electrical contractor licence number; or if paragraph&#160;(a) does not apply—at least 1 of the following details of the individual who performed the test or retest— the name of the individual; the individual’s electrical contractor licence number; the electrical contractor licence number of the individual’s employer; the individual’s electrical worker licence number.\n(sec.140-ssec.5) A person with management or control of the workplace must ensure all construction wiring at the workplace complies with the requirements of AS/NZS 3012.\n(sec.140-ssec.6) In this section— construction wiring , at a workplace, means temporary electrical wiring by which electricity is supplied for use in, and for the period of, construction work, within the meaning of the WHS Regulation , section&#160;289 , at the workplace. Subsections&#160;(1) to (5) are linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n- (a) the equipment is new; or\n- (b) both of the following apply— (i) the equipment has been inspected and tested by a competent person and found to comply with the requirements of AS/NZS 3012; (ii) the tag includes the day by which the equipment must be reinspected and retested and the information mentioned in subsection&#160;(4) .\n- (i) the equipment has been inspected and tested by a competent person and found to comply with the requirements of AS/NZS 3012;\n- (ii) the tag includes the day by which the equipment must be reinspected and retested and the information mentioned in subsection&#160;(4) .\n- (i) the equipment has been inspected and tested by a competent person and found to comply with the requirements of AS/NZS 3012;\n- (ii) the tag includes the day by which the equipment must be reinspected and retested and the information mentioned in subsection&#160;(4) .\n- (a) if the individual who performed the test or retest is employed or engaged by a corporation—at least 1 of the following— (i) the name of the individual; (ii) the individual’s electrical contractor licence number; (iii) the name of the corporation; (iv) the corporation’s electrical contractor licence number; or\n- (i) the name of the individual;\n- (ii) the individual’s electrical contractor licence number;\n- (iii) the name of the corporation;\n- (iv) the corporation’s electrical contractor licence number; or\n- (b) if paragraph&#160;(a) does not apply—at least 1 of the following details of the individual who performed the test or retest— (i) the name of the individual; (ii) the individual’s electrical contractor licence number; (iii) the electrical contractor licence number of the individual’s employer; (iv) the individual’s electrical worker licence number.\n- (i) the name of the individual;\n- (ii) the individual’s electrical contractor licence number;\n- (iii) the electrical contractor licence number of the individual’s employer;\n- (iv) the individual’s electrical worker licence number.\n- (i) the name of the individual;\n- (ii) the individual’s electrical contractor licence number;\n- (iii) the name of the corporation;\n- (iv) the corporation’s electrical contractor licence number; or\n- (i) the name of the individual;\n- (ii) the individual’s electrical contractor licence number;\n- (iii) the electrical contractor licence number of the individual’s employer;\n- (iv) the individual’s electrical worker licence number.","sortOrder":176},{"sectionNumber":"sec.141","sectionType":"section","heading":"Requirements for rural industry work","content":"### sec.141 Requirements for rural industry work\n\nThis section applies to a person conducting a business or undertaking that involves rural industry work performed at a workplace.\nThe person conducting the business or undertaking must ensure—\nspecified electrical equipment used by the person is visually inspected for electrical safety defects before it is connected to a socket-outlet; and\nif rural industry work is proposed to be performed, the proposed work is assessed to decide whether it involves a stated electrical risk factor; and\nif proposed rural industry work involves a stated electrical risk factor, control measures are implemented to prevent the electrical risk from the stated electrical risk factor; and\nif specified electrical equipment is used by the person that involves a stated electrical risk factor, the equipment—\nis connected to a safety switch; or\nis inspected and tested at least annually by a competent person and complies with AS/NZS 3760 (In-service safety inspection and testing of electrical equipment and RCDs) when tested; and\ncontrol measures are implemented for the risk of electric shock or burns from electrical welding work performed in the business or undertaking, including the wearing of protective clothing, gloves and footwear.\nIf, after inspecting and testing the equipment under subsection&#160;(2) (d) (ii) the competent person decides the equipment is safe to use, the person conducting the business or undertaking must ensure the competent person immediately attaches a durable tag to the equipment that states the prescribed details.\nIf, after inspecting and testing the equipment under subsection&#160;(2) (d) (ii) the competent person decides the equipment is not safe to use, the person conducting the business or undertaking must ensure—\nthe competent person immediately attaches a durable tag to the equipment that warns people not to use the equipment; and\nthe equipment is immediately withdrawn from use.\nThe person conducting the business or undertaking must ensure that, for the purposes of the business or undertaking, a tag is not attached to specified electrical equipment under subsection&#160;(2) unless—\nthe equipment is new; or\nboth of the following apply—\nthe equipment has been inspected and tested by a competent person;\nthe tag was attached by the competent person.\nIn this section—\npersonally supported electrical equipment includes hand held, or carried, electrical equipment, including, for example, a backpack-type vacuum cleaner.\nstated electrical risk factor means any of the following—\nuse of plug-in electrical equipment in an unroofed area or wet area, including, for example, a hose down area;\nuse of personally supported electrical equipment if the electrical supply cord is subject to flexing while the equipment is being used;\nuse of plug-in electrical equipment that is exposed to environmental factors that subject the equipment to abnormal wear or deterioration.\ncorrosive or other damaging dusts\ncorrosive chemicals in the air\nSubsections&#160;(1) to (5) are linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n(sec.141-ssec.1) This section applies to a person conducting a business or undertaking that involves rural industry work performed at a workplace.\n(sec.141-ssec.2) The person conducting the business or undertaking must ensure— specified electrical equipment used by the person is visually inspected for electrical safety defects before it is connected to a socket-outlet; and if rural industry work is proposed to be performed, the proposed work is assessed to decide whether it involves a stated electrical risk factor; and if proposed rural industry work involves a stated electrical risk factor, control measures are implemented to prevent the electrical risk from the stated electrical risk factor; and if specified electrical equipment is used by the person that involves a stated electrical risk factor, the equipment— is connected to a safety switch; or is inspected and tested at least annually by a competent person and complies with AS/NZS 3760 (In-service safety inspection and testing of electrical equipment and RCDs) when tested; and control measures are implemented for the risk of electric shock or burns from electrical welding work performed in the business or undertaking, including the wearing of protective clothing, gloves and footwear.\n(sec.141-ssec.3) If, after inspecting and testing the equipment under subsection&#160;(2) (d) (ii) the competent person decides the equipment is safe to use, the person conducting the business or undertaking must ensure the competent person immediately attaches a durable tag to the equipment that states the prescribed details.\n(sec.141-ssec.4) If, after inspecting and testing the equipment under subsection&#160;(2) (d) (ii) the competent person decides the equipment is not safe to use, the person conducting the business or undertaking must ensure— the competent person immediately attaches a durable tag to the equipment that warns people not to use the equipment; and the equipment is immediately withdrawn from use.\n(sec.141-ssec.5) The person conducting the business or undertaking must ensure that, for the purposes of the business or undertaking, a tag is not attached to specified electrical equipment under subsection&#160;(2) unless— the equipment is new; or both of the following apply— the equipment has been inspected and tested by a competent person; the tag was attached by the competent person.\n(sec.141-ssec.6) In this section— personally supported electrical equipment includes hand held, or carried, electrical equipment, including, for example, a backpack-type vacuum cleaner. stated electrical risk factor means any of the following— use of plug-in electrical equipment in an unroofed area or wet area, including, for example, a hose down area; use of personally supported electrical equipment if the electrical supply cord is subject to flexing while the equipment is being used; use of plug-in electrical equipment that is exposed to environmental factors that subject the equipment to abnormal wear or deterioration. corrosive or other damaging dusts corrosive chemicals in the air Subsections&#160;(1) to (5) are linked to the electrical safety duty in section&#160;30 of the Act (see section&#160;7 (1) ).\n- (a) specified electrical equipment used by the person is visually inspected for electrical safety defects before it is connected to a socket-outlet; and\n- (b) if rural industry work is proposed to be performed, the proposed work is assessed to decide whether it involves a stated electrical risk factor; and\n- (c) if proposed rural industry work involves a stated electrical risk factor, control measures are implemented to prevent the electrical risk from the stated electrical risk factor; and\n- (d) if specified electrical equipment is used by the person that involves a stated electrical risk factor, the equipment— (i) is connected to a safety switch; or (ii) is inspected and tested at least annually by a competent person and complies with AS/NZS 3760 (In-service safety inspection and testing of electrical equipment and RCDs) when tested; and\n- (i) is connected to a safety switch; or\n- (ii) is inspected and tested at least annually by a competent person and complies with AS/NZS 3760 (In-service safety inspection and testing of electrical equipment and RCDs) when tested; and\n- (e) control measures are implemented for the risk of electric shock or burns from electrical welding work performed in the business or undertaking, including the wearing of protective clothing, gloves and footwear.\n- (i) is connected to a safety switch; or\n- (ii) is inspected and tested at least annually by a competent person and complies with AS/NZS 3760 (In-service safety inspection and testing of electrical equipment and RCDs) when tested; and\n- (a) the competent person immediately attaches a durable tag to the equipment that warns people not to use the equipment; and\n- (b) the equipment is immediately withdrawn from use.\n- (a) the equipment is new; or\n- (b) both of the following apply— (i) the equipment has been inspected and tested by a competent person; (ii) the tag was attached by the competent person.\n- (i) the equipment has been inspected and tested by a competent person;\n- (ii) the tag was attached by the competent person.\n- (i) the equipment has been inspected and tested by a competent person;\n- (ii) the tag was attached by the competent person.\n- (a) use of plug-in electrical equipment in an unroofed area or wet area, including, for example, a hose down area;\n- (b) use of personally supported electrical equipment if the electrical supply cord is subject to flexing while the equipment is being used;\n- (c) use of plug-in electrical equipment that is exposed to environmental factors that subject the equipment to abnormal wear or deterioration. Examples of environmental factors that subject equipment to abnormal wear or deterioration— • corrosive or other damaging dusts • corrosive chemicals in the air\n- • corrosive or other damaging dusts\n- • corrosive chemicals in the air\n- • corrosive or other damaging dusts\n- • corrosive chemicals in the air","sortOrder":177},{"sectionNumber":"sec.142","sectionType":"section","heading":"Requirements for hiring out electrical equipment","content":"### sec.142 Requirements for hiring out electrical equipment\n\nThis section applies to a person (the hirer ) conducting a business or undertaking that involves hiring out electrical equipment to other persons.\nThe hirer must ensure each item of electrical equipment hired out by the hirer to another person—\neither—\nis inspected and tested by a competent person before each hiring; or\nhas a safety switch that can not be disconnected, deactivated or removed during the item’s operation; and\nis inspected, tested and tagged by a competent person at least once every 6 months; and\nif the item has a safety switch mentioned in paragraph&#160;(a) (ii) , the safety switch—\nis inspected, tested and tagged by a competent person at least once every 6 months; and\ncomplies with AS/NZS 3760 (In-service safety inspection and testing of electrical equipment and RCDs) when tested.\nHowever, subsection&#160;(2) (b) does not apply if the item is domestic electrical equipment hired for use in a domestic situation.\nrefrigerator, television or computer hired for use in a house, flat or unit\nrefrigerator hired for use in a mechanic’s workshop\nFor subsection&#160;(2) (a) (i) , if, because of the way in which the item of electrical equipment is designed, the item can not be tested without dismantling it, it is sufficient if the hirer ensures the item is tested to the extent it can be tested without dismantling it.\nIf, after inspecting and testing an item of electrical equipment under subsection&#160;(2) (b) the competent person decides the item is safe to use, the hirer must ensure the competent person immediately attaches a durable tag to the item that states the day by which the item must be reinspected and retested.\nIf, after inspecting and testing an item of electrical equipment under subsection&#160;(2) (b) the competent person decides the item is not safe to use, the hirer must ensure—\nthe competent person immediately attaches a durable tag to the item warning people not to use the item; and\nthe item is immediately withdrawn from use.\nThe hirer must keep records of the tests performed under subsection&#160;(2) (b) or (c) (i) for at least 5 years.\nA person who contravenes subsection&#160;(2) , (5) , (6) or (7) commits an offence.\nMaximum penalty—40 penalty units.\nIn this section—\ndomestic electrical equipment means computer equipment, browngoods or whitegoods.\n(sec.142-ssec.1) This section applies to a person (the hirer ) conducting a business or undertaking that involves hiring out electrical equipment to other persons.\n(sec.142-ssec.2) The hirer must ensure each item of electrical equipment hired out by the hirer to another person— either— is inspected and tested by a competent person before each hiring; or has a safety switch that can not be disconnected, deactivated or removed during the item’s operation; and is inspected, tested and tagged by a competent person at least once every 6 months; and if the item has a safety switch mentioned in paragraph&#160;(a) (ii) , the safety switch— is inspected, tested and tagged by a competent person at least once every 6 months; and complies with AS/NZS 3760 (In-service safety inspection and testing of electrical equipment and RCDs) when tested.\n(sec.142-ssec.3) However, subsection&#160;(2) (b) does not apply if the item is domestic electrical equipment hired for use in a domestic situation. refrigerator, television or computer hired for use in a house, flat or unit refrigerator hired for use in a mechanic’s workshop\n(sec.142-ssec.4) For subsection&#160;(2) (a) (i) , if, because of the way in which the item of electrical equipment is designed, the item can not be tested without dismantling it, it is sufficient if the hirer ensures the item is tested to the extent it can be tested without dismantling it.\n(sec.142-ssec.5) If, after inspecting and testing an item of electrical equipment under subsection&#160;(2) (b) the competent person decides the item is safe to use, the hirer must ensure the competent person immediately attaches a durable tag to the item that states the day by which the item must be reinspected and retested.\n(sec.142-ssec.6) If, after inspecting and testing an item of electrical equipment under subsection&#160;(2) (b) the competent person decides the item is not safe to use, the hirer must ensure— the competent person immediately attaches a durable tag to the item warning people not to use the item; and the item is immediately withdrawn from use.\n(sec.142-ssec.7) The hirer must keep records of the tests performed under subsection&#160;(2) (b) or (c) (i) for at least 5 years.\n(sec.142-ssec.8) A person who contravenes subsection&#160;(2) , (5) , (6) or (7) commits an offence. Maximum penalty—40 penalty units.\n(sec.142-ssec.9) In this section— domestic electrical equipment means computer equipment, browngoods or whitegoods.\n- (a) either— (i) is inspected and tested by a competent person before each hiring; or (ii) has a safety switch that can not be disconnected, deactivated or removed during the item’s operation; and\n- (i) is inspected and tested by a competent person before each hiring; or\n- (ii) has a safety switch that can not be disconnected, deactivated or removed during the item’s operation; and\n- (b) is inspected, tested and tagged by a competent person at least once every 6 months; and\n- (c) if the item has a safety switch mentioned in paragraph&#160;(a) (ii) , the safety switch— (i) is inspected, tested and tagged by a competent person at least once every 6 months; and (ii) complies with AS/NZS 3760 (In-service safety inspection and testing of electrical equipment and RCDs) when tested.\n- (i) is inspected, tested and tagged by a competent person at least once every 6 months; and\n- (ii) complies with AS/NZS 3760 (In-service safety inspection and testing of electrical equipment and RCDs) when tested.\n- (i) is inspected and tested by a competent person before each hiring; or\n- (ii) has a safety switch that can not be disconnected, deactivated or removed during the item’s operation; and\n- (i) is inspected, tested and tagged by a competent person at least once every 6 months; and\n- (ii) complies with AS/NZS 3760 (In-service safety inspection and testing of electrical equipment and RCDs) when tested.\n- (a) the competent person immediately attaches a durable tag to the item warning people not to use the item; and\n- (b) the item is immediately withdrawn from use.","sortOrder":178},{"sectionNumber":"pt.7","sectionType":"part","heading":"Licensing","content":"# Licensing","sortOrder":179},{"sectionNumber":"pt.7-div.1","sectionType":"division","heading":"Preliminary","content":"## Preliminary","sortOrder":180},{"sectionNumber":"sec.143","sectionType":"section","heading":"Definitions for part","content":"### sec.143 Definitions for part\n\nIn this part—\nqualified business person , for an applicant for an electrical contractor licence or for a licensed electrical contractor, means a person the regulator has endorsed as a qualified business person under section&#160;163 (1) .\nqualified technical person , for an applicant for an electrical contractor licence or for a licensed electrical contractor, means a person the regulator has endorsed as a qualified technical person under section&#160;164 (1) .","sortOrder":181},{"sectionNumber":"pt.7-div.2","sectionType":"division","heading":"Electrical work licence authorisation","content":"## Electrical work licence authorisation","sortOrder":182},{"sectionNumber":"sec.144","sectionType":"section","heading":"Electrical work licences that may be issued","content":"### sec.144 Electrical work licences that may be issued\n\nThe following classes of electrical work licences may be issued—\nelectrical mechanic licence;\nelectrical linesperson licence;\nelectrical fitter licence;\nelectrical jointer licence;\nrestricted electrical work licence;\nelectrical work training permit.\n- (a) electrical mechanic licence;\n- (b) electrical linesperson licence;\n- (c) electrical fitter licence;\n- (d) electrical jointer licence;\n- (e) restricted electrical work licence;\n- (f) electrical work training permit.","sortOrder":183},{"sectionNumber":"sec.145","sectionType":"section","heading":"Division does not authorise contravention of conditions or restrictions on licence","content":"### sec.145 Division does not authorise contravention of conditions or restrictions on licence\n\nThis division does not authorise a holder of an electrical work licence to contravene a condition or restriction included in the licence.\nFor the inclusion of conditions or restrictions in electrical licences, see section&#160;63 of the Act .\nFor the penalty for contravening a condition or restriction included in an electrical licence, see section&#160;57 of the Act .\n- 1 For the inclusion of conditions or restrictions in electrical licences, see section&#160;63 of the Act .\n- 2 For the penalty for contravening a condition or restriction included in an electrical licence, see section&#160;57 of the Act .","sortOrder":184},{"sectionNumber":"sec.146","sectionType":"section","heading":"What electrical mechanic licence authorises","content":"### sec.146 What electrical mechanic licence authorises\n\nAn electrical mechanic licence authorises the holder to perform all electrical work.\ninstalling or changing an electrical installation or electric line\nmaintaining, repairing, or connecting to a source of electricity, an item of electrical equipment\n- • installing or changing an electrical installation or electric line\n- • maintaining, repairing, or connecting to a source of electricity, an item of electrical equipment","sortOrder":185},{"sectionNumber":"sec.147","sectionType":"section","heading":"What electrical linesperson licence authorises","content":"### sec.147 What electrical linesperson licence authorises\n\nAn electrical linesperson licence authorises the holder to perform all electric line work.\nelectrical work in the building or maintenance of an overhead electric line\nelectrical work in the building or maintenance of street lighting connected to an overhead or underground electric line\ntests to ensure overhead electric lines are correctly connected\n- • electrical work in the building or maintenance of an overhead electric line\n- • electrical work in the building or maintenance of street lighting connected to an overhead or underground electric line\n- • tests to ensure overhead electric lines are correctly connected","sortOrder":186},{"sectionNumber":"sec.148","sectionType":"section","heading":"What electrical fitter licence authorises","content":"### sec.148 What electrical fitter licence authorises\n\nAn electrical fitter licence authorises the holder to perform all electrical equipment work.\nelectrical work, whether in a workshop or on site, of building, manufacturing, fitting, assembling, erecting, operating, testing or repairing electrical equipment\n- • electrical work, whether in a workshop or on site, of building, manufacturing, fitting, assembling, erecting, operating, testing or repairing electrical equipment","sortOrder":187},{"sectionNumber":"sec.149","sectionType":"section","heading":"What electrical jointer licence authorises","content":"### sec.149 What electrical jointer licence authorises\n\nAn electrical jointer licence authorises the holder to perform the following electrical work—\ninstalling, jointing and terminating cables to the extent the work requires specialised knowledge or skill;\nelectrical equipment work necessary for the work mentioned in paragraph&#160;(a) .\n- (a) installing, jointing and terminating cables to the extent the work requires specialised knowledge or skill;\n- (b) electrical equipment work necessary for the work mentioned in paragraph&#160;(a) .","sortOrder":188},{"sectionNumber":"sec.150","sectionType":"section","heading":"What restricted electrical work licence authorises","content":"### sec.150 What restricted electrical work licence authorises\n\nA restricted electrical work licence authorises the holder to perform electrical work of the particular type stated in the licence.\nA restricted electrical work licence may restrict the holder to the performance of electrical work incidental or special to a particular calling.","sortOrder":189},{"sectionNumber":"sec.151","sectionType":"section","heading":"What electrical work training permit authorises","content":"### sec.151 What electrical work training permit authorises\n\nAn electrical work training permit authorises the holder to perform the electrical work stated in the permit in accordance with the conditions about training stated in the permit.","sortOrder":190},{"sectionNumber":"pt.7-div.3","sectionType":"division","heading":"Requirements for issue of electrical work licences","content":"## Requirements for issue of electrical work licences","sortOrder":191},{"sectionNumber":"sec.152","sectionType":"section","heading":"Definitions for division","content":"### sec.152 Definitions for division\n\nIn this division—\ncorresponding training department means a department of another State in which a law that corresponds to, or substantially corresponds to, the Further Education and Training Act 2014 is administered.\nrelevant assessing authority means a relevant assessing authority under the Migration Regulations 1994 (Cwlth) .\nrelevant employer , in relation to an applicant for an electrical work licence, means—\nthe applicant’s current employer; or\na former employer of the applicant who has relevant knowledge of the applicant’s training and competency to perform electrical work.\ntraining plan , for an apprentice or trainee, see the Further Education and Training Act 2014 , schedule&#160;1 .\n- (a) the applicant’s current employer; or\n- (b) a former employer of the applicant who has relevant knowledge of the applicant’s training and competency to perform electrical work.","sortOrder":192},{"sectionNumber":"sec.153","sectionType":"section","heading":"Application of subdivision— Act , s&#160;59","content":"### sec.153 Application of subdivision— Act , s&#160;59\n\nThis subdivision prescribes, for section&#160;59 (4) of the Act , eligibility requirements that apply to an applicant for the issue of any of the following licences—\nan electrical mechanic licence;\nan electrical linesperson licence;\nan electrical fitter licence;\nan electrical jointer licence;\na restricted electrical work licence.\n- (a) an electrical mechanic licence;\n- (b) an electrical linesperson licence;\n- (c) an electrical fitter licence;\n- (d) an electrical jointer licence;\n- (e) a restricted electrical work licence.","sortOrder":193},{"sectionNumber":"sec.154","sectionType":"section","heading":"English language requirements","content":"### sec.154 English language requirements\n\nThe regulator must be satisfied the applicant is able to understand, and read and write in, the English language without the aid of an interpreter.","sortOrder":194},{"sectionNumber":"sec.155","sectionType":"section","heading":"Training requirements","content":"### sec.155 Training requirements\n\nThe regulator must be satisfied the applicant has been trained in, and is competent to carry out, resuscitation on an individual who has stopped breathing or is unconscious because of electric shock.\nAlso, if the licence applied for is an electrical linesperson licence, the regulator must be satisfied the applicant has been trained in, and is competent to carry out, the rescue of an individual from a pole top or transmission tower.\nHowever, subsection&#160;(1) or (2) does not prevent the issue of the electrical work licence if the regulator is satisfied—\nthe applicant has a medical condition that—\nprevents the applicant carrying out the relevant activity for the subsection; but\ndoes not otherwise affect the applicant’s ability to perform electrical work under the licence; and\nin the particular circumstances, it is reasonable to allow the applicant to carry out electrical work subject to a condition that the applicant must not act in a role for which it is a requirement that the applicant be competent in the relevant activity.\na safety observer\nIn this section—\nrelevant activity means—\nin relation to subsection&#160;(1) —resuscitation; or\nin relation to subsection&#160;(2) —the rescue of an individual from a pole top or transmission tower.\n(sec.155-ssec.1) The regulator must be satisfied the applicant has been trained in, and is competent to carry out, resuscitation on an individual who has stopped breathing or is unconscious because of electric shock.\n(sec.155-ssec.2) Also, if the licence applied for is an electrical linesperson licence, the regulator must be satisfied the applicant has been trained in, and is competent to carry out, the rescue of an individual from a pole top or transmission tower.\n(sec.155-ssec.3) However, subsection&#160;(1) or (2) does not prevent the issue of the electrical work licence if the regulator is satisfied— the applicant has a medical condition that— prevents the applicant carrying out the relevant activity for the subsection; but does not otherwise affect the applicant’s ability to perform electrical work under the licence; and in the particular circumstances, it is reasonable to allow the applicant to carry out electrical work subject to a condition that the applicant must not act in a role for which it is a requirement that the applicant be competent in the relevant activity. a safety observer\n(sec.155-ssec.4) In this section— relevant activity means— in relation to subsection&#160;(1) —resuscitation; or in relation to subsection&#160;(2) —the rescue of an individual from a pole top or transmission tower.\n- (a) the applicant has a medical condition that— (i) prevents the applicant carrying out the relevant activity for the subsection; but (ii) does not otherwise affect the applicant’s ability to perform electrical work under the licence; and\n- (i) prevents the applicant carrying out the relevant activity for the subsection; but\n- (ii) does not otherwise affect the applicant’s ability to perform electrical work under the licence; and\n- (b) in the particular circumstances, it is reasonable to allow the applicant to carry out electrical work subject to a condition that the applicant must not act in a role for which it is a requirement that the applicant be competent in the relevant activity. Example of a role mentioned in paragraph&#160;(b) — a safety observer\n- (i) prevents the applicant carrying out the relevant activity for the subsection; but\n- (ii) does not otherwise affect the applicant’s ability to perform electrical work under the licence; and\n- (a) in relation to subsection&#160;(1) —resuscitation; or\n- (b) in relation to subsection&#160;(2) —the rescue of an individual from a pole top or transmission tower.","sortOrder":195},{"sectionNumber":"sec.156","sectionType":"section","heading":"No outstanding disciplinary matters","content":"### sec.156 No outstanding disciplinary matters\n\nThe regulator must be satisfied the applicant does not have an outstanding disciplinary matter.\nWithout limiting the matters the regulator may consider under subsection&#160;(1) , the regulator may consider the applicant’s activities as a licensed electrical worker, whether before or after the commencement of this section, including the following—\ndisciplinary action taken against the applicant under a law regulating the activities of licensed electrical workers;\nnon-performance of a duty by the applicant under a law about electrical work and the reasons for the non-performance;\nremedial action taken by the applicant to address an activity mentioned in paragraph&#160;(a) or (b) .\n(sec.156-ssec.1) The regulator must be satisfied the applicant does not have an outstanding disciplinary matter.\n(sec.156-ssec.2) Without limiting the matters the regulator may consider under subsection&#160;(1) , the regulator may consider the applicant’s activities as a licensed electrical worker, whether before or after the commencement of this section, including the following— disciplinary action taken against the applicant under a law regulating the activities of licensed electrical workers; non-performance of a duty by the applicant under a law about electrical work and the reasons for the non-performance; remedial action taken by the applicant to address an activity mentioned in paragraph&#160;(a) or (b) .\n- (a) disciplinary action taken against the applicant under a law regulating the activities of licensed electrical workers;\n- (b) non-performance of a duty by the applicant under a law about electrical work and the reasons for the non-performance;\n- (c) remedial action taken by the applicant to address an activity mentioned in paragraph&#160;(a) or (b) .","sortOrder":196},{"sectionNumber":"sec.157","sectionType":"section","heading":"Technical requirements (other than for restricted electrical work licence)","content":"### sec.157 Technical requirements (other than for restricted electrical work licence)\n\nThis section does not apply in relation to a restricted electrical work licence.\nThe applicant must comply with the eligibility requirements stated in subsection&#160;(3) , (4) or (5) .\nIf the applicant has finished an apprenticeship under the Further Education and Training Act 2014 to achieve competence in the relevant electrical work, the applicant must have—\nsatisfactorily finished the apprenticeship; and\nsatisfactorily finished a course of instruction chosen by the regulator; and\ngiven the regulator a written statement—\nfrom a relevant employer verifying that the applicant has satisfactorily finished the training to be delivered under the training plan for the apprenticeship; and\nfrom the issuing RTO for the apprenticeship verifying that the applicant is competent in the relevant electrical work; and\nsatisfied the regulator the applicant is competent in the relevant electrical work.\nIf the applicant has finished an apprenticeship outside Queensland to achieve competence in the relevant electrical work, the applicant must have—\nsatisfactorily finished the apprenticeship that is, in the regulator’s opinion, at least equivalent to an apprenticeship mentioned in subsection&#160;(3) ; and\nsatisfactorily finished a course of instruction related to the apprenticeship that is, in the regulator’s opinion, at least equivalent to the course of instruction mentioned in subsection&#160;(3) (b) ; and\ngiven the regulator a written statement—\nfrom a relevant employer verifying that the applicant has satisfactorily finished the training to be delivered under the apprenticeship; and\nfrom the non-Queensland training organisation for the apprenticeship verifying that the applicant is competent in the relevant electrical work; and\nsatisfied the regulator the applicant is competent in the relevant electrical work.\nThe applicant must have satisfied the regulator that—\nthe applicant—\nholds a prescribed current licence; or\nwas the holder of a prescribed expired licence; or\nhas served an apprenticeship mentioned in subsection&#160;(3) , but has not satisfactorily finished the course of instruction mentioned in subsection&#160;(3) (b) ; or\nholds a certificate or other document issued by a relevant assessing authority stating that the applicant’s skills are suitable for carrying out the relevant electrical work; and\nthe applicant has complied with the regulator’s examination requirements; and\nthe applicant is competent in the relevant electrical work.\nIf an applicant can not comply with the requirement under subsection&#160;(3) (c) (i) or (4) (c) (i) (the employer statement requirement ), but otherwise complies with subsection&#160;(3) or (4) , the applicant is taken to have complied with the employer statement requirement if the applicant satisfies the regulator the applicant has satisfactorily finished the training mentioned in the requirement.\nIn this section—\nissuing RTO , in relation to an applicant who has finished an apprenticeship under the Further Education and Training Act 2014 , means the registered training organisation that issued a qualification or statement of attainment for training delivered to the applicant under the apprenticeship.\nnon-Queensland training organisation , in relation to an applicant who has finished an apprenticeship outside Queensland, means the registered training organisation, or training organisation outside of Australia, that issued a qualification or statement of attainment for training delivered to the applicant under the apprenticeship.\nprescribed current licence means—\nfor an applicant for an electrical mechanic licence—a current electrical fitter licence; or\nfor an applicant for an electrical linesperson licence, electrical fitter licence or electrical jointer licence—a current electrical mechanic licence.\nprescribed expired licence means—\nfor an applicant for an electrical mechanic licence—an electrical mechanic licence issued under the Act that has expired; or\nfor an applicant for an electrical linesperson licence—an electrical linesperson licence issued under the Act that has expired; or\nfor an applicant for an electrical fitter licence—an electrical fitter licence issued under the Act that has expired; or\nfor an applicant for an electrical jointer licence—an electrical jointer licence issued under the Act that has expired.\nrelevant electrical work , for an applicant for an electrical work licence, means—\nif the licence is an electrical mechanic licence—electrical work of an electrical mechanic; or\nif the licence is an electrical linesperson licence—electrical work of an electrical linesperson; or\nif the licence is an electrical fitter licence—electrical work of an electrical fitter; or\nif the licence is an electrical jointer licence—electrical work of an electrical jointer.\nstatement of attainment means—\na VET statement of attainment under the National Vocational Education and Training Regulator Act 2011 (Cwlth) ; or\na statement given to a person by a training organisation outside of Australia confirming that the person has satisfied the requirements of units of competency or modules stated in the statement.\n(sec.157-ssec.1) This section does not apply in relation to a restricted electrical work licence.\n(sec.157-ssec.2) The applicant must comply with the eligibility requirements stated in subsection&#160;(3) , (4) or (5) .\n(sec.157-ssec.3) If the applicant has finished an apprenticeship under the Further Education and Training Act 2014 to achieve competence in the relevant electrical work, the applicant must have— satisfactorily finished the apprenticeship; and satisfactorily finished a course of instruction chosen by the regulator; and given the regulator a written statement— from a relevant employer verifying that the applicant has satisfactorily finished the training to be delivered under the training plan for the apprenticeship; and from the issuing RTO for the apprenticeship verifying that the applicant is competent in the relevant electrical work; and satisfied the regulator the applicant is competent in the relevant electrical work.\n(sec.157-ssec.4) If the applicant has finished an apprenticeship outside Queensland to achieve competence in the relevant electrical work, the applicant must have— satisfactorily finished the apprenticeship that is, in the regulator’s opinion, at least equivalent to an apprenticeship mentioned in subsection&#160;(3) ; and satisfactorily finished a course of instruction related to the apprenticeship that is, in the regulator’s opinion, at least equivalent to the course of instruction mentioned in subsection&#160;(3) (b) ; and given the regulator a written statement— from a relevant employer verifying that the applicant has satisfactorily finished the training to be delivered under the apprenticeship; and from the non-Queensland training organisation for the apprenticeship verifying that the applicant is competent in the relevant electrical work; and satisfied the regulator the applicant is competent in the relevant electrical work.\n(sec.157-ssec.5) The applicant must have satisfied the regulator that— the applicant— holds a prescribed current licence; or was the holder of a prescribed expired licence; or has served an apprenticeship mentioned in subsection&#160;(3) , but has not satisfactorily finished the course of instruction mentioned in subsection&#160;(3) (b) ; or holds a certificate or other document issued by a relevant assessing authority stating that the applicant’s skills are suitable for carrying out the relevant electrical work; and the applicant has complied with the regulator’s examination requirements; and the applicant is competent in the relevant electrical work.\n(sec.157-ssec.6) If an applicant can not comply with the requirement under subsection&#160;(3) (c) (i) or (4) (c) (i) (the employer statement requirement ), but otherwise complies with subsection&#160;(3) or (4) , the applicant is taken to have complied with the employer statement requirement if the applicant satisfies the regulator the applicant has satisfactorily finished the training mentioned in the requirement.\n(sec.157-ssec.7) In this section— issuing RTO , in relation to an applicant who has finished an apprenticeship under the Further Education and Training Act 2014 , means the registered training organisation that issued a qualification or statement of attainment for training delivered to the applicant under the apprenticeship. non-Queensland training organisation , in relation to an applicant who has finished an apprenticeship outside Queensland, means the registered training organisation, or training organisation outside of Australia, that issued a qualification or statement of attainment for training delivered to the applicant under the apprenticeship. prescribed current licence means— for an applicant for an electrical mechanic licence—a current electrical fitter licence; or for an applicant for an electrical linesperson licence, electrical fitter licence or electrical jointer licence—a current electrical mechanic licence. prescribed expired licence means— for an applicant for an electrical mechanic licence—an electrical mechanic licence issued under the Act that has expired; or for an applicant for an electrical linesperson licence—an electrical linesperson licence issued under the Act that has expired; or for an applicant for an electrical fitter licence—an electrical fitter licence issued under the Act that has expired; or for an applicant for an electrical jointer licence—an electrical jointer licence issued under the Act that has expired. relevant electrical work , for an applicant for an electrical work licence, means— if the licence is an electrical mechanic licence—electrical work of an electrical mechanic; or if the licence is an electrical linesperson licence—electrical work of an electrical linesperson; or if the licence is an electrical fitter licence—electrical work of an electrical fitter; or if the licence is an electrical jointer licence—electrical work of an electrical jointer. statement of attainment means— a VET statement of attainment under the National Vocational Education and Training Regulator Act 2011 (Cwlth) ; or a statement given to a person by a training organisation outside of Australia confirming that the person has satisfied the requirements of units of competency or modules stated in the statement.\n- (a) satisfactorily finished the apprenticeship; and\n- (b) satisfactorily finished a course of instruction chosen by the regulator; and\n- (c) given the regulator a written statement— (i) from a relevant employer verifying that the applicant has satisfactorily finished the training to be delivered under the training plan for the apprenticeship; and (ii) from the issuing RTO for the apprenticeship verifying that the applicant is competent in the relevant electrical work; and\n- (i) from a relevant employer verifying that the applicant has satisfactorily finished the training to be delivered under the training plan for the apprenticeship; and\n- (ii) from the issuing RTO for the apprenticeship verifying that the applicant is competent in the relevant electrical work; and\n- (d) satisfied the regulator the applicant is competent in the relevant electrical work.\n- (i) from a relevant employer verifying that the applicant has satisfactorily finished the training to be delivered under the training plan for the apprenticeship; and\n- (ii) from the issuing RTO for the apprenticeship verifying that the applicant is competent in the relevant electrical work; and\n- (a) satisfactorily finished the apprenticeship that is, in the regulator’s opinion, at least equivalent to an apprenticeship mentioned in subsection&#160;(3) ; and\n- (b) satisfactorily finished a course of instruction related to the apprenticeship that is, in the regulator’s opinion, at least equivalent to the course of instruction mentioned in subsection&#160;(3) (b) ; and\n- (c) given the regulator a written statement— (i) from a relevant employer verifying that the applicant has satisfactorily finished the training to be delivered under the apprenticeship; and (ii) from the non-Queensland training organisation for the apprenticeship verifying that the applicant is competent in the relevant electrical work; and\n- (i) from a relevant employer verifying that the applicant has satisfactorily finished the training to be delivered under the apprenticeship; and\n- (ii) from the non-Queensland training organisation for the apprenticeship verifying that the applicant is competent in the relevant electrical work; and\n- (d) satisfied the regulator the applicant is competent in the relevant electrical work.\n- (i) from a relevant employer verifying that the applicant has satisfactorily finished the training to be delivered under the apprenticeship; and\n- (ii) from the non-Queensland training organisation for the apprenticeship verifying that the applicant is competent in the relevant electrical work; and\n- (a) the applicant— (i) holds a prescribed current licence; or (ii) was the holder of a prescribed expired licence; or (iii) has served an apprenticeship mentioned in subsection&#160;(3) , but has not satisfactorily finished the course of instruction mentioned in subsection&#160;(3) (b) ; or (iv) holds a certificate or other document issued by a relevant assessing authority stating that the applicant’s skills are suitable for carrying out the relevant electrical work; and\n- (i) holds a prescribed current licence; or\n- (ii) was the holder of a prescribed expired licence; or\n- (iii) has served an apprenticeship mentioned in subsection&#160;(3) , but has not satisfactorily finished the course of instruction mentioned in subsection&#160;(3) (b) ; or\n- (iv) holds a certificate or other document issued by a relevant assessing authority stating that the applicant’s skills are suitable for carrying out the relevant electrical work; and\n- (b) the applicant has complied with the regulator’s examination requirements; and\n- (c) the applicant is competent in the relevant electrical work.\n- (i) holds a prescribed current licence; or\n- (ii) was the holder of a prescribed expired licence; or\n- (iii) has served an apprenticeship mentioned in subsection&#160;(3) , but has not satisfactorily finished the course of instruction mentioned in subsection&#160;(3) (b) ; or\n- (iv) holds a certificate or other document issued by a relevant assessing authority stating that the applicant’s skills are suitable for carrying out the relevant electrical work; and\n- (a) for an applicant for an electrical mechanic licence—a current electrical fitter licence; or\n- (b) for an applicant for an electrical linesperson licence, electrical fitter licence or electrical jointer licence—a current electrical mechanic licence.\n- (a) for an applicant for an electrical mechanic licence—an electrical mechanic licence issued under the Act that has expired; or\n- (b) for an applicant for an electrical linesperson licence—an electrical linesperson licence issued under the Act that has expired; or\n- (c) for an applicant for an electrical fitter licence—an electrical fitter licence issued under the Act that has expired; or\n- (d) for an applicant for an electrical jointer licence—an electrical jointer licence issued under the Act that has expired.\n- (a) if the licence is an electrical mechanic licence—electrical work of an electrical mechanic; or\n- (b) if the licence is an electrical linesperson licence—electrical work of an electrical linesperson; or\n- (c) if the licence is an electrical fitter licence—electrical work of an electrical fitter; or\n- (d) if the licence is an electrical jointer licence—electrical work of an electrical jointer.\n- (a) a VET statement of attainment under the National Vocational Education and Training Regulator Act 2011 (Cwlth) ; or\n- (b) a statement given to a person by a training organisation outside of Australia confirming that the person has satisfied the requirements of units of competency or modules stated in the statement.","sortOrder":197},{"sectionNumber":"sec.158","sectionType":"section","heading":"Technical requirements—restricted electrical work licence","content":"### sec.158 Technical requirements—restricted electrical work licence\n\nThis section applies in relation to a restricted electrical work licence.\nThe applicant must comply with the eligibility requirements stated in subsection&#160;(3) , (4) , (5) or (6) .\nThe applicant must have—\nsatisfactorily finished a course of training, conducted by a registered training organisation, that the regulator considers appropriate; and\nsatisfactorily finished a course of instruction chosen by the regulator; and\ngiven the regulator a written statement—\nif the course of training is delivered under a training plan—from a relevant employer verifying the applicant has satisfactorily finished the training to be delivered under the training plan; and\nfrom the registered training organisation mentioned in paragraph&#160;(a) verifying that the applicant is competent in the relevant electrical work; and\nsatisfied the regulator the applicant is competent in the relevant electrical work.\nThe applicant must have—\nsatisfactorily finished a course of training outside Queensland that is, in the regulator’s opinion, at least equivalent to the course of training mentioned in subsection&#160;(3) (a) ; and\nsatisfactorily finished a course of instruction that is, in the regulator’s opinion, at least equivalent to the course of instruction mentioned in subsection&#160;(3) (b) ; and\ngiven the regulator a written statement—\nif the course of training is delivered under an apprenticeship or traineeship—from a relevant employer verifying the applicant has satisfactorily finished the training to be delivered under the apprenticeship or traineeship; and\nfrom the training organisation that delivered the course of training mentioned in paragraph&#160;(a) verifying that the applicant is competent in the relevant electrical work; and\nsatisfied the regulator the applicant is competent in the relevant electrical work.\nThe applicant must be the holder of a current licence, permit, certificate or other authority issued under a law of another State, the Commonwealth or New Zealand that the regulator decides is equivalent to the restricted electrical work licence.\nThe applicant must have—\nsatisfied the regulator that the applicant—\nis the holder of a tradesperson’s certificate within the meaning of the repealed Tradespersons’ Rights Regulation Act 1946 (Cwlth) in a relevant calling; or\nis the holder of a tradesperson’s certificate issued by a corresponding training department in a relevant calling; or\nis the holder of a certificate or other document issued by a relevant assessing authority stating that the applicant’s skills are suitable for an occupation that is or includes a relevant calling; or\nhas equivalent qualifications or experience in a relevant calling; or\nhas held a restricted electrical work licence that was issued under the Act and has expired; and\nsatisfactorily finished a course of instruction, chosen by the regulator, conducted by a registered training organisation; and\ngiven the regulator a written statement—\nif the course is training delivered to the applicant under a training plan—from a relevant employer verifying the applicant has satisfactorily finished the training to be delivered under the training plan; and\nfrom the registered training organisation verifying that the applicant is competent in performing the relevant electrical work; and\nsatisfied the regulator the applicant is competent to perform relevant electrical work.\nIf an applicant can not comply with the requirement under subsection&#160;(3) (c) (i) or (4) (c) (i) (the employer statement requirement ), but otherwise complies with subsection&#160;(3) or (4) , the applicant is taken to have complied with the employer statement requirement if the applicant satisfies the regulator the applicant has satisfactorily finished the training mentioned in the requirement.\nIn this section—\nrelevant calling means a calling the regulator decides requires the applicant to perform electrical work.\nrelevant electrical work , for an applicant for a restricted electrical work licence, means the electrical work the subject of the licence.\n(sec.158-ssec.1) This section applies in relation to a restricted electrical work licence.\n(sec.158-ssec.2) The applicant must comply with the eligibility requirements stated in subsection&#160;(3) , (4) , (5) or (6) .\n(sec.158-ssec.3) The applicant must have— satisfactorily finished a course of training, conducted by a registered training organisation, that the regulator considers appropriate; and satisfactorily finished a course of instruction chosen by the regulator; and given the regulator a written statement— if the course of training is delivered under a training plan—from a relevant employer verifying the applicant has satisfactorily finished the training to be delivered under the training plan; and from the registered training organisation mentioned in paragraph&#160;(a) verifying that the applicant is competent in the relevant electrical work; and satisfied the regulator the applicant is competent in the relevant electrical work.\n(sec.158-ssec.4) The applicant must have— satisfactorily finished a course of training outside Queensland that is, in the regulator’s opinion, at least equivalent to the course of training mentioned in subsection&#160;(3) (a) ; and satisfactorily finished a course of instruction that is, in the regulator’s opinion, at least equivalent to the course of instruction mentioned in subsection&#160;(3) (b) ; and given the regulator a written statement— if the course of training is delivered under an apprenticeship or traineeship—from a relevant employer verifying the applicant has satisfactorily finished the training to be delivered under the apprenticeship or traineeship; and from the training organisation that delivered the course of training mentioned in paragraph&#160;(a) verifying that the applicant is competent in the relevant electrical work; and satisfied the regulator the applicant is competent in the relevant electrical work.\n(sec.158-ssec.5) The applicant must be the holder of a current licence, permit, certificate or other authority issued under a law of another State, the Commonwealth or New Zealand that the regulator decides is equivalent to the restricted electrical work licence.\n(sec.158-ssec.6) The applicant must have— satisfied the regulator that the applicant— is the holder of a tradesperson’s certificate within the meaning of the repealed Tradespersons’ Rights Regulation Act 1946 (Cwlth) in a relevant calling; or is the holder of a tradesperson’s certificate issued by a corresponding training department in a relevant calling; or is the holder of a certificate or other document issued by a relevant assessing authority stating that the applicant’s skills are suitable for an occupation that is or includes a relevant calling; or has equivalent qualifications or experience in a relevant calling; or has held a restricted electrical work licence that was issued under the Act and has expired; and satisfactorily finished a course of instruction, chosen by the regulator, conducted by a registered training organisation; and given the regulator a written statement— if the course is training delivered to the applicant under a training plan—from a relevant employer verifying the applicant has satisfactorily finished the training to be delivered under the training plan; and from the registered training organisation verifying that the applicant is competent in performing the relevant electrical work; and satisfied the regulator the applicant is competent to perform relevant electrical work.\n(sec.158-ssec.7) If an applicant can not comply with the requirement under subsection&#160;(3) (c) (i) or (4) (c) (i) (the employer statement requirement ), but otherwise complies with subsection&#160;(3) or (4) , the applicant is taken to have complied with the employer statement requirement if the applicant satisfies the regulator the applicant has satisfactorily finished the training mentioned in the requirement.\n(sec.158-ssec.8) In this section— relevant calling means a calling the regulator decides requires the applicant to perform electrical work. relevant electrical work , for an applicant for a restricted electrical work licence, means the electrical work the subject of the licence.\n- (a) satisfactorily finished a course of training, conducted by a registered training organisation, that the regulator considers appropriate; and\n- (b) satisfactorily finished a course of instruction chosen by the regulator; and\n- (c) given the regulator a written statement— (i) if the course of training is delivered under a training plan—from a relevant employer verifying the applicant has satisfactorily finished the training to be delivered under the training plan; and (ii) from the registered training organisation mentioned in paragraph&#160;(a) verifying that the applicant is competent in the relevant electrical work; and\n- (i) if the course of training is delivered under a training plan—from a relevant employer verifying the applicant has satisfactorily finished the training to be delivered under the training plan; and\n- (ii) from the registered training organisation mentioned in paragraph&#160;(a) verifying that the applicant is competent in the relevant electrical work; and\n- (d) satisfied the regulator the applicant is competent in the relevant electrical work.\n- (i) if the course of training is delivered under a training plan—from a relevant employer verifying the applicant has satisfactorily finished the training to be delivered under the training plan; and\n- (ii) from the registered training organisation mentioned in paragraph&#160;(a) verifying that the applicant is competent in the relevant electrical work; and\n- (a) satisfactorily finished a course of training outside Queensland that is, in the regulator’s opinion, at least equivalent to the course of training mentioned in subsection&#160;(3) (a) ; and\n- (b) satisfactorily finished a course of instruction that is, in the regulator’s opinion, at least equivalent to the course of instruction mentioned in subsection&#160;(3) (b) ; and\n- (c) given the regulator a written statement— (i) if the course of training is delivered under an apprenticeship or traineeship—from a relevant employer verifying the applicant has satisfactorily finished the training to be delivered under the apprenticeship or traineeship; and (ii) from the training organisation that delivered the course of training mentioned in paragraph&#160;(a) verifying that the applicant is competent in the relevant electrical work; and\n- (i) if the course of training is delivered under an apprenticeship or traineeship—from a relevant employer verifying the applicant has satisfactorily finished the training to be delivered under the apprenticeship or traineeship; and\n- (ii) from the training organisation that delivered the course of training mentioned in paragraph&#160;(a) verifying that the applicant is competent in the relevant electrical work; and\n- (d) satisfied the regulator the applicant is competent in the relevant electrical work.\n- (i) if the course of training is delivered under an apprenticeship or traineeship—from a relevant employer verifying the applicant has satisfactorily finished the training to be delivered under the apprenticeship or traineeship; and\n- (ii) from the training organisation that delivered the course of training mentioned in paragraph&#160;(a) verifying that the applicant is competent in the relevant electrical work; and\n- (a) satisfied the regulator that the applicant— (i) is the holder of a tradesperson’s certificate within the meaning of the repealed Tradespersons’ Rights Regulation Act 1946 (Cwlth) in a relevant calling; or (ii) is the holder of a tradesperson’s certificate issued by a corresponding training department in a relevant calling; or (iii) is the holder of a certificate or other document issued by a relevant assessing authority stating that the applicant’s skills are suitable for an occupation that is or includes a relevant calling; or (iv) has equivalent qualifications or experience in a relevant calling; or (v) has held a restricted electrical work licence that was issued under the Act and has expired; and\n- (i) is the holder of a tradesperson’s certificate within the meaning of the repealed Tradespersons’ Rights Regulation Act 1946 (Cwlth) in a relevant calling; or\n- (ii) is the holder of a tradesperson’s certificate issued by a corresponding training department in a relevant calling; or\n- (iii) is the holder of a certificate or other document issued by a relevant assessing authority stating that the applicant’s skills are suitable for an occupation that is or includes a relevant calling; or\n- (iv) has equivalent qualifications or experience in a relevant calling; or\n- (v) has held a restricted electrical work licence that was issued under the Act and has expired; and\n- (b) satisfactorily finished a course of instruction, chosen by the regulator, conducted by a registered training organisation; and\n- (c) given the regulator a written statement— (i) if the course is training delivered to the applicant under a training plan—from a relevant employer verifying the applicant has satisfactorily finished the training to be delivered under the training plan; and (ii) from the registered training organisation verifying that the applicant is competent in performing the relevant electrical work; and\n- (i) if the course is training delivered to the applicant under a training plan—from a relevant employer verifying the applicant has satisfactorily finished the training to be delivered under the training plan; and\n- (ii) from the registered training organisation verifying that the applicant is competent in performing the relevant electrical work; and\n- (d) satisfied the regulator the applicant is competent to perform relevant electrical work.\n- (i) is the holder of a tradesperson’s certificate within the meaning of the repealed Tradespersons’ Rights Regulation Act 1946 (Cwlth) in a relevant calling; or\n- (ii) is the holder of a tradesperson’s certificate issued by a corresponding training department in a relevant calling; or\n- (iii) is the holder of a certificate or other document issued by a relevant assessing authority stating that the applicant’s skills are suitable for an occupation that is or includes a relevant calling; or\n- (iv) has equivalent qualifications or experience in a relevant calling; or\n- (v) has held a restricted electrical work licence that was issued under the Act and has expired; and\n- (i) if the course is training delivered to the applicant under a training plan—from a relevant employer verifying the applicant has satisfactorily finished the training to be delivered under the training plan; and\n- (ii) from the registered training organisation verifying that the applicant is competent in performing the relevant electrical work; and","sortOrder":198},{"sectionNumber":"sec.159","sectionType":"section","heading":"Eligibility requirements— Act , s&#160;59","content":"### sec.159 Eligibility requirements— Act , s&#160;59\n\nThis section prescribes, for section&#160;59 (4) of the Act , eligibility requirements that apply to an applicant for the issue of an electrical work training permit.\nThe applicant must have satisfied the regulator that—\nthe applicant is the holder of a relevant qualification; and\neither—\nthe applicant does not have any outstanding disciplinary matters; or\nthe applicant reasonably requires the permit to complete training related to an outstanding disciplinary matter.\nFor subsection&#160;(2) (a) , the applicant has a relevant qualification for electrical work mentioned in column 1 of the following table if the applicant holds a qualification mentioned in column 2 of the table opposite the electrical work.\nColumn 1\nColumn 2\nElectrical work\nQualification\n1\nelectrical mechanic\na current electrical fitter licence\na tradesperson’s certificate within the meaning of the repealed Tradespersons’ Rights Regulation Act 1946 (Cwlth) in the classification of an electrical mechanic\n2\nelectrical fitter\na tradesperson’s certificate within the meaning of the repealed Tradespersons’ Rights Regulation Act 1946 (Cwlth) in the classification of an electrical fitter\n3\nelectrical work of a relevant trade\nan electrical work licence in the relevant trade that was issued under the Act and has expired\na certificate or other document stating the applicant has served an apprenticeship to the calling of the relevant trade under the Further Education and Training Act 2014 , but has not satisfactorily finished a course of instruction chosen by the regulator\na certificate or other document issued by a relevant assessing authority stating the holder’s skills are suitable for the occupation of the relevant trade\n4\nelectrical work other than electrical work mentioned in items 1 to 3\na tradesperson’s certificate within the meaning of the repealed Tradespersons’ Rights Regulation Act 1946 (Cwlth) in a calling the regulator decides requires the applicant to perform the electrical work\na tradesperson’s certificate issued by a corresponding training department in a calling that the regulator decides requires the applicant to perform the electrical work\na certificate or other document issued by a relevant assessing authority stating that the applicant’s skills are suitable for an occupation that is or includes a calling the regulator decides requires the applicant to perform the electrical work\nan equivalent qualification or experience in a calling the regulator decides requires the applicant to perform the electrical work\nWithout limiting the matters the regulator may consider under subsection&#160;(2) (b) (i) , the regulator may consider the following about the applicant’s activities, whether before or after the commencement of this section—\ndisciplinary action taken against the applicant under a law regulating the activities of licensed electrical workers;\nthe applicant’s non-performance of a duty under a law about electrical work and the reasons for the non-performance;\nremedial action taken by the applicant to address an activity mentioned in paragraph&#160;(a) or (b) .\nIn this section—\nrelevant trade means the trade of an electrical mechanic, electrical linesperson, electrical fitter or electrical jointer.\n(sec.159-ssec.1) This section prescribes, for section&#160;59 (4) of the Act , eligibility requirements that apply to an applicant for the issue of an electrical work training permit.\n(sec.159-ssec.2) The applicant must have satisfied the regulator that— the applicant is the holder of a relevant qualification; and either— the applicant does not have any outstanding disciplinary matters; or the applicant reasonably requires the permit to complete training related to an outstanding disciplinary matter.\n(sec.159-ssec.3) For subsection&#160;(2) (a) , the applicant has a relevant qualification for electrical work mentioned in column 1 of the following table if the applicant holds a qualification mentioned in column 2 of the table opposite the electrical work. Column 1 Column 2 Electrical work Qualification 1 electrical mechanic a current electrical fitter licence a tradesperson’s certificate within the meaning of the repealed Tradespersons’ Rights Regulation Act 1946 (Cwlth) in the classification of an electrical mechanic 2 electrical fitter a tradesperson’s certificate within the meaning of the repealed Tradespersons’ Rights Regulation Act 1946 (Cwlth) in the classification of an electrical fitter 3 electrical work of a relevant trade an electrical work licence in the relevant trade that was issued under the Act and has expired a certificate or other document stating the applicant has served an apprenticeship to the calling of the relevant trade under the Further Education and Training Act 2014 , but has not satisfactorily finished a course of instruction chosen by the regulator a certificate or other document issued by a relevant assessing authority stating the holder’s skills are suitable for the occupation of the relevant trade 4 electrical work other than electrical work mentioned in items 1 to 3 a tradesperson’s certificate within the meaning of the repealed Tradespersons’ Rights Regulation Act 1946 (Cwlth) in a calling the regulator decides requires the applicant to perform the electrical work a tradesperson’s certificate issued by a corresponding training department in a calling that the regulator decides requires the applicant to perform the electrical work a certificate or other document issued by a relevant assessing authority stating that the applicant’s skills are suitable for an occupation that is or includes a calling the regulator decides requires the applicant to perform the electrical work an equivalent qualification or experience in a calling the regulator decides requires the applicant to perform the electrical work\n(sec.159-ssec.4) Without limiting the matters the regulator may consider under subsection&#160;(2) (b) (i) , the regulator may consider the following about the applicant’s activities, whether before or after the commencement of this section— disciplinary action taken against the applicant under a law regulating the activities of licensed electrical workers; the applicant’s non-performance of a duty under a law about electrical work and the reasons for the non-performance; remedial action taken by the applicant to address an activity mentioned in paragraph&#160;(a) or (b) .\n(sec.159-ssec.5) In this section— relevant trade means the trade of an electrical mechanic, electrical linesperson, electrical fitter or electrical jointer.\n- (a) the applicant is the holder of a relevant qualification; and\n- (b) either— (i) the applicant does not have any outstanding disciplinary matters; or (ii) the applicant reasonably requires the permit to complete training related to an outstanding disciplinary matter.\n- (i) the applicant does not have any outstanding disciplinary matters; or\n- (ii) the applicant reasonably requires the permit to complete training related to an outstanding disciplinary matter.\n- (i) the applicant does not have any outstanding disciplinary matters; or\n- (ii) the applicant reasonably requires the permit to complete training related to an outstanding disciplinary matter.\n- (a) disciplinary action taken against the applicant under a law regulating the activities of licensed electrical workers;\n- (b) the applicant’s non-performance of a duty under a law about electrical work and the reasons for the non-performance;\n- (c) remedial action taken by the applicant to address an activity mentioned in paragraph&#160;(a) or (b) .","sortOrder":199},{"sectionNumber":"sec.160","sectionType":"section","heading":"Term of electrical work licence","content":"### sec.160 Term of electrical work licence\n\nThe following electrical work licences may be issued for a maximum of 5 years—\nan electrical mechanic licence;\nan electrical linesperson licence;\nan electrical fitter licence;\nan electrical jointer licence;\na restricted electrical work licence.\nAn electrical work training permit may be issued for a maximum of 1 year.\n(sec.160-ssec.1) The following electrical work licences may be issued for a maximum of 5 years— an electrical mechanic licence; an electrical linesperson licence; an electrical fitter licence; an electrical jointer licence; a restricted electrical work licence.\n(sec.160-ssec.2) An electrical work training permit may be issued for a maximum of 1 year.\n- (a) an electrical mechanic licence;\n- (b) an electrical linesperson licence;\n- (c) an electrical fitter licence;\n- (d) an electrical jointer licence;\n- (e) a restricted electrical work licence.","sortOrder":200},{"sectionNumber":"pt.7-div.4","sectionType":"division","heading":"Requirements for issue of electrical contractor licences","content":"## Requirements for issue of electrical contractor licences","sortOrder":201},{"sectionNumber":"sec.161","sectionType":"section","heading":"Definitions for division","content":"### sec.161 Definitions for division\n\nIn this division—\napplicant , for an electrical contractor licence, means an individual, partnership or corporation that has applied for the issue of the licence.\nemployee , for an applicant, includes—\nfor an applicant that is a partnership—an individual who is a partner in the partnership; and\nfor an applicant that is a corporation—an executive officer or member of the corporation.\n- (a) for an applicant that is a partnership—an individual who is a partner in the partnership; and\n- (b) for an applicant that is a corporation—an executive officer or member of the corporation.","sortOrder":202},{"sectionNumber":"sec.162","sectionType":"section","heading":"Eligibility requirements—electrical contractor licence— Act , s&#160;59","content":"### sec.162 Eligibility requirements—electrical contractor licence— Act , s&#160;59\n\nFor section&#160;59 (4) of the Act , the eligibility requirements for the issue of an electrical contractor licence are that—\nthe applicant has at least 1 qualified business person; and\nthe applicant has at least 1 qualified technical person to perform electrical work for the applicant; and\nthe applicant has complied with the insurance requirements under section&#160;165 ; and\nthe applicant has satisfied the regulator that the electrical work to be performed by the applicant as a licensed electrical contractor is proposed to be—\nperformed by a qualified technical person for the applicant under the qualified technical person’s electrical work licence; or\nsupervised by a qualified technical person for the applicant who is authorised to perform the work under the qualified technical person’s electrical work licence.\n- (a) the applicant has at least 1 qualified business person; and\n- (b) the applicant has at least 1 qualified technical person to perform electrical work for the applicant; and\n- (c) the applicant has complied with the insurance requirements under section&#160;165 ; and\n- (d) the applicant has satisfied the regulator that the electrical work to be performed by the applicant as a licensed electrical contractor is proposed to be— (i) performed by a qualified technical person for the applicant under the qualified technical person’s electrical work licence; or (ii) supervised by a qualified technical person for the applicant who is authorised to perform the work under the qualified technical person’s electrical work licence.\n- (i) performed by a qualified technical person for the applicant under the qualified technical person’s electrical work licence; or\n- (ii) supervised by a qualified technical person for the applicant who is authorised to perform the work under the qualified technical person’s electrical work licence.\n- (i) performed by a qualified technical person for the applicant under the qualified technical person’s electrical work licence; or\n- (ii) supervised by a qualified technical person for the applicant who is authorised to perform the work under the qualified technical person’s electrical work licence.","sortOrder":203},{"sectionNumber":"sec.163","sectionType":"section","heading":"Qualified business person","content":"### sec.163 Qualified business person\n\nThe regulator must endorse the name of an individual on an applicant’s electrical contractor licence as a qualified business person for the applicant if the regulator is satisfied the individual—\nis someone who—\nhas operated a business for a period of, or periods totalling, 5 years; or\nholds a diploma or higher level qualification in business; or\nhas satisfactorily finished a course of instruction approved by the regulator under subsection&#160;(3) (a) related to the conduct of a business; and\nis the applicant or an employee of the applicant; and\nhas, if required by the regulator, satisfactorily finished an examination or a course of instruction approved by the regulator under subsection&#160;(3) (b) on business aspects of performing electrical work; and\nis a fit and proper person; and\nis competent to perform the business aspects of performing electrical work as, or for, a licensed electrical contractor.\nIn deciding whether a person who is an individual is a fit and proper person under subsection&#160;(1) (d) , the regulator may consider only—\nthe standard of honesty and integrity demonstrated by the person in commercial and other activities in which the person has been involved; and\nany failure by the person to perform commercial or statutory obligations and the reasons for the failure.\nFor this section, the regulator may—\napprove courses of instruction related to the conduct of a business; and\napprove examinations or courses of instruction on business aspects of performing electrical work.\nAn examination or course of instruction approved by the regulator under subsection&#160;(3) must be published on the department’s website.\n(sec.163-ssec.1) The regulator must endorse the name of an individual on an applicant’s electrical contractor licence as a qualified business person for the applicant if the regulator is satisfied the individual— is someone who— has operated a business for a period of, or periods totalling, 5 years; or holds a diploma or higher level qualification in business; or has satisfactorily finished a course of instruction approved by the regulator under subsection&#160;(3) (a) related to the conduct of a business; and is the applicant or an employee of the applicant; and has, if required by the regulator, satisfactorily finished an examination or a course of instruction approved by the regulator under subsection&#160;(3) (b) on business aspects of performing electrical work; and is a fit and proper person; and is competent to perform the business aspects of performing electrical work as, or for, a licensed electrical contractor.\n(sec.163-ssec.2) In deciding whether a person who is an individual is a fit and proper person under subsection&#160;(1) (d) , the regulator may consider only— the standard of honesty and integrity demonstrated by the person in commercial and other activities in which the person has been involved; and any failure by the person to perform commercial or statutory obligations and the reasons for the failure.\n(sec.163-ssec.3) For this section, the regulator may— approve courses of instruction related to the conduct of a business; and approve examinations or courses of instruction on business aspects of performing electrical work.\n(sec.163-ssec.4) An examination or course of instruction approved by the regulator under subsection&#160;(3) must be published on the department’s website.\n- (a) is someone who— (i) has operated a business for a period of, or periods totalling, 5 years; or (ii) holds a diploma or higher level qualification in business; or (iii) has satisfactorily finished a course of instruction approved by the regulator under subsection&#160;(3) (a) related to the conduct of a business; and\n- (i) has operated a business for a period of, or periods totalling, 5 years; or\n- (ii) holds a diploma or higher level qualification in business; or\n- (iii) has satisfactorily finished a course of instruction approved by the regulator under subsection&#160;(3) (a) related to the conduct of a business; and\n- (b) is the applicant or an employee of the applicant; and\n- (c) has, if required by the regulator, satisfactorily finished an examination or a course of instruction approved by the regulator under subsection&#160;(3) (b) on business aspects of performing electrical work; and\n- (d) is a fit and proper person; and\n- (e) is competent to perform the business aspects of performing electrical work as, or for, a licensed electrical contractor.\n- (i) has operated a business for a period of, or periods totalling, 5 years; or\n- (ii) holds a diploma or higher level qualification in business; or\n- (iii) has satisfactorily finished a course of instruction approved by the regulator under subsection&#160;(3) (a) related to the conduct of a business; and\n- (a) the standard of honesty and integrity demonstrated by the person in commercial and other activities in which the person has been involved; and\n- (b) any failure by the person to perform commercial or statutory obligations and the reasons for the failure.\n- (a) approve courses of instruction related to the conduct of a business; and\n- (b) approve examinations or courses of instruction on business aspects of performing electrical work.","sortOrder":204},{"sectionNumber":"sec.164","sectionType":"section","heading":"Qualified technical person","content":"### sec.164 Qualified technical person\n\nThe regulator must endorse the name of an individual on an applicant’s electrical contractor licence as a qualified technical person for an applicant if the regulator is satisfied the individual—\nis the applicant or an employee of the applicant; and\nhas, if required by the regulator, satisfactorily finished a course of instruction or an examination on technical aspects of performing electrical work; and\nif the electrical work to be performed by the applicant may be performed only by the holder of an electrical work licence—\nholds an electrical work licence; and\nhas held an electrical work licence for at least 2 years, or a shorter period considered acceptable by the regulator; and\nis a fit and proper person; and\nis competent to perform electrical work as, or for, a licensed electrical contractor.\nIn deciding whether a person who is an individual is a fit and proper person under subsection&#160;(1) (d) , the regulator may consider only—\nthe standard of honesty and integrity demonstrated by the person in commercial and other activities in which the person has been involved; and\nany failure by the person to perform commercial or statutory obligations and the reasons for the failure.\nDespite subsection&#160;(2) , an individual is not a fit and proper person if the individual is disqualified from being a qualified technical person for the holder of an electrical contractor licence under part&#160;9 of the Act .\n(sec.164-ssec.1) The regulator must endorse the name of an individual on an applicant’s electrical contractor licence as a qualified technical person for an applicant if the regulator is satisfied the individual— is the applicant or an employee of the applicant; and has, if required by the regulator, satisfactorily finished a course of instruction or an examination on technical aspects of performing electrical work; and if the electrical work to be performed by the applicant may be performed only by the holder of an electrical work licence— holds an electrical work licence; and has held an electrical work licence for at least 2 years, or a shorter period considered acceptable by the regulator; and is a fit and proper person; and is competent to perform electrical work as, or for, a licensed electrical contractor.\n(sec.164-ssec.2) In deciding whether a person who is an individual is a fit and proper person under subsection&#160;(1) (d) , the regulator may consider only— the standard of honesty and integrity demonstrated by the person in commercial and other activities in which the person has been involved; and any failure by the person to perform commercial or statutory obligations and the reasons for the failure.\n(sec.164-ssec.3) Despite subsection&#160;(2) , an individual is not a fit and proper person if the individual is disqualified from being a qualified technical person for the holder of an electrical contractor licence under part&#160;9 of the Act .\n- (a) is the applicant or an employee of the applicant; and\n- (b) has, if required by the regulator, satisfactorily finished a course of instruction or an examination on technical aspects of performing electrical work; and\n- (c) if the electrical work to be performed by the applicant may be performed only by the holder of an electrical work licence— (i) holds an electrical work licence; and (ii) has held an electrical work licence for at least 2 years, or a shorter period considered acceptable by the regulator; and\n- (i) holds an electrical work licence; and\n- (ii) has held an electrical work licence for at least 2 years, or a shorter period considered acceptable by the regulator; and\n- (d) is a fit and proper person; and\n- (e) is competent to perform electrical work as, or for, a licensed electrical contractor.\n- (i) holds an electrical work licence; and\n- (ii) has held an electrical work licence for at least 2 years, or a shorter period considered acceptable by the regulator; and\n- (a) the standard of honesty and integrity demonstrated by the person in commercial and other activities in which the person has been involved; and\n- (b) any failure by the person to perform commercial or statutory obligations and the reasons for the failure.","sortOrder":205},{"sectionNumber":"sec.165","sectionType":"section","heading":"Insurance requirements for applicant for electrical contractor licence","content":"### sec.165 Insurance requirements for applicant for electrical contractor licence\n\nAn applicant for an electrical contractor licence must give the regulator evidence that the applicant holds the following insurance—\npublic and products liability insurance that covers the applicant for at least $5,000,000;\nconsumer protection insurance that covers the applicant for at least $50,000.\n- (a) public and products liability insurance that covers the applicant for at least $5,000,000;\n- (b) consumer protection insurance that covers the applicant for at least $50,000.","sortOrder":206},{"sectionNumber":"sec.166","sectionType":"section","heading":"Term of electrical contractor licence","content":"### sec.166 Term of electrical contractor licence\n\nAn electrical contractor licence may be issued for a maximum of 1 year.","sortOrder":207},{"sectionNumber":"pt.7-div.5","sectionType":"division","heading":"Requirements for renewal or reinstatement of electrical licences","content":"## Requirements for renewal or reinstatement of electrical licences","sortOrder":208},{"sectionNumber":"sec.167","sectionType":"section","heading":"Eligibility requirements—electrical work licence— Act , ss&#160;60 and 61","content":"### sec.167 Eligibility requirements—electrical work licence— Act , ss&#160;60 and 61\n\nFor sections&#160;60 (4) and 61 (4) of the Act , the eligibility requirements for the renewal or reinstatement of an electrical work licence are that the regulator must be satisfied that—\nthe applicant is or was the holder of the electrical work licence the applicant has applied to renew or reinstate; and\nthe applicant continues to satisfy the resuscitation requirement in section&#160;155 (1) ; and\nfor renewal or reinstatement of an electrical linesperson licence—the applicant continues to satisfy the rescue requirement in section&#160;155 (2) ; and\nthe applicant is competent in the electrical work to be performed under the licence; and\nthe applicant does not have an outstanding disciplinary matter.\nHowever, subsection&#160;(1) (b) or (c) does not prevent the renewal or reinstatement of the electrical work licence if the regulator is satisfied—\nthe applicant has a medical condition that—\nprevents the applicant carrying out the relevant activity for the subsection; but\ndoes not otherwise affect the applicant’s ability to perform electrical work under the licence; and\nin the particular circumstances, it is reasonable to allow the applicant to carry out electrical work subject to a condition that the applicant must not act in a role for which it is a requirement that the applicant be competent in the relevant activity.\na safety observer\nThis section does not apply in relation to an electrical work training permit.\nIn this section—\nrelevant activity means—\nin relation to subsection&#160;(1) (b) —resuscitation; or\nin relation to subsection&#160;(1) (c) —the rescue of an individual from a pole top or transmission tower.\nFor the renewal or reinstatement of an electrical linesperson licence by a person who was eligible for the licence before 1 October 2002, see section&#160;320 .\nFor the renewal or reinstatement of an electrical jointer licence by a person who was eligible for the licence before 1 October 2002, see section&#160;321 .\n(sec.167-ssec.1) For sections&#160;60 (4) and 61 (4) of the Act , the eligibility requirements for the renewal or reinstatement of an electrical work licence are that the regulator must be satisfied that— the applicant is or was the holder of the electrical work licence the applicant has applied to renew or reinstate; and the applicant continues to satisfy the resuscitation requirement in section&#160;155 (1) ; and for renewal or reinstatement of an electrical linesperson licence—the applicant continues to satisfy the rescue requirement in section&#160;155 (2) ; and the applicant is competent in the electrical work to be performed under the licence; and the applicant does not have an outstanding disciplinary matter.\n(sec.167-ssec.2) However, subsection&#160;(1) (b) or (c) does not prevent the renewal or reinstatement of the electrical work licence if the regulator is satisfied— the applicant has a medical condition that— prevents the applicant carrying out the relevant activity for the subsection; but does not otherwise affect the applicant’s ability to perform electrical work under the licence; and in the particular circumstances, it is reasonable to allow the applicant to carry out electrical work subject to a condition that the applicant must not act in a role for which it is a requirement that the applicant be competent in the relevant activity. a safety observer\n(sec.167-ssec.3) This section does not apply in relation to an electrical work training permit.\n(sec.167-ssec.4) In this section— relevant activity means— in relation to subsection&#160;(1) (b) —resuscitation; or in relation to subsection&#160;(1) (c) —the rescue of an individual from a pole top or transmission tower.\n- (a) the applicant is or was the holder of the electrical work licence the applicant has applied to renew or reinstate; and\n- (b) the applicant continues to satisfy the resuscitation requirement in section&#160;155 (1) ; and\n- (c) for renewal or reinstatement of an electrical linesperson licence—the applicant continues to satisfy the rescue requirement in section&#160;155 (2) ; and\n- (d) the applicant is competent in the electrical work to be performed under the licence; and\n- (e) the applicant does not have an outstanding disciplinary matter.\n- (a) the applicant has a medical condition that— (i) prevents the applicant carrying out the relevant activity for the subsection; but (ii) does not otherwise affect the applicant’s ability to perform electrical work under the licence; and\n- (i) prevents the applicant carrying out the relevant activity for the subsection; but\n- (ii) does not otherwise affect the applicant’s ability to perform electrical work under the licence; and\n- (b) in the particular circumstances, it is reasonable to allow the applicant to carry out electrical work subject to a condition that the applicant must not act in a role for which it is a requirement that the applicant be competent in the relevant activity. Example of a role mentioned in paragraph&#160;(b) — a safety observer\n- (i) prevents the applicant carrying out the relevant activity for the subsection; but\n- (ii) does not otherwise affect the applicant’s ability to perform electrical work under the licence; and\n- (a) in relation to subsection&#160;(1) (b) —resuscitation; or\n- (b) in relation to subsection&#160;(1) (c) —the rescue of an individual from a pole top or transmission tower.\n- 1 For the renewal or reinstatement of an electrical linesperson licence by a person who was eligible for the licence before 1 October 2002, see section&#160;320 .\n- 2 For the renewal or reinstatement of an electrical jointer licence by a person who was eligible for the licence before 1 October 2002, see section&#160;321 .","sortOrder":209},{"sectionNumber":"sec.168","sectionType":"section","heading":"Eligibility requirements—electrical contractor licence— Act , ss&#160;60 and 61","content":"### sec.168 Eligibility requirements—electrical contractor licence— Act , ss&#160;60 and 61\n\nFor sections&#160;60 (4) and 61 (4) of the Act , the regulator must be satisfied the person who is or was the holder of the electrical contractor licence satisfies the requirements of section&#160;162 in relation to the issue of the licence.","sortOrder":210},{"sectionNumber":"sec.169","sectionType":"section","heading":"Eligibility requirements—pre-2019 electrical contractor licence— Act , ss&#160;60 and 61","content":"### sec.169 Eligibility requirements—pre-2019 electrical contractor licence— Act , ss&#160;60 and 61\n\nThis section applies if a person—\nheld an electrical contractor licence before 1 January 2019; or\napplied for an electrical contractor licence before 1 January 2019 and was granted the licence after 1 January 2019.\nFor applying the eligibility requirements of section&#160;162 (a) and (b) as applied by section&#160;168 , the expired Electrical Safety Regulation 2013 , section&#160;7 , as in force immediately before 1 January 2019, is taken to apply in relation to who is a qualified business person in relation to the applicant.\nSubsection&#160;(2) applies despite section&#160;163 .\n(sec.169-ssec.1) This section applies if a person— held an electrical contractor licence before 1 January 2019; or applied for an electrical contractor licence before 1 January 2019 and was granted the licence after 1 January 2019.\n(sec.169-ssec.2) For applying the eligibility requirements of section&#160;162 (a) and (b) as applied by section&#160;168 , the expired Electrical Safety Regulation 2013 , section&#160;7 , as in force immediately before 1 January 2019, is taken to apply in relation to who is a qualified business person in relation to the applicant.\n(sec.169-ssec.3) Subsection&#160;(2) applies despite section&#160;163 .\n- (a) held an electrical contractor licence before 1 January 2019; or\n- (b) applied for an electrical contractor licence before 1 January 2019 and was granted the licence after 1 January 2019.","sortOrder":211},{"sectionNumber":"sec.170","sectionType":"section","heading":"Term of electrical licences","content":"### sec.170 Term of electrical licences\n\nEach of the following electrical work licences may be renewed or reinstated for a maximum of 5 years—\nan electrical mechanic licence;\nan electrical linesperson licence;\nan electrical fitter licence;\nan electrical jointer licence;\na restricted electrical work licence.\nAn electrical contractor licence may be renewed or reinstated for a maximum of 1 year.\n(sec.170-ssec.1) Each of the following electrical work licences may be renewed or reinstated for a maximum of 5 years— an electrical mechanic licence; an electrical linesperson licence; an electrical fitter licence; an electrical jointer licence; a restricted electrical work licence.\n(sec.170-ssec.2) An electrical contractor licence may be renewed or reinstated for a maximum of 1 year.\n- (a) an electrical mechanic licence;\n- (b) an electrical linesperson licence;\n- (c) an electrical fitter licence;\n- (d) an electrical jointer licence;\n- (e) a restricted electrical work licence.","sortOrder":212},{"sectionNumber":"pt.7-div.6","sectionType":"division","heading":"Administration of electrical licences","content":"## Administration of electrical licences","sortOrder":213},{"sectionNumber":"sec.171","sectionType":"section","heading":"Register of electrical licences","content":"### sec.171 Register of electrical licences\n\nThe regulator must keep a register containing information about electrical licences.\nThe register must be kept in the form the regulator considers appropriate to ensure the information in the register can be efficiently recorded and accessed.\nThe regulator may decide to keep the register of electrical licences in electronic form.\nThe regulator may order the information in the register in the way the regulator considers appropriate.\nThe regulator may decide to separate historical information about electrical licences from current information.\nWithout limiting subsections&#160;(1) to (3) , the register must include the following information, for each electrical licence—\nthe full name and address of the holder;\nan identifying number;\nthe date the licence was issued;\ndetails of every renewal and reinstatement of the licence, and of any failure to renew the licence;\ndetails of disciplinary action taken by the licensing committee against the holder;\ndetails of anything else the regulator considers should be included in the register.\nthe conditions or restrictions on an electrical work licence\nThe regulator may publish some or all of the information included in the register in the way the regulator considers appropriate.\npublishing the register on the internet in the form of a database that allows consumers to obtain licensing details about an electrical contractor or a person conducting a business or undertaking to check the validity of an employee’s electrical work licence\n(sec.171-ssec.1) The regulator must keep a register containing information about electrical licences.\n(sec.171-ssec.2) The register must be kept in the form the regulator considers appropriate to ensure the information in the register can be efficiently recorded and accessed. The regulator may decide to keep the register of electrical licences in electronic form.\n(sec.171-ssec.3) The regulator may order the information in the register in the way the regulator considers appropriate. The regulator may decide to separate historical information about electrical licences from current information.\n(sec.171-ssec.4) Without limiting subsections&#160;(1) to (3) , the register must include the following information, for each electrical licence— the full name and address of the holder; an identifying number; the date the licence was issued; details of every renewal and reinstatement of the licence, and of any failure to renew the licence; details of disciplinary action taken by the licensing committee against the holder; details of anything else the regulator considers should be included in the register. the conditions or restrictions on an electrical work licence\n(sec.171-ssec.5) The regulator may publish some or all of the information included in the register in the way the regulator considers appropriate. publishing the register on the internet in the form of a database that allows consumers to obtain licensing details about an electrical contractor or a person conducting a business or undertaking to check the validity of an employee’s electrical work licence\n- (a) the full name and address of the holder;\n- (b) an identifying number;\n- (c) the date the licence was issued;\n- (d) details of every renewal and reinstatement of the licence, and of any failure to renew the licence;\n- (e) details of disciplinary action taken by the licensing committee against the holder;\n- (f) details of anything else the regulator considers should be included in the register. Example for paragraph&#160;(f) — the conditions or restrictions on an electrical work licence","sortOrder":214},{"sectionNumber":"sec.172","sectionType":"section","heading":"Requirement for holder of electrical licence to notify changed contact details","content":"### sec.172 Requirement for holder of electrical licence to notify changed contact details\n\nThis section applies if contact details recorded in the register for the holder of an electrical licence, including the holder’s name and address, are no longer correct.\nThe holder must, within 10 business days after the details become incorrect, give the regulator notice of the correct details.\nMaximum penalty—20 penalty units.\nSubsection&#160;(2) does not apply to—\na change of name of a corporation or partnership that is the holder of an electrical contractor licence; or\na change of the membership of a partnership that is the holder of an electrical contractor licence.\nIn this section—\nregister means the register of electrical licences the regulator is required to keep under section&#160;171 .\n(sec.172-ssec.1) This section applies if contact details recorded in the register for the holder of an electrical licence, including the holder’s name and address, are no longer correct.\n(sec.172-ssec.2) The holder must, within 10 business days after the details become incorrect, give the regulator notice of the correct details. Maximum penalty—20 penalty units.\n(sec.172-ssec.3) Subsection&#160;(2) does not apply to— a change of name of a corporation or partnership that is the holder of an electrical contractor licence; or a change of the membership of a partnership that is the holder of an electrical contractor licence.\n(sec.172-ssec.4) In this section— register means the register of electrical licences the regulator is required to keep under section&#160;171 .\n- (a) a change of name of a corporation or partnership that is the holder of an electrical contractor licence; or\n- (b) a change of the membership of a partnership that is the holder of an electrical contractor licence.","sortOrder":215},{"sectionNumber":"sec.173","sectionType":"section","heading":"Application for endorsement of additional qualified business person or qualified technical person","content":"### sec.173 Application for endorsement of additional qualified business person or qualified technical person\n\nAn applicant for an electrical contractor licence or a licensed electrical contractor may apply to the regulator to have 1 or more individuals endorsed as—\na qualified business person for the applicant or licensed electrical contractor; or\na qualified technical person for the applicant or licensed electrical contractor.\nThe applicant or licensed electrical contractor may make the application at any time—\nafter applying for the issue of the electrical contractor licence; and\nbefore the day that is 1 year after the licence expires.\nThe regulator must decide the application—\nfor an application mentioned in subsection&#160;(1) (a) —under section&#160;163 ; or\nfor an application mentioned in subsection&#160;(1) (b) —under section&#160;164 .\nIf the regulator refuses to endorse the individual to be a qualified business person or a qualified technical person for the applicant or licensed electrical contractor, the regulator must give the applicant or licensed electrical contractor an information notice for the decision.\nIn this section—\napplicant see section&#160;161 .\n(sec.173-ssec.1) An applicant for an electrical contractor licence or a licensed electrical contractor may apply to the regulator to have 1 or more individuals endorsed as— a qualified business person for the applicant or licensed electrical contractor; or a qualified technical person for the applicant or licensed electrical contractor.\n(sec.173-ssec.2) The applicant or licensed electrical contractor may make the application at any time— after applying for the issue of the electrical contractor licence; and before the day that is 1 year after the licence expires.\n(sec.173-ssec.3) The regulator must decide the application— for an application mentioned in subsection&#160;(1) (a) —under section&#160;163 ; or for an application mentioned in subsection&#160;(1) (b) —under section&#160;164 .\n(sec.173-ssec.4) If the regulator refuses to endorse the individual to be a qualified business person or a qualified technical person for the applicant or licensed electrical contractor, the regulator must give the applicant or licensed electrical contractor an information notice for the decision.\n(sec.173-ssec.5) In this section— applicant see section&#160;161 .\n- (a) a qualified business person for the applicant or licensed electrical contractor; or\n- (b) a qualified technical person for the applicant or licensed electrical contractor.\n- (a) after applying for the issue of the electrical contractor licence; and\n- (b) before the day that is 1 year after the licence expires.\n- (a) for an application mentioned in subsection&#160;(1) (a) —under section&#160;163 ; or\n- (b) for an application mentioned in subsection&#160;(1) (b) —under section&#160;164 .","sortOrder":216},{"sectionNumber":"sec.174","sectionType":"section","heading":"Removal of endorsement of qualified business person or qualified technical person","content":"### sec.174 Removal of endorsement of qualified business person or qualified technical person\n\nThis section applies in relation to a qualified person for a licensed electrical contractor.\nThe licensed electrical contractor must advise the regulator within 10 business days after the day any of the following happens—\nif the licensed electrical contractor is an individual—the qualified person is no longer an employee of the licensed electrical contractor;\nif the licensed electrical contractor is a partnership—the qualified person is no longer a partner or employee of the licensed electrical contractor;\nif the licensed electrical contractor is a corporation—the qualified person is no longer an executive officer or employee of the licensed electrical contractor;\nthe qualified person is no longer a fit and proper person;\nif the qualified person is the qualified business person for the licensed electrical contractor—the person is no longer competent to perform the business aspects of performing electrical work as or for the licensed electrical contractor;\nif the qualified person is the qualified technical person for the licensed electrical contractor—the person is no longer competent to perform electrical work as or for the licensed electrical contractor;\nif the qualified person is the qualified technical person for the licensed electrical contractor—the person is no longer the holder of an electrical work licence.\nMaximum penalty—20 penalty units.\nOn receiving the advice, the regulator must remove the endorsement of the qualified person from the licensed electrical contractor’s licence.\nIn this section—\nqualified person , for a licensed electrical contractor, means an individual whose name is endorsed on an electrical contractor licence as a qualified business person or a qualified technical person for the licensed electrical contractor.\n(sec.174-ssec.1) This section applies in relation to a qualified person for a licensed electrical contractor.\n(sec.174-ssec.2) The licensed electrical contractor must advise the regulator within 10 business days after the day any of the following happens— if the licensed electrical contractor is an individual—the qualified person is no longer an employee of the licensed electrical contractor; if the licensed electrical contractor is a partnership—the qualified person is no longer a partner or employee of the licensed electrical contractor; if the licensed electrical contractor is a corporation—the qualified person is no longer an executive officer or employee of the licensed electrical contractor; the qualified person is no longer a fit and proper person; if the qualified person is the qualified business person for the licensed electrical contractor—the person is no longer competent to perform the business aspects of performing electrical work as or for the licensed electrical contractor; if the qualified person is the qualified technical person for the licensed electrical contractor—the person is no longer competent to perform electrical work as or for the licensed electrical contractor; if the qualified person is the qualified technical person for the licensed electrical contractor—the person is no longer the holder of an electrical work licence. Maximum penalty—20 penalty units.\n(sec.174-ssec.3) On receiving the advice, the regulator must remove the endorsement of the qualified person from the licensed electrical contractor’s licence.\n(sec.174-ssec.4) In this section— qualified person , for a licensed electrical contractor, means an individual whose name is endorsed on an electrical contractor licence as a qualified business person or a qualified technical person for the licensed electrical contractor.\n- (a) if the licensed electrical contractor is an individual—the qualified person is no longer an employee of the licensed electrical contractor;\n- (b) if the licensed electrical contractor is a partnership—the qualified person is no longer a partner or employee of the licensed electrical contractor;\n- (c) if the licensed electrical contractor is a corporation—the qualified person is no longer an executive officer or employee of the licensed electrical contractor;\n- (d) the qualified person is no longer a fit and proper person;\n- (e) if the qualified person is the qualified business person for the licensed electrical contractor—the person is no longer competent to perform the business aspects of performing electrical work as or for the licensed electrical contractor;\n- (f) if the qualified person is the qualified technical person for the licensed electrical contractor—the person is no longer competent to perform electrical work as or for the licensed electrical contractor;\n- (g) if the qualified person is the qualified technical person for the licensed electrical contractor—the person is no longer the holder of an electrical work licence.","sortOrder":217},{"sectionNumber":"sec.175","sectionType":"section","heading":"Automatic suspension and cancellation of electrical contractor licence","content":"### sec.175 Automatic suspension and cancellation of electrical contractor licence\n\nAn electrical contractor licence is automatically suspended if, for a period of 30 days, there is no person—\nwho is a qualified business person and whose name is endorsed on the electrical contractor licence as a qualified business person for the licensed electrical contractor; or\nwho is a qualified technical person and whose name is endorsed on the electrical contractor licence as a qualified technical person for the licensed electrical contractor.\nThe licence is automatically cancelled if, 30 days after the day the licence was automatically suspended under subsection&#160;(1) , there is still no person whose name is endorsed on the electrical contractor licence as mentioned in subsection&#160;(1) (a) or (b) .\n(sec.175-ssec.1) An electrical contractor licence is automatically suspended if, for a period of 30 days, there is no person— who is a qualified business person and whose name is endorsed on the electrical contractor licence as a qualified business person for the licensed electrical contractor; or who is a qualified technical person and whose name is endorsed on the electrical contractor licence as a qualified technical person for the licensed electrical contractor.\n(sec.175-ssec.2) The licence is automatically cancelled if, 30 days after the day the licence was automatically suspended under subsection&#160;(1) , there is still no person whose name is endorsed on the electrical contractor licence as mentioned in subsection&#160;(1) (a) or (b) .\n- (a) who is a qualified business person and whose name is endorsed on the electrical contractor licence as a qualified business person for the licensed electrical contractor; or\n- (b) who is a qualified technical person and whose name is endorsed on the electrical contractor licence as a qualified technical person for the licensed electrical contractor.","sortOrder":218},{"sectionNumber":"sec.176","sectionType":"section","heading":"Change of name of corporation, partnership or business","content":"### sec.176 Change of name of corporation, partnership or business\n\nThis section applies to the holder of an electrical contractor licence if either of the following changes—\nthe name of the corporation or partnership holding the electrical contractor licence;\nthe name ( business name ) under which the holder carries on business.\nThe holder of the electrical contractor licence must, within 30 days after the change of name or business name, give the regulator written notice of the change.\nMaximum penalty—20 penalty units.\nThe notice may state the holder’s preference about how the regulator is to act under subsection&#160;(4) .\nAfter receiving the notice and considering any stated preference, the regulator must—\nreissue the licence endorsed with information about the change of name or business name; or\ncancel the licence and issue a new electrical contractor licence; or\ncancel the licence.\nA licence reissued by the regulator under subsection&#160;(4) (a) has, subject to the endorsement, continuing effect as the original electrical contractor licence.\nA new electrical contractor licence issued by the regulator under subsection&#160;(4) (b) must be endorsed with a memorandum stating the reasons for the issue of the new licence.\nIf the regulator decides to cancel the licence under subsection&#160;(4) (c) , the regulator must give the former holder an information notice for the decision.\n(sec.176-ssec.1) This section applies to the holder of an electrical contractor licence if either of the following changes— the name of the corporation or partnership holding the electrical contractor licence; the name ( business name ) under which the holder carries on business.\n(sec.176-ssec.2) The holder of the electrical contractor licence must, within 30 days after the change of name or business name, give the regulator written notice of the change. Maximum penalty—20 penalty units.\n(sec.176-ssec.3) The notice may state the holder’s preference about how the regulator is to act under subsection&#160;(4) .\n(sec.176-ssec.4) After receiving the notice and considering any stated preference, the regulator must— reissue the licence endorsed with information about the change of name or business name; or cancel the licence and issue a new electrical contractor licence; or cancel the licence.\n(sec.176-ssec.5) A licence reissued by the regulator under subsection&#160;(4) (a) has, subject to the endorsement, continuing effect as the original electrical contractor licence.\n(sec.176-ssec.6) A new electrical contractor licence issued by the regulator under subsection&#160;(4) (b) must be endorsed with a memorandum stating the reasons for the issue of the new licence.\n(sec.176-ssec.7) If the regulator decides to cancel the licence under subsection&#160;(4) (c) , the regulator must give the former holder an information notice for the decision.\n- (a) the name of the corporation or partnership holding the electrical contractor licence;\n- (b) the name ( business name ) under which the holder carries on business.\n- (a) reissue the licence endorsed with information about the change of name or business name; or\n- (b) cancel the licence and issue a new electrical contractor licence; or\n- (c) cancel the licence.","sortOrder":219},{"sectionNumber":"sec.177","sectionType":"section","heading":"Change in membership of partnership","content":"### sec.177 Change in membership of partnership\n\nThis section applies if—\na partnership is the holder of an electrical contractor licence; and\nthere is a change in the membership of the partnership, whether by the death or retirement of a member or the admission of a new member.\nThe continuing members of the partnership must, within 30 days after the membership change, give the regulator written notice of the change that includes full information and particulars of the change.\nMaximum penalty—20 penalty units.\nThe notice may state the members’ preference about how the regulator is to act under subsection&#160;(4) .\nAfter receiving the notice and considering any stated preference, the regulator must—\nreissue the licence endorsed with information about the membership change; or\ncancel the licence and issue a new licence; or\ncancel the licence.\nA licence endorsed by the regulator with the change of the membership of the partnership under subsection&#160;(4) (a) has, subject to the endorsement, continuing effect as the original electrical contractor licence.\nA new licence issued by the regulator under subsection&#160;(4) (b) must be endorsed with a memorandum stating the reasons for the issue of the new licence.\nThe regulator may issue a new licence to the partnership under subsection&#160;(4) (b) only if the regulator is satisfied that—\nthe entire business of electrical contracting work carried on by the partnership in Queensland before the membership change is to be carried on by the partnership after the new licence is issued; and\nthe partnership complies with the eligibility requirements for the issue of the new licence.\nIf the regulator decides to cancel the licence under subsection&#160;(4) (c) , the regulator must give the partnership an information notice for the decision.\nNothing in this section affects a requirement under this division for the endorsement of an electrical contractor licence issued to a partnership.\n(sec.177-ssec.1) This section applies if— a partnership is the holder of an electrical contractor licence; and there is a change in the membership of the partnership, whether by the death or retirement of a member or the admission of a new member.\n(sec.177-ssec.2) The continuing members of the partnership must, within 30 days after the membership change, give the regulator written notice of the change that includes full information and particulars of the change. Maximum penalty—20 penalty units.\n(sec.177-ssec.3) The notice may state the members’ preference about how the regulator is to act under subsection&#160;(4) .\n(sec.177-ssec.4) After receiving the notice and considering any stated preference, the regulator must— reissue the licence endorsed with information about the membership change; or cancel the licence and issue a new licence; or cancel the licence.\n(sec.177-ssec.5) A licence endorsed by the regulator with the change of the membership of the partnership under subsection&#160;(4) (a) has, subject to the endorsement, continuing effect as the original electrical contractor licence.\n(sec.177-ssec.6) A new licence issued by the regulator under subsection&#160;(4) (b) must be endorsed with a memorandum stating the reasons for the issue of the new licence.\n(sec.177-ssec.7) The regulator may issue a new licence to the partnership under subsection&#160;(4) (b) only if the regulator is satisfied that— the entire business of electrical contracting work carried on by the partnership in Queensland before the membership change is to be carried on by the partnership after the new licence is issued; and the partnership complies with the eligibility requirements for the issue of the new licence.\n(sec.177-ssec.8) If the regulator decides to cancel the licence under subsection&#160;(4) (c) , the regulator must give the partnership an information notice for the decision.\n(sec.177-ssec.9) Nothing in this section affects a requirement under this division for the endorsement of an electrical contractor licence issued to a partnership.\n- (a) a partnership is the holder of an electrical contractor licence; and\n- (b) there is a change in the membership of the partnership, whether by the death or retirement of a member or the admission of a new member.\n- (a) reissue the licence endorsed with information about the membership change; or\n- (b) cancel the licence and issue a new licence; or\n- (c) cancel the licence.\n- (a) the entire business of electrical contracting work carried on by the partnership in Queensland before the membership change is to be carried on by the partnership after the new licence is issued; and\n- (b) the partnership complies with the eligibility requirements for the issue of the new licence.","sortOrder":220},{"sectionNumber":"sec.178","sectionType":"section","heading":"Giving regulator licence if required","content":"### sec.178 Giving regulator licence if required\n\nThe holder of an electrical licence, or another person who has control of the licence, must, if required by the regulator, give the licence to the regulator if the licence—\nhas been cancelled or suspended; or\nhas ended; or\nis required to have anything endorsed on it.\nMaximum penalty—20 penalty units.\n- (a) has been cancelled or suspended; or\n- (b) has ended; or\n- (c) is required to have anything endorsed on it.","sortOrder":221},{"sectionNumber":"sec.179","sectionType":"section","heading":"Replacement of electrical licence","content":"### sec.179 Replacement of electrical licence\n\nIf, on application by the holder of an electrical licence, the regulator is satisfied the licence has been lost, damaged or destroyed, the regulator may issue a replacement licence.\nHowever, if a fixed fee applies to the application, the application must be accompanied by the fixed fee.\n(sec.179-ssec.1) If, on application by the holder of an electrical licence, the regulator is satisfied the licence has been lost, damaged or destroyed, the regulator may issue a replacement licence.\n(sec.179-ssec.2) However, if a fixed fee applies to the application, the application must be accompanied by the fixed fee.","sortOrder":222},{"sectionNumber":"sec.180","sectionType":"section","heading":"Surrender of electrical licence","content":"### sec.180 Surrender of electrical licence\n\nThe holder of an electrical licence may surrender the licence by written notice given to the regulator.","sortOrder":223},{"sectionNumber":"pt.7-div.7","sectionType":"division","heading":"Other matters","content":"## Other matters","sortOrder":224},{"sectionNumber":"sec.181","sectionType":"section","heading":"Testing electrical equipment without electrical licence— Act , s&#160;55","content":"### sec.181 Testing electrical equipment without electrical licence— Act , s&#160;55\n\nFor section&#160;55 (3) (d) of the Act , the following testing is authorised—\nthe testing of electrical equipment by a competent person, if the testing is required under part&#160;6 ;\nthe testing of the works of an electricity entity by a competent person;\na competent person testing protection relay operation that is part of the works of an electricity entity\nthe testing of electrical equipment by a person, other than testing mentioned in paragraph&#160;(a) or (b) , if the testing does not interfere with the integrity of the electrical equipment.\na person testing a safety switch in a domestic electrical installation by operating a test button on the safety switch\na person using an appropriate voltmeter to measure voltage\n- (a) the testing of electrical equipment by a competent person, if the testing is required under part&#160;6 ;\n- (b) the testing of the works of an electricity entity by a competent person; Example for paragraph&#160;(b) — a competent person testing protection relay operation that is part of the works of an electricity entity\n- (c) the testing of electrical equipment by a person, other than testing mentioned in paragraph&#160;(a) or (b) , if the testing does not interfere with the integrity of the electrical equipment. Examples for paragraph&#160;(c) — • a person testing a safety switch in a domestic electrical installation by operating a test button on the safety switch • a person using an appropriate voltmeter to measure voltage\n- • a person testing a safety switch in a domestic electrical installation by operating a test button on the safety switch\n- • a person using an appropriate voltmeter to measure voltage\n- • a person testing a safety switch in a domestic electrical installation by operating a test button on the safety switch\n- • a person using an appropriate voltmeter to measure voltage","sortOrder":225},{"sectionNumber":"sec.182","sectionType":"section","heading":"Operation of trade contractor’s licence","content":"### sec.182 Operation of trade contractor’s licence\n\nThis section applies to a person conducting a business or undertaking that includes the performance of electrical work, other than electrical installation work.\nThe person is taken to be the holder of an electrical contractor licence to the extent that performance of the electrical work is a necessary part of, or is incidental to, the performance of work under a trade contractor’s licence.\nIn this section—\ntrade contractor’s licence means a trade contractor’s licence under the Queensland Building and Construction Commission Regulation 2018 .\n(sec.182-ssec.1) This section applies to a person conducting a business or undertaking that includes the performance of electrical work, other than electrical installation work.\n(sec.182-ssec.2) The person is taken to be the holder of an electrical contractor licence to the extent that performance of the electrical work is a necessary part of, or is incidental to, the performance of work under a trade contractor’s licence.\n(sec.182-ssec.3) In this section— trade contractor’s licence means a trade contractor’s licence under the Queensland Building and Construction Commission Regulation 2018 .","sortOrder":226},{"sectionNumber":"sec.183","sectionType":"section","heading":"Details to be included in register of workers— Act , sch&#160;2 , definition prescribed details","content":"### sec.183 Details to be included in register of workers— Act , sch&#160;2 , definition prescribed details\n\nFor schedule&#160;2 of the Act , definition prescribed details , the details are—\nthe holder’s name; and\neach of the following details about the holder’s electrical work licence—\nthe identifying number of the licence or, if it is an external licence, the number, code or another way of identifying the licence;\nthe class of the licence;\nif the licence is a restricted electrical work licence—the type of electrical work stated on the licence;\nthe conditions or restrictions included in the licence;\nthe day the licence expires;\nif the licence is an external licence—the jurisdiction in which the external licence was issued.\n- (a) the holder’s name; and\n- (b) each of the following details about the holder’s electrical work licence— (i) the identifying number of the licence or, if it is an external licence, the number, code or another way of identifying the licence; (ii) the class of the licence; (iii) if the licence is a restricted electrical work licence—the type of electrical work stated on the licence; (iv) the conditions or restrictions included in the licence; (v) the day the licence expires; (vi) if the licence is an external licence—the jurisdiction in which the external licence was issued.\n- (i) the identifying number of the licence or, if it is an external licence, the number, code or another way of identifying the licence;\n- (ii) the class of the licence;\n- (iii) if the licence is a restricted electrical work licence—the type of electrical work stated on the licence;\n- (iv) the conditions or restrictions included in the licence;\n- (v) the day the licence expires;\n- (vi) if the licence is an external licence—the jurisdiction in which the external licence was issued.\n- (i) the identifying number of the licence or, if it is an external licence, the number, code or another way of identifying the licence;\n- (ii) the class of the licence;\n- (iii) if the licence is a restricted electrical work licence—the type of electrical work stated on the licence;\n- (iv) the conditions or restrictions included in the licence;\n- (v) the day the licence expires;\n- (vi) if the licence is an external licence—the jurisdiction in which the external licence was issued.","sortOrder":227},{"sectionNumber":"sec.184","sectionType":"section","heading":"Requirements about fees— Act , ss&#160;59 , 60 and 61","content":"### sec.184 Requirements about fees— Act , ss&#160;59 , 60 and 61\n\nFor sections&#160;59 (2) , 60 (2) and 61 (2) of the Act , an electrical licence application under part&#160;4 , division&#160;2 of the Act must be accompanied by the fee for the application stated in schedule&#160;9 .","sortOrder":228},{"sectionNumber":"sec.185","sectionType":"section","heading":"Refund of fees","content":"### sec.185 Refund of fees\n\nThis section applies if either of the following applications is refused by the regulator or is withdrawn before it is decided—\nan application for the issue of an electrical licence;\nan application for renewal or reinstatement of an electrical licence.\nThe amount stated in schedule&#160;9 as the administration component of the fee paid for the application must be refunded.\n(sec.185-ssec.1) This section applies if either of the following applications is refused by the regulator or is withdrawn before it is decided— an application for the issue of an electrical licence; an application for renewal or reinstatement of an electrical licence.\n(sec.185-ssec.2) The amount stated in schedule&#160;9 as the administration component of the fee paid for the application must be refunded.\n- (a) an application for the issue of an electrical licence;\n- (b) an application for renewal or reinstatement of an electrical licence.","sortOrder":229},{"sectionNumber":"sec.186","sectionType":"section","heading":"Examinations","content":"### sec.186 Examinations\n\nIn deciding examinations for assessing a person’s competency, or conditions with which a person must comply, the regulator may decide the person must—\nundertake an examination conducted by the regulator; or\nsatisfactorily finish a course of instruction recognised by the regulator during which the student’s performance is assessed; or\nundertake 1 or more examinations, oral or written tests, or practical tests.\nThe examinations and tests may be conducted by—\nthe regulator; or\nan examiner approved by the regulator under section&#160;187 ; or\na registered training organisation.\n(sec.186-ssec.1) In deciding examinations for assessing a person’s competency, or conditions with which a person must comply, the regulator may decide the person must— undertake an examination conducted by the regulator; or satisfactorily finish a course of instruction recognised by the regulator during which the student’s performance is assessed; or undertake 1 or more examinations, oral or written tests, or practical tests.\n(sec.186-ssec.2) The examinations and tests may be conducted by— the regulator; or an examiner approved by the regulator under section&#160;187 ; or a registered training organisation.\n- (a) undertake an examination conducted by the regulator; or\n- (b) satisfactorily finish a course of instruction recognised by the regulator during which the student’s performance is assessed; or\n- (c) undertake 1 or more examinations, oral or written tests, or practical tests.\n- (a) the regulator; or\n- (b) an examiner approved by the regulator under section&#160;187 ; or\n- (c) a registered training organisation.","sortOrder":230},{"sectionNumber":"sec.187","sectionType":"section","heading":"Approved examiners","content":"### sec.187 Approved examiners\n\nThe regulator may approve examiners to conduct examinations or tests required by the regulator.","sortOrder":231},{"sectionNumber":"sec.188","sectionType":"section","heading":"Advertising by licensed electrical contractor","content":"### sec.188 Advertising by licensed electrical contractor\n\nThe holder of an electrical contractor licence who publishes an advertisement about the holder’s business must ensure the advertisement states—\neither—\nthe name under which the holder is licensed; or\nif the holder carries on business under a registered business name—the holder’s registered business name; and\nthat the holder is licensed under the Act ; and\nthe identifying number of the holder’s electrical contractor licence.\nMaximum penalty—40 penalty units.\nIn this section—\nregistered business name means a business name registered under the Business Names Registration Act 2011 (Cwlth) .\n(sec.188-ssec.1) The holder of an electrical contractor licence who publishes an advertisement about the holder’s business must ensure the advertisement states— either— the name under which the holder is licensed; or if the holder carries on business under a registered business name—the holder’s registered business name; and that the holder is licensed under the Act ; and the identifying number of the holder’s electrical contractor licence. Maximum penalty—40 penalty units.\n(sec.188-ssec.2) In this section— registered business name means a business name registered under the Business Names Registration Act 2011 (Cwlth) .\n- (a) either— (i) the name under which the holder is licensed; or (ii) if the holder carries on business under a registered business name—the holder’s registered business name; and\n- (i) the name under which the holder is licensed; or\n- (ii) if the holder carries on business under a registered business name—the holder’s registered business name; and\n- (b) that the holder is licensed under the Act ; and\n- (c) the identifying number of the holder’s electrical contractor licence.\n- (i) the name under which the holder is licensed; or\n- (ii) if the holder carries on business under a registered business name—the holder’s registered business name; and","sortOrder":232},{"sectionNumber":"pt.7-div.8","sectionType":"division","heading":"External licences","content":"## External licences","sortOrder":233},{"sectionNumber":"sec.189","sectionType":"section","heading":"External licence equivalents— Act , s&#160;65","content":"### sec.189 External licence equivalents— Act , s&#160;65\n\nFor section&#160;65 (1) of the Act , an external licence mentioned in column 1 of schedule&#160;4 is equivalent to the electrical work licence stated in column 2 of that schedule for the external licence.","sortOrder":234},{"sectionNumber":"pt.8","sectionType":"part","heading":"Electrical work","content":"# Electrical work","sortOrder":235},{"sectionNumber":"pt.8-div.1","sectionType":"division","heading":"Preliminary","content":"## Preliminary","sortOrder":236},{"sectionNumber":"sec.190","sectionType":"section","heading":"Purpose of part— Act , s&#160;210","content":"### sec.190 Purpose of part— Act , s&#160;210\n\nThis part, other than divisions&#160;3 and 4 , prescribes, for section&#160;210 (2) (c) of the Act , safety and technical requirements for electrical work.\nDivisions&#160;3 and 4 prescribe, for section&#160;210 (2) (d) of the Act , safety and technical requirements for working in contact with, or near to, energised electrical equipment.\n(sec.190-ssec.1) This part, other than divisions&#160;3 and 4 , prescribes, for section&#160;210 (2) (c) of the Act , safety and technical requirements for electrical work.\n(sec.190-ssec.2) Divisions&#160;3 and 4 prescribe, for section&#160;210 (2) (d) of the Act , safety and technical requirements for working in contact with, or near to, energised electrical equipment.","sortOrder":237},{"sectionNumber":"pt.8-div.2","sectionType":"division","heading":"Performing electrical work","content":"## Performing electrical work","sortOrder":238},{"sectionNumber":"sec.191","sectionType":"section","heading":"Licensed electrical worker to ensure electrical installation complies with wiring rules","content":"### sec.191 Licensed electrical worker to ensure electrical installation complies with wiring rules\n\nA licensed electrical worker who performs electrical work on an electrical installation must ensure the installation, to the extent it is affected by the electrical work, complies with the wiring rules.\nMaximum penalty—40 penalty units.","sortOrder":239},{"sectionNumber":"sec.192","sectionType":"section","heading":"Person conducting a business or undertaking to ensure electrical installation complies with requirements","content":"### sec.192 Person conducting a business or undertaking to ensure electrical installation complies with requirements\n\nA person conducting a business or undertaking that performs electrical work on an electrical installation must ensure the installation, to the extent it is affected by the electrical work, complies with—\nif the installation is to be used for construction work—the wiring rules and AS/NZS 3012 (Electrical installations—Construction and demolition sites); or\notherwise—the wiring rules.\nMaximum penalty—40 penalty units.\nSee section&#160;22 (3) of the Act for when the person conducting the business or undertaking is also a worker.\nIn this section—\nconstruction work see the WHS Regulation , section&#160;289 .\n(sec.192-ssec.1) A person conducting a business or undertaking that performs electrical work on an electrical installation must ensure the installation, to the extent it is affected by the electrical work, complies with— if the installation is to be used for construction work—the wiring rules and AS/NZS 3012 (Electrical installations—Construction and demolition sites); or otherwise—the wiring rules. Maximum penalty—40 penalty units. See section&#160;22 (3) of the Act for when the person conducting the business or undertaking is also a worker.\n(sec.192-ssec.2) In this section— construction work see the WHS Regulation , section&#160;289 .\n- (a) if the installation is to be used for construction work—the wiring rules and AS/NZS 3012 (Electrical installations—Construction and demolition sites); or\n- (b) otherwise—the wiring rules.","sortOrder":240},{"sectionNumber":"pt.8-div.3","sectionType":"division","heading":"Electrical work on or near energised electrical equipment","content":"## Electrical work on or near energised electrical equipment","sortOrder":241},{"sectionNumber":"sec.193","sectionType":"section","heading":"Definitions for division","content":"### sec.193 Definitions for division\n\nIn this division—\nelectrical work does not include high voltage live line work.\nnear , in relation to electrical equipment, means within 3m of an exposed energised part of the equipment.\nsafe work method statement , in relation to electrical work on or near energised electrical equipment, means a safe work method statement prepared under section&#160;199 .","sortOrder":242},{"sectionNumber":"sec.194","sectionType":"section","heading":"References to person conducting a business or undertaking","content":"### sec.194 References to person conducting a business or undertaking\n\nIn this division, other than sections&#160;197 , 201 and 202 , a reference to a person conducting a business or undertaking in relation to electrical work is a reference to the person conducting the business or undertaking that is performing the electrical work.","sortOrder":243},{"sectionNumber":"sec.195","sectionType":"section","heading":"Electrical work on or near energised electrical equipment","content":"### sec.195 Electrical work on or near energised electrical equipment\n\nA person conducting a business or undertaking must ensure electrical work is not performed on or near energised electrical equipment unless—\nit is necessary in the interests of health and safety that the work is performed on or near the electrical equipment while the equipment is energised; or\nIt may be necessary that life-saving equipment remain energised and operating while electrical work is performed on or near the equipment.\nit is necessary that the electrical equipment is energised in order for the work to be performed properly; or\nit is necessary for testing the electrical equipment under section&#160;196 (1) ; or\nthere is no reasonable alternative way of carrying out the work.\nIt may be necessary, to avoid widespread outages, that works of an electricity entity remain energised and operating while electrical work is performed on or near the works.\nMaximum penalty—60 penalty units.\nThe electrical work that may be performed under subsection&#160;(1) (a) , (b) or (d) includes testing of the energised electrical equipment.\ndetecting a fault or defect in electrical equipment\nlocating a fault or defect in electrical equipment\nmeasuring the performance of electrical equipment\nverifying compliance with the wiring rules\n(sec.195-ssec.1) A person conducting a business or undertaking must ensure electrical work is not performed on or near energised electrical equipment unless— it is necessary in the interests of health and safety that the work is performed on or near the electrical equipment while the equipment is energised; or It may be necessary that life-saving equipment remain energised and operating while electrical work is performed on or near the equipment. it is necessary that the electrical equipment is energised in order for the work to be performed properly; or it is necessary for testing the electrical equipment under section&#160;196 (1) ; or there is no reasonable alternative way of carrying out the work. It may be necessary, to avoid widespread outages, that works of an electricity entity remain energised and operating while electrical work is performed on or near the works. Maximum penalty—60 penalty units.\n(sec.195-ssec.2) The electrical work that may be performed under subsection&#160;(1) (a) , (b) or (d) includes testing of the energised electrical equipment. detecting a fault or defect in electrical equipment locating a fault or defect in electrical equipment measuring the performance of electrical equipment verifying compliance with the wiring rules\n- (a) it is necessary in the interests of health and safety that the work is performed on or near the electrical equipment while the equipment is energised; or Example— It may be necessary that life-saving equipment remain energised and operating while electrical work is performed on or near the equipment.\n- (b) it is necessary that the electrical equipment is energised in order for the work to be performed properly; or\n- (c) it is necessary for testing the electrical equipment under section&#160;196 (1) ; or\n- (d) there is no reasonable alternative way of carrying out the work. Example— It may be necessary, to avoid widespread outages, that works of an electricity entity remain energised and operating while electrical work is performed on or near the works.\n- • detecting a fault or defect in electrical equipment\n- • locating a fault or defect in electrical equipment\n- • measuring the performance of electrical equipment\n- • verifying compliance with the wiring rules","sortOrder":244},{"sectionNumber":"sec.196","sectionType":"section","heading":"Duty to decide whether equipment is energised","content":"### sec.196 Duty to decide whether equipment is energised\n\nA person conducting a business or undertaking must ensure that, before electrical work is performed on or near electrical equipment, the equipment is tested by a competent person to decide whether or not it is energised.\nMaximum penalty—60 penalty units.\nSee section&#160;195 (1) (c) in relation to carrying out testing on electrical equipment for this section.\nSee section&#160;203 for how testing is to be carried out.\nThe person conducting the business or undertaking must ensure—\neach exposed part is treated as energised until it is isolated and found not to be energised; and\neach high voltage exposed part is earthed after being de-energised.\nMaximum penalty—60 penalty units.\n(sec.196-ssec.1) A person conducting a business or undertaking must ensure that, before electrical work is performed on or near electrical equipment, the equipment is tested by a competent person to decide whether or not it is energised. Maximum penalty—60 penalty units. See section&#160;195 (1) (c) in relation to carrying out testing on electrical equipment for this section. See section&#160;203 for how testing is to be carried out.\n(sec.196-ssec.2) The person conducting the business or undertaking must ensure— each exposed part is treated as energised until it is isolated and found not to be energised; and each high voltage exposed part is earthed after being de-energised. Maximum penalty—60 penalty units.\n- 1 See section&#160;195 (1) (c) in relation to carrying out testing on electrical equipment for this section.\n- 2 See section&#160;203 for how testing is to be carried out.\n- (a) each exposed part is treated as energised until it is isolated and found not to be energised; and\n- (b) each high voltage exposed part is earthed after being de-energised.","sortOrder":245},{"sectionNumber":"sec.197","sectionType":"section","heading":"De-energised equipment must not be inadvertently re-energised","content":"### sec.197 De-energised equipment must not be inadvertently re-energised\n\nA person conducting a business or undertaking must ensure electrical equipment that has been de-energised to allow electrical work to be performed on or near the equipment is not inadvertently re-energised while the work is being performed.\nMaximum penalty—60 penalty units.","sortOrder":246},{"sectionNumber":"sec.198","sectionType":"section","heading":"Licensed electrical worker to take precautions to prevent de-energised equipment from being inadvertently re-energised","content":"### sec.198 Licensed electrical worker to take precautions to prevent de-energised equipment from being inadvertently re-energised\n\nThis section applies if—\na licensed electrical worker is performing electrical work; and\nto perform the work, the worker has de-energised, or otherwise isolated from electricity, an item of electrical equipment that—\nis the subject of the electrical work; or\nis near where the electrical work is being performed; and\nto de-energise, or otherwise isolate, the item of electrical equipment, the licensed electrical worker has operated a device; and\nwhile the worker is performing the work, the worker does not have the device under the worker’s sole effective control.\nThe licensed electrical worker must ensure both of the following—\nthere is a warning sign attached to the device, in a prominent position, that is suitable in the circumstances, having regard to AS 1319 (Safety signs for the occupational environment);\nthe device—\nis locked when in the open position; or\nusing a personal lock to lock an air-conditioner isolator in the open position\nusing a locking device that stops a miniature circuit breaker from being closed\nplacing a lockable shroud on the male inlet plug of electrical equipment\nis prevented from being accidentally closed.\ndisengaging a circuit breaker so the circuit breaker is separated from the busbars\nremoving circuit cables from a fuse or circuit breaker\ninsertion of a mechanical restriction\nMaximum penalty—40 penalty units.\nIn this section—\ndevice means a circuit breaker, disconnection point, fuse or switch.\n(sec.198-ssec.1) This section applies if— a licensed electrical worker is performing electrical work; and to perform the work, the worker has de-energised, or otherwise isolated from electricity, an item of electrical equipment that— is the subject of the electrical work; or is near where the electrical work is being performed; and to de-energise, or otherwise isolate, the item of electrical equipment, the licensed electrical worker has operated a device; and while the worker is performing the work, the worker does not have the device under the worker’s sole effective control.\n(sec.198-ssec.2) The licensed electrical worker must ensure both of the following— there is a warning sign attached to the device, in a prominent position, that is suitable in the circumstances, having regard to AS 1319 (Safety signs for the occupational environment); the device— is locked when in the open position; or using a personal lock to lock an air-conditioner isolator in the open position using a locking device that stops a miniature circuit breaker from being closed placing a lockable shroud on the male inlet plug of electrical equipment is prevented from being accidentally closed. disengaging a circuit breaker so the circuit breaker is separated from the busbars removing circuit cables from a fuse or circuit breaker insertion of a mechanical restriction Maximum penalty—40 penalty units.\n(sec.198-ssec.3) In this section— device means a circuit breaker, disconnection point, fuse or switch.\n- (a) a licensed electrical worker is performing electrical work; and\n- (b) to perform the work, the worker has de-energised, or otherwise isolated from electricity, an item of electrical equipment that— (i) is the subject of the electrical work; or (ii) is near where the electrical work is being performed; and\n- (i) is the subject of the electrical work; or\n- (ii) is near where the electrical work is being performed; and\n- (c) to de-energise, or otherwise isolate, the item of electrical equipment, the licensed electrical worker has operated a device; and\n- (d) while the worker is performing the work, the worker does not have the device under the worker’s sole effective control.\n- (i) is the subject of the electrical work; or\n- (ii) is near where the electrical work is being performed; and\n- (a) there is a warning sign attached to the device, in a prominent position, that is suitable in the circumstances, having regard to AS 1319 (Safety signs for the occupational environment);\n- (b) the device— (i) is locked when in the open position; or Examples for subparagraph&#160;(i) — • using a personal lock to lock an air-conditioner isolator in the open position • using a locking device that stops a miniature circuit breaker from being closed • placing a lockable shroud on the male inlet plug of electrical equipment (ii) is prevented from being accidentally closed. Examples for subparagraph&#160;(ii) — • disengaging a circuit breaker so the circuit breaker is separated from the busbars • removing circuit cables from a fuse or circuit breaker • insertion of a mechanical restriction\n- (i) is locked when in the open position; or Examples for subparagraph&#160;(i) — • using a personal lock to lock an air-conditioner isolator in the open position • using a locking device that stops a miniature circuit breaker from being closed • placing a lockable shroud on the male inlet plug of electrical equipment\n- • using a personal lock to lock an air-conditioner isolator in the open position\n- • using a locking device that stops a miniature circuit breaker from being closed\n- • placing a lockable shroud on the male inlet plug of electrical equipment\n- (ii) is prevented from being accidentally closed. Examples for subparagraph&#160;(ii) — • disengaging a circuit breaker so the circuit breaker is separated from the busbars • removing circuit cables from a fuse or circuit breaker • insertion of a mechanical restriction\n- • disengaging a circuit breaker so the circuit breaker is separated from the busbars\n- • removing circuit cables from a fuse or circuit breaker\n- • insertion of a mechanical restriction\n- (i) is locked when in the open position; or Examples for subparagraph&#160;(i) — • using a personal lock to lock an air-conditioner isolator in the open position • using a locking device that stops a miniature circuit breaker from being closed • placing a lockable shroud on the male inlet plug of electrical equipment\n- • using a personal lock to lock an air-conditioner isolator in the open position\n- • using a locking device that stops a miniature circuit breaker from being closed\n- • placing a lockable shroud on the male inlet plug of electrical equipment\n- (ii) is prevented from being accidentally closed. Examples for subparagraph&#160;(ii) — • disengaging a circuit breaker so the circuit breaker is separated from the busbars • removing circuit cables from a fuse or circuit breaker • insertion of a mechanical restriction\n- • disengaging a circuit breaker so the circuit breaker is separated from the busbars\n- • removing circuit cables from a fuse or circuit breaker\n- • insertion of a mechanical restriction\n- • using a personal lock to lock an air-conditioner isolator in the open position\n- • using a locking device that stops a miniature circuit breaker from being closed\n- • placing a lockable shroud on the male inlet plug of electrical equipment\n- • disengaging a circuit breaker so the circuit breaker is separated from the busbars\n- • removing circuit cables from a fuse or circuit breaker\n- • insertion of a mechanical restriction","sortOrder":247},{"sectionNumber":"sec.199","sectionType":"section","heading":"Preliminary steps","content":"### sec.199 Preliminary steps\n\nBefore electrical work on or near energised electrical equipment commences at a workplace, the person conducting the business or undertaking must ensure—\na competent person conducts a risk assessment in relation to the proposed electrical work and records the results of the risk assessment; and\nSee section&#160;8 in relation to risk assessments for a class of hazards, tasks, things or circumstances.\na safe work method statement is prepared for the proposed electrical work that complies with section&#160;200 ; and\nthe area where the electrical work is to be performed is clear of obstructions to allow for easy access and exit; and\nthe point at which the electrical equipment can be disconnected or isolated from its electricity supply is—\nclearly marked or labelled; and\nclear of obstructions to allow for easy access and exit by the worker who is to perform the electrical work or any other competent person; and\ncapable of being operated quickly; and\nthe person authorises the electrical work after consulting with the person with management or control of the workplace.\nMaximum penalty—60 penalty units.\nSubsection&#160;(1) (c) does not apply in relation to—\nelectrical work on or near electrical equipment if—\nthe work is to be performed on the supply side of the main switch on the main switchboard for the equipment; and\nthe point at which the equipment can be disconnected from its electricity supply is not reasonably accessible from the work location; or\nelectric line work.\n(sec.199-ssec.1) Before electrical work on or near energised electrical equipment commences at a workplace, the person conducting the business or undertaking must ensure— a competent person conducts a risk assessment in relation to the proposed electrical work and records the results of the risk assessment; and See section&#160;8 in relation to risk assessments for a class of hazards, tasks, things or circumstances. a safe work method statement is prepared for the proposed electrical work that complies with section&#160;200 ; and the area where the electrical work is to be performed is clear of obstructions to allow for easy access and exit; and the point at which the electrical equipment can be disconnected or isolated from its electricity supply is— clearly marked or labelled; and clear of obstructions to allow for easy access and exit by the worker who is to perform the electrical work or any other competent person; and capable of being operated quickly; and the person authorises the electrical work after consulting with the person with management or control of the workplace. Maximum penalty—60 penalty units.\n(sec.199-ssec.2) Subsection&#160;(1) (c) does not apply in relation to— electrical work on or near electrical equipment if— the work is to be performed on the supply side of the main switch on the main switchboard for the equipment; and the point at which the equipment can be disconnected from its electricity supply is not reasonably accessible from the work location; or electric line work.\n- (a) a competent person conducts a risk assessment in relation to the proposed electrical work and records the results of the risk assessment; and Note— See section&#160;8 in relation to risk assessments for a class of hazards, tasks, things or circumstances.\n- (b) a safe work method statement is prepared for the proposed electrical work that complies with section&#160;200 ; and\n- (c) the area where the electrical work is to be performed is clear of obstructions to allow for easy access and exit; and\n- (d) the point at which the electrical equipment can be disconnected or isolated from its electricity supply is— (i) clearly marked or labelled; and (ii) clear of obstructions to allow for easy access and exit by the worker who is to perform the electrical work or any other competent person; and (iii) capable of being operated quickly; and\n- (i) clearly marked or labelled; and\n- (ii) clear of obstructions to allow for easy access and exit by the worker who is to perform the electrical work or any other competent person; and\n- (iii) capable of being operated quickly; and\n- (e) the person authorises the electrical work after consulting with the person with management or control of the workplace.\n- (i) clearly marked or labelled; and\n- (ii) clear of obstructions to allow for easy access and exit by the worker who is to perform the electrical work or any other competent person; and\n- (iii) capable of being operated quickly; and\n- (a) electrical work on or near electrical equipment if— (i) the work is to be performed on the supply side of the main switch on the main switchboard for the equipment; and (ii) the point at which the equipment can be disconnected from its electricity supply is not reasonably accessible from the work location; or\n- (i) the work is to be performed on the supply side of the main switch on the main switchboard for the equipment; and\n- (ii) the point at which the equipment can be disconnected from its electricity supply is not reasonably accessible from the work location; or\n- (b) electric line work.\n- (i) the work is to be performed on the supply side of the main switch on the main switchboard for the equipment; and\n- (ii) the point at which the equipment can be disconnected from its electricity supply is not reasonably accessible from the work location; or","sortOrder":248},{"sectionNumber":"sec.200","sectionType":"section","heading":"Contents of safe work method statement","content":"### sec.200 Contents of safe work method statement\n\nFor section&#160;199 (1) (b) , the safe work method statement must—\nidentify the proposed electrical work; and\nidentify hazards associated with the proposed electrical work and risks associated with those hazards; and\ndescribe the measures to be implemented to control the risks; and\npreventing persons from accessing an area where electrical work is being carried out on or near energised electrical equipment if the persons are not needed for the performance of the work\ndescribe how the measures mentioned in paragraph&#160;(c) are to be implemented, monitored and reviewed.\n- (a) identify the proposed electrical work; and\n- (b) identify hazards associated with the proposed electrical work and risks associated with those hazards; and\n- (c) describe the measures to be implemented to control the risks; and Example of a measure to control risks— preventing persons from accessing an area where electrical work is being carried out on or near energised electrical equipment if the persons are not needed for the performance of the work\n- (d) describe how the measures mentioned in paragraph&#160;(c) are to be implemented, monitored and reviewed.","sortOrder":249},{"sectionNumber":"sec.201","sectionType":"section","heading":"Unauthorised access to electrical equipment while work performed","content":"### sec.201 Unauthorised access to electrical equipment while work performed\n\nA person conducting a business or undertaking must ensure that only persons authorised by the person conducting the business or undertaking enter the immediate area in which electrical work is being performed on or near energised electrical equipment.\nMaximum penalty—60 penalty units.","sortOrder":250},{"sectionNumber":"sec.202","sectionType":"section","heading":"Contact with electrical equipment while work performed","content":"### sec.202 Contact with electrical equipment while work performed\n\nA person conducting a business or undertaking must ensure that, while electrical work is being performed on or near energised electrical equipment, all persons are prevented from creating an electrical risk by inadvertently making contact with an exposed energised part of the equipment.\nMaximum penalty—60 penalty units.","sortOrder":251},{"sectionNumber":"sec.203","sectionType":"section","heading":"How work is to be performed","content":"### sec.203 How work is to be performed\n\nA person conducting a business or undertaking must ensure electrical work on or near energised electrical equipment is performed—\nby a competent person who has tools, testing equipment and personal protective equipment that—\nare suitable for the work; and\nhave been properly tested; and\nare in good working order; and\nin accordance with a safe work method statement prepared for the work; and\nsubject to subsection&#160;(3) , observed by a safety observer.\nMaximum penalty—60 penalty units.\nThe person conducting the business or undertaking must ensure, so far as is reasonably practicable, that the person who performs the electrical work uses the tools, testing equipment and personal protective equipment properly.\nMaximum penalty—60 penalty units.\nA safety observer is not required if—\nthe work consists only of testing; and\na risk assessment conducted under section&#160;199 (1) (a) shows there is no serious risk associated with the proposed work.\nA safety observer is not required to observe the testing of the polarity of an installed outlet if a risk assessment shows there is no serious risk in performing the work.\n(sec.203-ssec.1) A person conducting a business or undertaking must ensure electrical work on or near energised electrical equipment is performed— by a competent person who has tools, testing equipment and personal protective equipment that— are suitable for the work; and have been properly tested; and are in good working order; and in accordance with a safe work method statement prepared for the work; and subject to subsection&#160;(3) , observed by a safety observer. Maximum penalty—60 penalty units.\n(sec.203-ssec.2) The person conducting the business or undertaking must ensure, so far as is reasonably practicable, that the person who performs the electrical work uses the tools, testing equipment and personal protective equipment properly. Maximum penalty—60 penalty units.\n(sec.203-ssec.3) A safety observer is not required if— the work consists only of testing; and a risk assessment conducted under section&#160;199 (1) (a) shows there is no serious risk associated with the proposed work. A safety observer is not required to observe the testing of the polarity of an installed outlet if a risk assessment shows there is no serious risk in performing the work.\n- (a) by a competent person who has tools, testing equipment and personal protective equipment that— (i) are suitable for the work; and (ii) have been properly tested; and (iii) are in good working order; and\n- (i) are suitable for the work; and\n- (ii) have been properly tested; and\n- (iii) are in good working order; and\n- (b) in accordance with a safe work method statement prepared for the work; and\n- (c) subject to subsection&#160;(3) , observed by a safety observer.\n- (i) are suitable for the work; and\n- (ii) have been properly tested; and\n- (iii) are in good working order; and\n- (a) the work consists only of testing; and\n- (b) a risk assessment conducted under section&#160;199 (1) (a) shows there is no serious risk associated with the proposed work.","sortOrder":252},{"sectionNumber":"sec.204","sectionType":"section","heading":"Record keeping","content":"### sec.204 Record keeping\n\nThis section applies to a person conducting a business or undertaking in relation to—\na risk assessment the person is required to conduct under section&#160;199 (1) (a) ; and\na safe work method statement the person is required to prepare under section&#160;199 (1) (b) .\nSubject to subsection&#160;(3) , the person must keep—\na copy of the risk assessment until at least 28 days after the work to which it relates is completed; and\na copy of the safe work method statement until the work to which it relates is completed.\nMaximum penalty—\nfor an individual—12 1 / 2 penalty units; or\nfor a body corporate—60 penalty units.\nHowever, if a serious electrical incident or dangerous electrical event occurs in connection with the work to which the risk assessment and safe work method statement relate, the person must keep the risk assessment and safe work method statement for at least 2 years after the incident occurs.\nMaximum penalty—\nfor an individual—12 1 / 2 penalty units; or\nfor a body corporate—60 penalty units.\nThe person must ensure that, for the period for which the risk assessment or safe work method statement must be kept under this section, a copy is readily accessible to any worker engaged by the person to carry out the work to which the risk assessment or safe work method statement relates.\nMaximum penalty—36 penalty units.\nThe person must ensure that, for the period for which the risk assessment or safe work method statement must be kept under this section, a copy is available for inspection under the Act .\nMaximum penalty—\nfor an individual—12 1 / 2 penalty units; or\nfor a body corporate—60 penalty units.\n(sec.204-ssec.1) This section applies to a person conducting a business or undertaking in relation to— a risk assessment the person is required to conduct under section&#160;199 (1) (a) ; and a safe work method statement the person is required to prepare under section&#160;199 (1) (b) .\n(sec.204-ssec.2) Subject to subsection&#160;(3) , the person must keep— a copy of the risk assessment until at least 28 days after the work to which it relates is completed; and a copy of the safe work method statement until the work to which it relates is completed. Maximum penalty— for an individual—12 1 / 2 penalty units; or for a body corporate—60 penalty units.\n(sec.204-ssec.3) However, if a serious electrical incident or dangerous electrical event occurs in connection with the work to which the risk assessment and safe work method statement relate, the person must keep the risk assessment and safe work method statement for at least 2 years after the incident occurs. Maximum penalty— for an individual—12 1 / 2 penalty units; or for a body corporate—60 penalty units.\n(sec.204-ssec.4) The person must ensure that, for the period for which the risk assessment or safe work method statement must be kept under this section, a copy is readily accessible to any worker engaged by the person to carry out the work to which the risk assessment or safe work method statement relates. Maximum penalty—36 penalty units.\n(sec.204-ssec.5) The person must ensure that, for the period for which the risk assessment or safe work method statement must be kept under this section, a copy is available for inspection under the Act . Maximum penalty— for an individual—12 1 / 2 penalty units; or for a body corporate—60 penalty units.\n- (a) a risk assessment the person is required to conduct under section&#160;199 (1) (a) ; and\n- (b) a safe work method statement the person is required to prepare under section&#160;199 (1) (b) .\n- (a) a copy of the risk assessment until at least 28 days after the work to which it relates is completed; and\n- (b) a copy of the safe work method statement until the work to which it relates is completed.\n- (a) for an individual—12 1 / 2 penalty units; or\n- (b) for a body corporate—60 penalty units.\n- (a) for an individual—12 1 / 2 penalty units; or\n- (b) for a body corporate—60 penalty units.\n- (a) for an individual—12 1 / 2 penalty units; or\n- (b) for a body corporate—60 penalty units.","sortOrder":253},{"sectionNumber":"pt.8-div.4","sectionType":"division","heading":"High voltage live line work","content":"## High voltage live line work","sortOrder":254},{"sectionNumber":"sec.205","sectionType":"section","heading":"Performance of high voltage live line work","content":"### sec.205 Performance of high voltage live line work\n\nA person (a worker ) must not perform high voltage live line work unless the worker performs the work under—\na written authorisation from the person in control of the electrical equipment the subject of the work; and\na high voltage live line work management plan prepared under section&#160;206 .\nMaximum penalty—40 penalty units.\nA person in control of electrical equipment may authorise a worker’s performance of high voltage live line work in relation to the electrical equipment only if—\nthe person in control is satisfied the worker—\nhas successfully finished an appropriate course of training; and\nhas been assessed by the provider of the course as competent to perform the work; and\nthe written authorisation states the voltages of the electrical equipment on which the high voltage live line work may be performed by the worker.\nSubsection&#160;(4) applies if the written authorisation provides for the performance of work on more than 1 occasion.\nThe person in control of electrical equipment must, while the authorisation is in effect, cause the worker to be regularly assessed to ensure the worker remains competent to perform the high voltage live line work.\nMaximum penalty—40 penalty units.\n(sec.205-ssec.1) A person (a worker ) must not perform high voltage live line work unless the worker performs the work under— a written authorisation from the person in control of the electrical equipment the subject of the work; and a high voltage live line work management plan prepared under section&#160;206 . Maximum penalty—40 penalty units.\n(sec.205-ssec.2) A person in control of electrical equipment may authorise a worker’s performance of high voltage live line work in relation to the electrical equipment only if— the person in control is satisfied the worker— has successfully finished an appropriate course of training; and has been assessed by the provider of the course as competent to perform the work; and the written authorisation states the voltages of the electrical equipment on which the high voltage live line work may be performed by the worker.\n(sec.205-ssec.3) Subsection&#160;(4) applies if the written authorisation provides for the performance of work on more than 1 occasion.\n(sec.205-ssec.4) The person in control of electrical equipment must, while the authorisation is in effect, cause the worker to be regularly assessed to ensure the worker remains competent to perform the high voltage live line work. Maximum penalty—40 penalty units.\n- (a) a written authorisation from the person in control of the electrical equipment the subject of the work; and\n- (b) a high voltage live line work management plan prepared under section&#160;206 .\n- (a) the person in control is satisfied the worker— (i) has successfully finished an appropriate course of training; and (ii) has been assessed by the provider of the course as competent to perform the work; and\n- (i) has successfully finished an appropriate course of training; and\n- (ii) has been assessed by the provider of the course as competent to perform the work; and\n- (b) the written authorisation states the voltages of the electrical equipment on which the high voltage live line work may be performed by the worker.\n- (i) has successfully finished an appropriate course of training; and\n- (ii) has been assessed by the provider of the course as competent to perform the work; and","sortOrder":255},{"sectionNumber":"sec.206","sectionType":"section","heading":"Preparation of high voltage live line work management plan","content":"### sec.206 Preparation of high voltage live line work management plan\n\nFor section&#160;205 (1) (b) , a high voltage live line work management plan is a plan for the performance of high voltage live line work that includes procedures developed in accordance with the following standards—\nAS 5804.1 (High-voltage live working—General);\nAS 5804.2 (High-voltage live working—Glove and barrier work);\nAS 5804.3 (High-voltage live working—Stick work);\nAS 5804.4 (High-voltage live working—Barehand work).\nThe high voltage live line work management plan must be—\ndeveloped in conjunction with each of the following—\nrepresentatives of workers who are to perform high voltage live line work under the plan;\nif the high voltage live line work involves the works of an electricity entity—the electricity entity;\nother persons who might reasonably be expected to have an interest in the performance of the high voltage live line work; and\napproved by a person who—\nis an electrical engineer who has expertise as a professional engineer in the performance of high voltage live line work; or\nhas expertise the person in control of the electrical equipment the subject of the high voltage live line work decides is equivalent to the expertise mentioned in subparagraph&#160;(i) .\n(sec.206-ssec.1) For section&#160;205 (1) (b) , a high voltage live line work management plan is a plan for the performance of high voltage live line work that includes procedures developed in accordance with the following standards— AS 5804.1 (High-voltage live working—General); AS 5804.2 (High-voltage live working—Glove and barrier work); AS 5804.3 (High-voltage live working—Stick work); AS 5804.4 (High-voltage live working—Barehand work).\n(sec.206-ssec.2) The high voltage live line work management plan must be— developed in conjunction with each of the following— representatives of workers who are to perform high voltage live line work under the plan; if the high voltage live line work involves the works of an electricity entity—the electricity entity; other persons who might reasonably be expected to have an interest in the performance of the high voltage live line work; and approved by a person who— is an electrical engineer who has expertise as a professional engineer in the performance of high voltage live line work; or has expertise the person in control of the electrical equipment the subject of the high voltage live line work decides is equivalent to the expertise mentioned in subparagraph&#160;(i) .\n- (a) AS 5804.1 (High-voltage live working—General);\n- (b) AS 5804.2 (High-voltage live working—Glove and barrier work);\n- (c) AS 5804.3 (High-voltage live working—Stick work);\n- (d) AS 5804.4 (High-voltage live working—Barehand work).\n- (a) developed in conjunction with each of the following— (i) representatives of workers who are to perform high voltage live line work under the plan; (ii) if the high voltage live line work involves the works of an electricity entity—the electricity entity; (iii) other persons who might reasonably be expected to have an interest in the performance of the high voltage live line work; and\n- (i) representatives of workers who are to perform high voltage live line work under the plan;\n- (ii) if the high voltage live line work involves the works of an electricity entity—the electricity entity;\n- (iii) other persons who might reasonably be expected to have an interest in the performance of the high voltage live line work; and\n- (b) approved by a person who— (i) is an electrical engineer who has expertise as a professional engineer in the performance of high voltage live line work; or (ii) has expertise the person in control of the electrical equipment the subject of the high voltage live line work decides is equivalent to the expertise mentioned in subparagraph&#160;(i) .\n- (i) is an electrical engineer who has expertise as a professional engineer in the performance of high voltage live line work; or\n- (ii) has expertise the person in control of the electrical equipment the subject of the high voltage live line work decides is equivalent to the expertise mentioned in subparagraph&#160;(i) .\n- (i) representatives of workers who are to perform high voltage live line work under the plan;\n- (ii) if the high voltage live line work involves the works of an electricity entity—the electricity entity;\n- (iii) other persons who might reasonably be expected to have an interest in the performance of the high voltage live line work; and\n- (i) is an electrical engineer who has expertise as a professional engineer in the performance of high voltage live line work; or\n- (ii) has expertise the person in control of the electrical equipment the subject of the high voltage live line work decides is equivalent to the expertise mentioned in subparagraph&#160;(i) .","sortOrder":256},{"sectionNumber":"pt.8-div.5","sectionType":"division","heading":"Testing of work","content":"## Testing of work","sortOrder":257},{"sectionNumber":"sec.207","sectionType":"section","heading":"Testing of electrical equipment after electrical work","content":"### sec.207 Testing of electrical equipment after electrical work\n\nThis section applies if electrical work is performed on electrical equipment.\nA person who performs all or part of the electrical work, and is responsible for making the electrical equipment ready to connect to a source of electricity for use for its intended purpose, must ensure the electrical equipment is tested as required under subsections&#160;(6) and (7) .\nMaximum penalty—40 penalty units.\nIf a training person performs the work mentioned in subsection&#160;(2) under the supervision of a licensed electrical worker, subsection&#160;(2) applies to the licensed electrical worker and not the training person as if the licensed electrical worker were performing the work.\nA licensed electrical contractor or electricity entity who performs the electrical work of connecting the electrical equipment to a source of electricity for use for its intended purpose must ensure the electrical equipment is tested as required under subsections&#160;(6) and (7) .\nMaximum penalty—40 penalty units.\nSubsection&#160;(4) does not require a distribution entity to ensure the testing of the electrical equipment if—\nthe electrical work is, or is part of, electrical work performed on an electrical installation; and\na licensed electrical contractor has given the distribution entity a notice under section&#160;228 about the testing of the electrical work performed on the electrical installation.\nThe testing of the electrical equipment must be directed at ensuring the electrical equipment, to the extent it is affected by the electrical work, is electrically safe.\nIf the electrical equipment is energised for testing, the person who performs the test must ensure persons not necessary for the testing are electrically safe.\n(sec.207-ssec.1) This section applies if electrical work is performed on electrical equipment.\n(sec.207-ssec.2) A person who performs all or part of the electrical work, and is responsible for making the electrical equipment ready to connect to a source of electricity for use for its intended purpose, must ensure the electrical equipment is tested as required under subsections&#160;(6) and (7) . Maximum penalty—40 penalty units.\n(sec.207-ssec.3) If a training person performs the work mentioned in subsection&#160;(2) under the supervision of a licensed electrical worker, subsection&#160;(2) applies to the licensed electrical worker and not the training person as if the licensed electrical worker were performing the work.\n(sec.207-ssec.4) A licensed electrical contractor or electricity entity who performs the electrical work of connecting the electrical equipment to a source of electricity for use for its intended purpose must ensure the electrical equipment is tested as required under subsections&#160;(6) and (7) . Maximum penalty—40 penalty units.\n(sec.207-ssec.5) Subsection&#160;(4) does not require a distribution entity to ensure the testing of the electrical equipment if— the electrical work is, or is part of, electrical work performed on an electrical installation; and a licensed electrical contractor has given the distribution entity a notice under section&#160;228 about the testing of the electrical work performed on the electrical installation.\n(sec.207-ssec.6) The testing of the electrical equipment must be directed at ensuring the electrical equipment, to the extent it is affected by the electrical work, is electrically safe.\n(sec.207-ssec.7) If the electrical equipment is energised for testing, the person who performs the test must ensure persons not necessary for the testing are electrically safe.\n- (a) the electrical work is, or is part of, electrical work performed on an electrical installation; and\n- (b) a licensed electrical contractor has given the distribution entity a notice under section&#160;228 about the testing of the electrical work performed on the electrical installation.","sortOrder":258},{"sectionNumber":"sec.208","sectionType":"section","heading":"Certificate of testing and safety","content":"### sec.208 Certificate of testing and safety\n\nThis section applies if a licensed electrical contractor performs electrical work that must be tested under this division.\nThe contractor must, as soon as practicable after testing the electrical work, ensure the person for whom the electrical work was performed is given a certificate complying with this section.\nMaximum penalty—40 penalty units.\nThe certificate must state the following—\nthe name and address of the person for whom the work was performed;\nthe electrical equipment tested;\nthe day the electrical equipment was tested;\nthe identifying number of the electrical contractor licence under which the electrical equipment was tested.\nThe certificate must certify that the electrical equipment, to the extent it is affected by the electrical work, is electrically safe.\nA licensed electrical contractor must keep a copy of a certificate given under this section for at least 5 years after the certificate is given.\nMaximum penalty—20 penalty units.\n(sec.208-ssec.1) This section applies if a licensed electrical contractor performs electrical work that must be tested under this division.\n(sec.208-ssec.2) The contractor must, as soon as practicable after testing the electrical work, ensure the person for whom the electrical work was performed is given a certificate complying with this section. Maximum penalty—40 penalty units.\n(sec.208-ssec.3) The certificate must state the following— the name and address of the person for whom the work was performed; the electrical equipment tested; the day the electrical equipment was tested; the identifying number of the electrical contractor licence under which the electrical equipment was tested.\n(sec.208-ssec.4) The certificate must certify that the electrical equipment, to the extent it is affected by the electrical work, is electrically safe.\n(sec.208-ssec.5) A licensed electrical contractor must keep a copy of a certificate given under this section for at least 5 years after the certificate is given. Maximum penalty—20 penalty units.\n- (a) the name and address of the person for whom the work was performed;\n- (b) the electrical equipment tested;\n- (c) the day the electrical equipment was tested;\n- (d) the identifying number of the electrical contractor licence under which the electrical equipment was tested.","sortOrder":259},{"sectionNumber":"pt.8-div.6","sectionType":"division","heading":"Replacement of appliances","content":"## Replacement of appliances","sortOrder":260},{"sectionNumber":"sec.209","sectionType":"section","heading":"Circumstances for replacing similar appliance— Act , s&#160;19","content":"### sec.209 Circumstances for replacing similar appliance— Act , s&#160;19\n\nFor section&#160;19 (1) (b) of the Act , the following circumstances are prescribed—\nthe similar appliance has—\na voltage rating that is the same as the voltage rating of the appliance included in the electrical installation (the old appliance ); and\na current rating that is not greater than the current rating of the old appliance; and\na power rating that is not greater than the power rating of the old appliance; and\nthe same way of performing the function as the old appliance; and\nelectrical characteristics that are the same as or better than the electrical characteristics of the old appliance;\ningress protection rating, insulation, earthing, operating temperature\nthe electrical installation is not located in a hazardous area.\nIn this section—\ncurrent rating , for an appliance, means the current stated on the appliance as the current the appliance consumes when operating under normal circumstances.\npower rating , for an appliance, means the power stated on the appliance as the power the appliance consumes when operating under normal circumstances.\nvoltage rating , for an appliance, means the voltage stated on the appliance as the voltage the appliance is designed to be supplied with to operate under normal conditions.\n(sec.209-ssec.1) For section&#160;19 (1) (b) of the Act , the following circumstances are prescribed— the similar appliance has— a voltage rating that is the same as the voltage rating of the appliance included in the electrical installation (the old appliance ); and a current rating that is not greater than the current rating of the old appliance; and a power rating that is not greater than the power rating of the old appliance; and the same way of performing the function as the old appliance; and electrical characteristics that are the same as or better than the electrical characteristics of the old appliance; ingress protection rating, insulation, earthing, operating temperature the electrical installation is not located in a hazardous area.\n(sec.209-ssec.2) In this section— current rating , for an appliance, means the current stated on the appliance as the current the appliance consumes when operating under normal circumstances. power rating , for an appliance, means the power stated on the appliance as the power the appliance consumes when operating under normal circumstances. voltage rating , for an appliance, means the voltage stated on the appliance as the voltage the appliance is designed to be supplied with to operate under normal conditions.\n- (a) the similar appliance has— (i) a voltage rating that is the same as the voltage rating of the appliance included in the electrical installation (the old appliance ); and (ii) a current rating that is not greater than the current rating of the old appliance; and (iii) a power rating that is not greater than the power rating of the old appliance; and (iv) the same way of performing the function as the old appliance; and (v) electrical characteristics that are the same as or better than the electrical characteristics of the old appliance; Examples of electrical characteristics— ingress protection rating, insulation, earthing, operating temperature\n- (i) a voltage rating that is the same as the voltage rating of the appliance included in the electrical installation (the old appliance ); and\n- (ii) a current rating that is not greater than the current rating of the old appliance; and\n- (iii) a power rating that is not greater than the power rating of the old appliance; and\n- (iv) the same way of performing the function as the old appliance; and\n- (v) electrical characteristics that are the same as or better than the electrical characteristics of the old appliance; Examples of electrical characteristics— ingress protection rating, insulation, earthing, operating temperature\n- (b) the electrical installation is not located in a hazardous area.\n- (i) a voltage rating that is the same as the voltage rating of the appliance included in the electrical installation (the old appliance ); and\n- (ii) a current rating that is not greater than the current rating of the old appliance; and\n- (iii) a power rating that is not greater than the power rating of the old appliance; and\n- (iv) the same way of performing the function as the old appliance; and\n- (v) electrical characteristics that are the same as or better than the electrical characteristics of the old appliance; Examples of electrical characteristics— ingress protection rating, insulation, earthing, operating temperature","sortOrder":261},{"sectionNumber":"pt.8-div.7","sectionType":"division","heading":"Other requirements","content":"## Other requirements","sortOrder":262},{"sectionNumber":"sec.210","sectionType":"section","heading":"Electrical equipment with serious defect not to be connected to electricity source","content":"### sec.210 Electrical equipment with serious defect not to be connected to electricity source\n\nIf an item of electrical equipment has a serious defect, a licensed electrical worker must not connect the equipment to a source of electricity for use for its intended purpose.\nMaximum penalty—40 penalty units.","sortOrder":263},{"sectionNumber":"sec.211","sectionType":"section","heading":"Rescue and resuscitation training","content":"### sec.211 Rescue and resuscitation training\n\nA person conducting a business or undertaking must ensure workers who are required to perform, or help in performing, electrical work are competent in rescue and resuscitation in accordance with recognised practices in the electricity industry.\nMaximum penalty—40 penalty units.\nSubsection&#160;(1) does not apply in relation to a worker if it is a condition of the worker’s electrical work licence that the person must not act in a role for which it is a requirement that the worker be competent in rescue and resuscitation, including as a safety observer.\n(sec.211-ssec.1) A person conducting a business or undertaking must ensure workers who are required to perform, or help in performing, electrical work are competent in rescue and resuscitation in accordance with recognised practices in the electricity industry. Maximum penalty—40 penalty units.\n(sec.211-ssec.2) Subsection&#160;(1) does not apply in relation to a worker if it is a condition of the worker’s electrical work licence that the person must not act in a role for which it is a requirement that the worker be competent in rescue and resuscitation, including as a safety observer.","sortOrder":264},{"sectionNumber":"pt.8-div.8","sectionType":"division","heading":"Documents about electrical work","content":"## Documents about electrical work","sortOrder":265},{"sectionNumber":"sec.212","sectionType":"section","heading":"Application of division","content":"### sec.212 Application of division\n\nThis division applies in relation to the performance of electrical work as part of the business or undertaking conducted by a licensed electrical contractor.","sortOrder":266},{"sectionNumber":"sec.213","sectionType":"section","heading":"Who may sign documents about electrical work","content":"### sec.213 Who may sign documents about electrical work\n\nA person must not sign a document required under the Act , or by an electricity entity, about the performance of the electrical work unless the person is—\nif the licensed electrical contractor is an individual—a qualified technical person for the individual; or\nif the licensed electrical contractor is a partnership—a qualified technical person for the partnership; or\nif the licensed electrical contractor is a corporation—a qualified technical person for the corporation.\nMaximum penalty—20 penalty units.\nIn this section—\nqualified technical person , for an individual, partnership or corporation, see section&#160;143 .\n(sec.213-ssec.1) A person must not sign a document required under the Act , or by an electricity entity, about the performance of the electrical work unless the person is— if the licensed electrical contractor is an individual—a qualified technical person for the individual; or if the licensed electrical contractor is a partnership—a qualified technical person for the partnership; or if the licensed electrical contractor is a corporation—a qualified technical person for the corporation. Maximum penalty—20 penalty units.\n(sec.213-ssec.2) In this section— qualified technical person , for an individual, partnership or corporation, see section&#160;143 .\n- (a) if the licensed electrical contractor is an individual—a qualified technical person for the individual; or\n- (b) if the licensed electrical contractor is a partnership—a qualified technical person for the partnership; or\n- (c) if the licensed electrical contractor is a corporation—a qualified technical person for the corporation.","sortOrder":267},{"sectionNumber":"pt.8-div.9","sectionType":"division","heading":"Misrepresentations","content":"## Misrepresentations","sortOrder":268},{"sectionNumber":"sec.214","sectionType":"section","heading":"Misrepresentations about electrical equipment or work","content":"### sec.214 Misrepresentations about electrical equipment or work\n\nA person must not, in trade or commerce, represent that someone who is not a licensed electrical worker may lawfully—\nconnect to a source of electricity an item of electrical equipment that may only be connected to a source of electricity by a licensed electrical worker; or\ndo electrical work that may be done only by a licensed electrical worker.\nMaximum penalty—40 penalty units.\nA person conducting a business or undertaking must take all reasonable steps to ensure the person’s workers do not contravene subsection&#160;(1) .\nMaximum penalty—40 penalty units.\n(sec.214-ssec.1) A person must not, in trade or commerce, represent that someone who is not a licensed electrical worker may lawfully— connect to a source of electricity an item of electrical equipment that may only be connected to a source of electricity by a licensed electrical worker; or do electrical work that may be done only by a licensed electrical worker. Maximum penalty—40 penalty units.\n(sec.214-ssec.2) A person conducting a business or undertaking must take all reasonable steps to ensure the person’s workers do not contravene subsection&#160;(1) . Maximum penalty—40 penalty units.\n- (a) connect to a source of electricity an item of electrical equipment that may only be connected to a source of electricity by a licensed electrical worker; or\n- (b) do electrical work that may be done only by a licensed electrical worker.","sortOrder":269},{"sectionNumber":"sec.215","sectionType":"section","heading":"Misrepresentations about lawful authority to contract for performance of electrical work","content":"### sec.215 Misrepresentations about lawful authority to contract for performance of electrical work\n\nA person must not, in trade or commerce, represent that a person who is not a licensed electrical contractor may lawfully contract for the performance of electrical work that only a licensed electrical contractor may perform.\nMaximum penalty—40 penalty units.\nA person conducting a business or undertaking must take all reasonable steps to ensure the person’s workers do not contravene subsection&#160;(1) .\nMaximum penalty—40 penalty units.\n(sec.215-ssec.1) A person must not, in trade or commerce, represent that a person who is not a licensed electrical contractor may lawfully contract for the performance of electrical work that only a licensed electrical contractor may perform. Maximum penalty—40 penalty units.\n(sec.215-ssec.2) A person conducting a business or undertaking must take all reasonable steps to ensure the person’s workers do not contravene subsection&#160;(1) . Maximum penalty—40 penalty units.","sortOrder":270},{"sectionNumber":"pt.9","sectionType":"part","heading":"Electricity supply","content":"# Electricity supply","sortOrder":271},{"sectionNumber":"pt.9-div.1","sectionType":"division","heading":"Preliminary","content":"## Preliminary","sortOrder":272},{"sectionNumber":"sec.216","sectionType":"section","heading":"Purpose of part— Act , s&#160;210","content":"### sec.216 Purpose of part— Act , s&#160;210\n\nThis part prescribes, for section&#160;210 (2) (f) of the Act , safety and technical requirements for electricity supply.","sortOrder":273},{"sectionNumber":"pt.9-div.2","sectionType":"division","heading":"Connection to source of electricity","content":"## Connection to source of electricity","sortOrder":274},{"sectionNumber":"sec.217","sectionType":"section","heading":"Electrical installation not to be initially connected without examination and testing","content":"### sec.217 Electrical installation not to be initially connected without examination and testing\n\nA person must not connect an electrical installation to a source of electricity supplied by a distribution entity for the first time unless the distribution entity has—\nexamined the consumer mains and the consumer main switchboard for the electrical installation and confirmed there are no serious defects; and\ncarried out tests to ensure the consumer mains and the consumer main switchboard are electrically safe.\nMaximum penalty—40 penalty units.\nThe distribution entity may charge a consumer for an examination or test performed under subsection&#160;(1) only if, at the consumer’s request, the examination or test is performed outside normal working hours.\n(sec.217-ssec.1) A person must not connect an electrical installation to a source of electricity supplied by a distribution entity for the first time unless the distribution entity has— examined the consumer mains and the consumer main switchboard for the electrical installation and confirmed there are no serious defects; and carried out tests to ensure the consumer mains and the consumer main switchboard are electrically safe. Maximum penalty—40 penalty units.\n(sec.217-ssec.2) The distribution entity may charge a consumer for an examination or test performed under subsection&#160;(1) only if, at the consumer’s request, the examination or test is performed outside normal working hours.\n- (a) examined the consumer mains and the consumer main switchboard for the electrical installation and confirmed there are no serious defects; and\n- (b) carried out tests to ensure the consumer mains and the consumer main switchboard are electrically safe.","sortOrder":275},{"sectionNumber":"sec.218","sectionType":"section","heading":"Electrical installation with serious defect not to be connected","content":"### sec.218 Electrical installation with serious defect not to be connected\n\nIf an electrical installation has a serious defect, a person must not connect the installation to a source of electricity for use for its intended purpose.\nMaximum penalty—40 penalty units.\nSubsection&#160;(1) does not apply to a person if the person does not know, and could not reasonably be expected to know, before connecting the electrical installation to a source of electricity that the installation has a serious defect.\nAlso, subsection&#160;(1) does not apply to a distribution entity unless the serious defect in the electrical installation is located in a consumer main switchboard or between a consumer main switchboard and the works of the distribution entity.\n(sec.218-ssec.1) If an electrical installation has a serious defect, a person must not connect the installation to a source of electricity for use for its intended purpose. Maximum penalty—40 penalty units.\n(sec.218-ssec.2) Subsection&#160;(1) does not apply to a person if the person does not know, and could not reasonably be expected to know, before connecting the electrical installation to a source of electricity that the installation has a serious defect.\n(sec.218-ssec.3) Also, subsection&#160;(1) does not apply to a distribution entity unless the serious defect in the electrical installation is located in a consumer main switchboard or between a consumer main switchboard and the works of the distribution entity.","sortOrder":276},{"sectionNumber":"sec.219","sectionType":"section","heading":"Electrical installation not to be connected if work not tested","content":"### sec.219 Electrical installation not to be connected if work not tested\n\nA person must not connect an electrical installation on which electrical work has been performed to a source of electricity unless—\nthe electrical work has been performed by the holder of an electrical licence that authorises the performance of the work; and\nthe electrical installation, to the extent it is affected by the electrical work, has been tested to ensure it is electrically safe and complies with the requirements of the wiring rules.\nMaximum penalty—40 penalty units.\nSubsection&#160;(1) does not apply to the connection of the electrical installation to a source of electricity for the first time.\n(sec.219-ssec.1) A person must not connect an electrical installation on which electrical work has been performed to a source of electricity unless— the electrical work has been performed by the holder of an electrical licence that authorises the performance of the work; and the electrical installation, to the extent it is affected by the electrical work, has been tested to ensure it is electrically safe and complies with the requirements of the wiring rules. Maximum penalty—40 penalty units.\n(sec.219-ssec.2) Subsection&#160;(1) does not apply to the connection of the electrical installation to a source of electricity for the first time.\n- (a) the electrical work has been performed by the holder of an electrical licence that authorises the performance of the work; and\n- (b) the electrical installation, to the extent it is affected by the electrical work, has been tested to ensure it is electrically safe and complies with the requirements of the wiring rules.","sortOrder":277},{"sectionNumber":"sec.220","sectionType":"section","heading":"Reconnection of electrical installation","content":"### sec.220 Reconnection of electrical installation\n\nA person must not reconnect an electrical installation to a source of electricity supplied by a distribution entity unless the person is authorised under subsection&#160;(2) or (3) .\nMaximum penalty—40 penalty units.\nA distribution entity may reconnect an electrical installation to a source of electricity if—\nthe distribution entity first performs a visual inspection of the electrical installation and finds there are no serious defects; or\nthe distribution entity does not first perform a visual inspection of the electrical installation, but all of the following circumstances apply—\nthe electrical installation was disconnected by the distribution entity inadvertently or because of debt;\nthe electrical installation has been disconnected for less than 30 days;\nthe reconnection is for the purpose of supplying the same consumer.\nA licensed electrical contractor may reconnect an electrical installation to a source of electricity if the contractor has rectified a serious defect that has caused a distribution entity or inspector to leave the installation disconnected.\nA distribution entity must keep a record, for at least 5 years, of all electrical installations that have been disconnected from a source of electricity supplied by the distribution entity and that, in the absence of authorisation under subsection&#160;(2) or (3) , must not be reconnected.\nMaximum penalty—20 penalty units.\nA distribution entity may charge a consumer for an inspection performed under subsection&#160;(2) (a) only if, at the consumer’s request, the inspection is performed outside normal working hours.\nThis section does not apply to a reconnection if the reconnection, and the disconnection preceding it, are performed in the ordinary course of electrical work.\n(sec.220-ssec.1) A person must not reconnect an electrical installation to a source of electricity supplied by a distribution entity unless the person is authorised under subsection&#160;(2) or (3) . Maximum penalty—40 penalty units.\n(sec.220-ssec.2) A distribution entity may reconnect an electrical installation to a source of electricity if— the distribution entity first performs a visual inspection of the electrical installation and finds there are no serious defects; or the distribution entity does not first perform a visual inspection of the electrical installation, but all of the following circumstances apply— the electrical installation was disconnected by the distribution entity inadvertently or because of debt; the electrical installation has been disconnected for less than 30 days; the reconnection is for the purpose of supplying the same consumer.\n(sec.220-ssec.3) A licensed electrical contractor may reconnect an electrical installation to a source of electricity if the contractor has rectified a serious defect that has caused a distribution entity or inspector to leave the installation disconnected.\n(sec.220-ssec.4) A distribution entity must keep a record, for at least 5 years, of all electrical installations that have been disconnected from a source of electricity supplied by the distribution entity and that, in the absence of authorisation under subsection&#160;(2) or (3) , must not be reconnected. Maximum penalty—20 penalty units.\n(sec.220-ssec.5) A distribution entity may charge a consumer for an inspection performed under subsection&#160;(2) (a) only if, at the consumer’s request, the inspection is performed outside normal working hours.\n(sec.220-ssec.6) This section does not apply to a reconnection if the reconnection, and the disconnection preceding it, are performed in the ordinary course of electrical work.\n- (a) the distribution entity first performs a visual inspection of the electrical installation and finds there are no serious defects; or\n- (b) the distribution entity does not first perform a visual inspection of the electrical installation, but all of the following circumstances apply— (i) the electrical installation was disconnected by the distribution entity inadvertently or because of debt; (ii) the electrical installation has been disconnected for less than 30 days; (iii) the reconnection is for the purpose of supplying the same consumer.\n- (i) the electrical installation was disconnected by the distribution entity inadvertently or because of debt;\n- (ii) the electrical installation has been disconnected for less than 30 days;\n- (iii) the reconnection is for the purpose of supplying the same consumer.\n- (i) the electrical installation was disconnected by the distribution entity inadvertently or because of debt;\n- (ii) the electrical installation has been disconnected for less than 30 days;\n- (iii) the reconnection is for the purpose of supplying the same consumer.","sortOrder":278},{"sectionNumber":"sec.221","sectionType":"section","heading":"High voltage or hazardous area electrical installation not to be connected without inspection","content":"### sec.221 High voltage or hazardous area electrical installation not to be connected without inspection\n\nThis section applies in relation to—\na high voltage electrical installation; and\nan electrical installation located in a hazardous area.\nA person must not connect or reconnect the electrical installation to a source of electricity after electrical installation work or electric line work (the electrical work ) has been performed on the electrical installation unless—\nboth of the following circumstances apply—\nthe electrical work has been inspected by an accredited auditor;\nthe accredited auditor has certified that the electrical installation, to the extent affected by the electrical work, has been tested to ensure it is electrically safe and complies with the requirements of the wiring rules; or\nfor an electrical installation located in a hazardous area—\nthe electrical work consists of replacing electrical equipment that is a part of the electrical installation with similar electrical equipment in the circumstances mentioned in section&#160;222 ; and\nthe electrical equipment being replaced is not a switchboard, cable or wire.\nMaximum penalty—40 penalty units.\nA person must not, at a particular place, connect the electrical installation to a source of electricity for the first time at the place unless—\nthe electrical installation has been inspected by an accredited auditor; and\nthe accredited auditor has certified that the electrical installation has been tested to ensure it is electrically safe and complies with the requirements of the wiring rules.\nMaximum penalty—40 penalty units.\nThis section applies in addition to the other provisions in this division about the connection or reconnection of the electrical installation to a source of electricity.\n(sec.221-ssec.1) This section applies in relation to— a high voltage electrical installation; and an electrical installation located in a hazardous area.\n(sec.221-ssec.2) A person must not connect or reconnect the electrical installation to a source of electricity after electrical installation work or electric line work (the electrical work ) has been performed on the electrical installation unless— both of the following circumstances apply— the electrical work has been inspected by an accredited auditor; the accredited auditor has certified that the electrical installation, to the extent affected by the electrical work, has been tested to ensure it is electrically safe and complies with the requirements of the wiring rules; or for an electrical installation located in a hazardous area— the electrical work consists of replacing electrical equipment that is a part of the electrical installation with similar electrical equipment in the circumstances mentioned in section&#160;222 ; and the electrical equipment being replaced is not a switchboard, cable or wire. Maximum penalty—40 penalty units.\n(sec.221-ssec.3) A person must not, at a particular place, connect the electrical installation to a source of electricity for the first time at the place unless— the electrical installation has been inspected by an accredited auditor; and the accredited auditor has certified that the electrical installation has been tested to ensure it is electrically safe and complies with the requirements of the wiring rules. Maximum penalty—40 penalty units.\n(sec.221-ssec.4) This section applies in addition to the other provisions in this division about the connection or reconnection of the electrical installation to a source of electricity.\n- (a) a high voltage electrical installation; and\n- (b) an electrical installation located in a hazardous area.\n- (a) both of the following circumstances apply— (i) the electrical work has been inspected by an accredited auditor; (ii) the accredited auditor has certified that the electrical installation, to the extent affected by the electrical work, has been tested to ensure it is electrically safe and complies with the requirements of the wiring rules; or\n- (i) the electrical work has been inspected by an accredited auditor;\n- (ii) the accredited auditor has certified that the electrical installation, to the extent affected by the electrical work, has been tested to ensure it is electrically safe and complies with the requirements of the wiring rules; or\n- (b) for an electrical installation located in a hazardous area— (i) the electrical work consists of replacing electrical equipment that is a part of the electrical installation with similar electrical equipment in the circumstances mentioned in section&#160;222 ; and (ii) the electrical equipment being replaced is not a switchboard, cable or wire.\n- (i) the electrical work consists of replacing electrical equipment that is a part of the electrical installation with similar electrical equipment in the circumstances mentioned in section&#160;222 ; and\n- (ii) the electrical equipment being replaced is not a switchboard, cable or wire.\n- (i) the electrical work has been inspected by an accredited auditor;\n- (ii) the accredited auditor has certified that the electrical installation, to the extent affected by the electrical work, has been tested to ensure it is electrically safe and complies with the requirements of the wiring rules; or\n- (i) the electrical work consists of replacing electrical equipment that is a part of the electrical installation with similar electrical equipment in the circumstances mentioned in section&#160;222 ; and\n- (ii) the electrical equipment being replaced is not a switchboard, cable or wire.\n- (a) the electrical installation has been inspected by an accredited auditor; and\n- (b) the accredited auditor has certified that the electrical installation has been tested to ensure it is electrically safe and complies with the requirements of the wiring rules.","sortOrder":279},{"sectionNumber":"sec.222","sectionType":"section","heading":"Circumstances for replacing electrical equipment with similar electrical equipment","content":"### sec.222 Circumstances for replacing electrical equipment with similar electrical equipment\n\nFor section&#160;221 (2) (b) (i) , the circumstances are—\nif the electrical equipment being replaced consumes electricity—the replacement equipment—\nhas the same voltage rating as the equipment being replaced; and\nhas a current rating that is not greater than the current rating of the equipment being replaced; and\nhas a power rating that is not greater than the power rating of the equipment being replaced; and\nperforms its function in the same way as the equipment being replaced; and\nhas electrical characteristics that are the same as or better than the electrical characteristics of the equipment being replaced, including when the equipment is operating in circumstances other than normal circumstances; and\ningress protection rating, insulation, earthing, operating temperature\nis designed to operate at the same frequency range as the equipment being replaced; or\nif the electrical equipment being replaced is used for controlling electricity—the replacement electrical equipment—\nhas the same voltage rating as the equipment being replaced; and\nhas the same current rating as the equipment being replaced; and\nperforms its function in the same way as the equipment being replaced; and\nhas electrical characteristics that are the same as or better than the electrical characteristics of the equipment being replaced, including when the equipment is operating in circumstances other than normal circumstances; and\ningress protection rating, insulation, earthing, operating temperature, breaking current rating\nis designed to operate at the same frequency range as the equipment being replaced.\nIn this section—\ncurrent rating , for electrical equipment, means the current stated on the equipment as the current the equipment consumes or controls when operating in normal circumstances.\nfrequency range , for electrical equipment, means the frequency or range of frequencies stated on the equipment as the frequency or range of frequencies the equipment is designed to safely operate at in normal circumstances.\npower rating , for electrical equipment, means the power stated on the equipment as the power the equipment consumes when operating in normal circumstances.\nvoltage rating , for electrical equipment, means—\nif the electrical equipment consumes electricity—the maximum voltage the electrical equipment is designed to be supplied with to operate in normal circumstances; or\nif the electrical equipment is used for controlling electricity—the voltage the electrical equipment can safely control in normal circumstances.\n(sec.222-ssec.1) For section&#160;221 (2) (b) (i) , the circumstances are— if the electrical equipment being replaced consumes electricity—the replacement equipment— has the same voltage rating as the equipment being replaced; and has a current rating that is not greater than the current rating of the equipment being replaced; and has a power rating that is not greater than the power rating of the equipment being replaced; and performs its function in the same way as the equipment being replaced; and has electrical characteristics that are the same as or better than the electrical characteristics of the equipment being replaced, including when the equipment is operating in circumstances other than normal circumstances; and ingress protection rating, insulation, earthing, operating temperature is designed to operate at the same frequency range as the equipment being replaced; or if the electrical equipment being replaced is used for controlling electricity—the replacement electrical equipment— has the same voltage rating as the equipment being replaced; and has the same current rating as the equipment being replaced; and performs its function in the same way as the equipment being replaced; and has electrical characteristics that are the same as or better than the electrical characteristics of the equipment being replaced, including when the equipment is operating in circumstances other than normal circumstances; and ingress protection rating, insulation, earthing, operating temperature, breaking current rating is designed to operate at the same frequency range as the equipment being replaced.\n(sec.222-ssec.2) In this section— current rating , for electrical equipment, means the current stated on the equipment as the current the equipment consumes or controls when operating in normal circumstances. frequency range , for electrical equipment, means the frequency or range of frequencies stated on the equipment as the frequency or range of frequencies the equipment is designed to safely operate at in normal circumstances. power rating , for electrical equipment, means the power stated on the equipment as the power the equipment consumes when operating in normal circumstances. voltage rating , for electrical equipment, means— if the electrical equipment consumes electricity—the maximum voltage the electrical equipment is designed to be supplied with to operate in normal circumstances; or if the electrical equipment is used for controlling electricity—the voltage the electrical equipment can safely control in normal circumstances.\n- (a) if the electrical equipment being replaced consumes electricity—the replacement equipment— (i) has the same voltage rating as the equipment being replaced; and (ii) has a current rating that is not greater than the current rating of the equipment being replaced; and (iii) has a power rating that is not greater than the power rating of the equipment being replaced; and (iv) performs its function in the same way as the equipment being replaced; and (v) has electrical characteristics that are the same as or better than the electrical characteristics of the equipment being replaced, including when the equipment is operating in circumstances other than normal circumstances; and Examples of electrical characteristics— ingress protection rating, insulation, earthing, operating temperature (vi) is designed to operate at the same frequency range as the equipment being replaced; or\n- (i) has the same voltage rating as the equipment being replaced; and\n- (ii) has a current rating that is not greater than the current rating of the equipment being replaced; and\n- (iii) has a power rating that is not greater than the power rating of the equipment being replaced; and\n- (iv) performs its function in the same way as the equipment being replaced; and\n- (v) has electrical characteristics that are the same as or better than the electrical characteristics of the equipment being replaced, including when the equipment is operating in circumstances other than normal circumstances; and Examples of electrical characteristics— ingress protection rating, insulation, earthing, operating temperature\n- (vi) is designed to operate at the same frequency range as the equipment being replaced; or\n- (b) if the electrical equipment being replaced is used for controlling electricity—the replacement electrical equipment— (i) has the same voltage rating as the equipment being replaced; and (ii) has the same current rating as the equipment being replaced; and (iii) performs its function in the same way as the equipment being replaced; and (iv) has electrical characteristics that are the same as or better than the electrical characteristics of the equipment being replaced, including when the equipment is operating in circumstances other than normal circumstances; and Examples of electrical characteristics— ingress protection rating, insulation, earthing, operating temperature, breaking current rating (v) is designed to operate at the same frequency range as the equipment being replaced.\n- (i) has the same voltage rating as the equipment being replaced; and\n- (ii) has the same current rating as the equipment being replaced; and\n- (iii) performs its function in the same way as the equipment being replaced; and\n- (iv) has electrical characteristics that are the same as or better than the electrical characteristics of the equipment being replaced, including when the equipment is operating in circumstances other than normal circumstances; and Examples of electrical characteristics— ingress protection rating, insulation, earthing, operating temperature, breaking current rating\n- (v) is designed to operate at the same frequency range as the equipment being replaced.\n- (i) has the same voltage rating as the equipment being replaced; and\n- (ii) has a current rating that is not greater than the current rating of the equipment being replaced; and\n- (iii) has a power rating that is not greater than the power rating of the equipment being replaced; and\n- (iv) performs its function in the same way as the equipment being replaced; and\n- (v) has electrical characteristics that are the same as or better than the electrical characteristics of the equipment being replaced, including when the equipment is operating in circumstances other than normal circumstances; and Examples of electrical characteristics— ingress protection rating, insulation, earthing, operating temperature\n- (vi) is designed to operate at the same frequency range as the equipment being replaced; or\n- (i) has the same voltage rating as the equipment being replaced; and\n- (ii) has the same current rating as the equipment being replaced; and\n- (iii) performs its function in the same way as the equipment being replaced; and\n- (iv) has electrical characteristics that are the same as or better than the electrical characteristics of the equipment being replaced, including when the equipment is operating in circumstances other than normal circumstances; and Examples of electrical characteristics— ingress protection rating, insulation, earthing, operating temperature, breaking current rating\n- (v) is designed to operate at the same frequency range as the equipment being replaced.\n- (a) if the electrical equipment consumes electricity—the maximum voltage the electrical equipment is designed to be supplied with to operate in normal circumstances; or\n- (b) if the electrical equipment is used for controlling electricity—the voltage the electrical equipment can safely control in normal circumstances.","sortOrder":280},{"sectionNumber":"sec.223","sectionType":"section","heading":"Compliance with Act and regulation","content":"### sec.223 Compliance with Act and regulation\n\nThis section applies in relation to an electrical installation on which electrical work has been performed.\nA licensed electrical contractor must not connect the electrical installation to a source of electricity unless the contractor is satisfied the Act and this regulation have been complied with in relation to the electrical installation to the extent it is affected by the electrical work.\nMaximum penalty—40 penalty units.\n(sec.223-ssec.1) This section applies in relation to an electrical installation on which electrical work has been performed.\n(sec.223-ssec.2) A licensed electrical contractor must not connect the electrical installation to a source of electricity unless the contractor is satisfied the Act and this regulation have been complied with in relation to the electrical installation to the extent it is affected by the electrical work. Maximum penalty—40 penalty units.","sortOrder":281},{"sectionNumber":"sec.224","sectionType":"section","heading":"Disconnection and reconnection of low voltage electrical installation","content":"### sec.224 Disconnection and reconnection of low voltage electrical installation\n\nThis section applies to an eligible person who—\nperforms electrical installation work on a consumer’s consumer terminals, consumer mains or consumer main switchboard; or\nisolates electricity supply to an electrical installation to eliminate an exclusion zone that would otherwise exist.\nDespite anything else in this division, the eligible person may, in accordance with a recognised practice in the electricity industry, de-energise and re-energise the consumer’s electrical installation by—\nremoving and replacing a fuse wedge from a service fuse; or\nswitching off and on a circuit breaker installed as a service line disconnector.\nIf subsection&#160;(1) (a) applies, the eligible person must, before reconnecting the electrical installation to a source of electricity, test to ensure the installation is electrically safe.\nMaximum penalty—40 penalty units.\nIf subsection&#160;(1) (b) applies, the eligible person must, before reconnecting the electrical installation to a source of electricity—\nif the eligible person, or another person acting for the eligible person, has performed electrical work on the installation—test to ensure the installation is safe to reconnect to the source; or\notherwise—perform a visual inspection of the part of the installation that is in the area of the eliminated exclusion zone to ensure the installation has no serious defects.\nMaximum penalty—40 penalty units.\nIn this section—\neligible person means—\na licensed electrical contractor; or\na person who holds an electrical mechanic licence and is performing work for a licensed electrical contractor as an employee of the contractor; or\na person who holds an electrical mechanic licence and is performing work for the person or a relative of the person at premises owned or occupied by the person or relative.\n(sec.224-ssec.1) This section applies to an eligible person who— performs electrical installation work on a consumer’s consumer terminals, consumer mains or consumer main switchboard; or isolates electricity supply to an electrical installation to eliminate an exclusion zone that would otherwise exist.\n(sec.224-ssec.2) Despite anything else in this division, the eligible person may, in accordance with a recognised practice in the electricity industry, de-energise and re-energise the consumer’s electrical installation by— removing and replacing a fuse wedge from a service fuse; or switching off and on a circuit breaker installed as a service line disconnector.\n(sec.224-ssec.3) If subsection&#160;(1) (a) applies, the eligible person must, before reconnecting the electrical installation to a source of electricity, test to ensure the installation is electrically safe. Maximum penalty—40 penalty units.\n(sec.224-ssec.4) If subsection&#160;(1) (b) applies, the eligible person must, before reconnecting the electrical installation to a source of electricity— if the eligible person, or another person acting for the eligible person, has performed electrical work on the installation—test to ensure the installation is safe to reconnect to the source; or otherwise—perform a visual inspection of the part of the installation that is in the area of the eliminated exclusion zone to ensure the installation has no serious defects. Maximum penalty—40 penalty units.\n(sec.224-ssec.5) In this section— eligible person means— a licensed electrical contractor; or a person who holds an electrical mechanic licence and is performing work for a licensed electrical contractor as an employee of the contractor; or a person who holds an electrical mechanic licence and is performing work for the person or a relative of the person at premises owned or occupied by the person or relative.\n- (a) performs electrical installation work on a consumer’s consumer terminals, consumer mains or consumer main switchboard; or\n- (b) isolates electricity supply to an electrical installation to eliminate an exclusion zone that would otherwise exist.\n- (a) removing and replacing a fuse wedge from a service fuse; or\n- (b) switching off and on a circuit breaker installed as a service line disconnector.\n- (a) if the eligible person, or another person acting for the eligible person, has performed electrical work on the installation—test to ensure the installation is safe to reconnect to the source; or\n- (b) otherwise—perform a visual inspection of the part of the installation that is in the area of the eliminated exclusion zone to ensure the installation has no serious defects.\n- (a) a licensed electrical contractor; or\n- (b) a person who holds an electrical mechanic licence and is performing work for a licensed electrical contractor as an employee of the contractor; or\n- (c) a person who holds an electrical mechanic licence and is performing work for the person or a relative of the person at premises owned or occupied by the person or relative.","sortOrder":282},{"sectionNumber":"pt.9-div.3","sectionType":"division","heading":"Private generating plant","content":"## Private generating plant","sortOrder":283},{"sectionNumber":"sec.225","sectionType":"section","heading":"Definition for division","content":"### sec.225 Definition for division\n\nIn this division—\nprivate generating plant means equipment used for generating electricity, other than equipment used by an electricity entity under an authority or special approval under the Electricity Act.","sortOrder":284},{"sectionNumber":"sec.226","sectionType":"section","heading":"Generating plant for emergency supply","content":"### sec.226 Generating plant for emergency supply\n\nThis section applies to a person if private generating plant is—\ninstalled at the person’s premises as part of the person’s electrical installation; and\nintended to provide a supply of electricity ( emergency supply ) to the person’s electrical installation, or to the person’s electrical installation and the electrical installation of another person, during an interruption of the supply of electricity from a distribution entity.\nThe person must ensure that, when the private generating plant is operating to provide emergency supply, there is effective isolation between—\nall active conductors of each electrical installation to which the private generating plant is connected; and\nany part of an electrical installation mentioned in paragraph&#160;(a) still connected to the supply from the distribution entity.\nMaximum penalty—40 penalty units.\nThe person must ensure the installation of the private generating plant complies with the requirements of the wiring rules.\nMaximum penalty—40 penalty units.\n(sec.226-ssec.1) This section applies to a person if private generating plant is— installed at the person’s premises as part of the person’s electrical installation; and intended to provide a supply of electricity ( emergency supply ) to the person’s electrical installation, or to the person’s electrical installation and the electrical installation of another person, during an interruption of the supply of electricity from a distribution entity.\n(sec.226-ssec.2) The person must ensure that, when the private generating plant is operating to provide emergency supply, there is effective isolation between— all active conductors of each electrical installation to which the private generating plant is connected; and any part of an electrical installation mentioned in paragraph&#160;(a) still connected to the supply from the distribution entity. Maximum penalty—40 penalty units.\n(sec.226-ssec.3) The person must ensure the installation of the private generating plant complies with the requirements of the wiring rules. Maximum penalty—40 penalty units.\n- (a) installed at the person’s premises as part of the person’s electrical installation; and\n- (b) intended to provide a supply of electricity ( emergency supply ) to the person’s electrical installation, or to the person’s electrical installation and the electrical installation of another person, during an interruption of the supply of electricity from a distribution entity.\n- (a) all active conductors of each electrical installation to which the private generating plant is connected; and\n- (b) any part of an electrical installation mentioned in paragraph&#160;(a) still connected to the supply from the distribution entity.","sortOrder":285},{"sectionNumber":"sec.227","sectionType":"section","heading":"Generating plant for interconnection to works of electricity entity","content":"### sec.227 Generating plant for interconnection to works of electricity entity\n\nThis section applies to a person if—\nprivate generating plant is installed at the person’s premises as part of the person’s electrical installation; and\nthe private generating plant is intended to interconnect with the works of an electricity entity.\nThe person must comply with the electricity entity’s conditions for ensuring safe and stable parallel operation of the private generating plant with the works of the electricity entity.\nMaximum penalty—40 penalty units.\n(sec.227-ssec.1) This section applies to a person if— private generating plant is installed at the person’s premises as part of the person’s electrical installation; and the private generating plant is intended to interconnect with the works of an electricity entity.\n(sec.227-ssec.2) The person must comply with the electricity entity’s conditions for ensuring safe and stable parallel operation of the private generating plant with the works of the electricity entity. Maximum penalty—40 penalty units.\n- (a) private generating plant is installed at the person’s premises as part of the person’s electrical installation; and\n- (b) the private generating plant is intended to interconnect with the works of an electricity entity.","sortOrder":286},{"sectionNumber":"pt.9-div.4","sectionType":"division","heading":"Testing","content":"## Testing","sortOrder":287},{"sectionNumber":"sec.228","sectionType":"section","heading":"Notice of test by licensed electrical contractor","content":"### sec.228 Notice of test by licensed electrical contractor\n\nThis section applies if, under this part—\na licensed electrical contractor is required to test electrical work performed on an electrical installation; and\nthe electrical installation is required to be examined or tested by the distribution entity that supplies or is to supply electricity to the electrical installation.\nThe licensed electrical contractor must, as soon as practicable after carrying out the test, give the distribution entity a notice complying with subsection&#160;(3) .\nMaximum penalty—40 penalty units.\nThe notice must state that—\nthe tests required to be carried out by the licensed electrical contractor will be carried out in the way required under this part; and\nthe electrical installation will be electrically safe by the date stated in the notice; and\nthe electrical installation will be ready for connection by the date stated in the notice.\n(sec.228-ssec.1) This section applies if, under this part— a licensed electrical contractor is required to test electrical work performed on an electrical installation; and the electrical installation is required to be examined or tested by the distribution entity that supplies or is to supply electricity to the electrical installation.\n(sec.228-ssec.2) The licensed electrical contractor must, as soon as practicable after carrying out the test, give the distribution entity a notice complying with subsection&#160;(3) . Maximum penalty—40 penalty units.\n(sec.228-ssec.3) The notice must state that— the tests required to be carried out by the licensed electrical contractor will be carried out in the way required under this part; and the electrical installation will be electrically safe by the date stated in the notice; and the electrical installation will be ready for connection by the date stated in the notice.\n- (a) a licensed electrical contractor is required to test electrical work performed on an electrical installation; and\n- (b) the electrical installation is required to be examined or tested by the distribution entity that supplies or is to supply electricity to the electrical installation.\n- (a) the tests required to be carried out by the licensed electrical contractor will be carried out in the way required under this part; and\n- (b) the electrical installation will be electrically safe by the date stated in the notice; and\n- (c) the electrical installation will be ready for connection by the date stated in the notice.","sortOrder":288},{"sectionNumber":"sec.229","sectionType":"section","heading":"Certificate of testing and compliance","content":"### sec.229 Certificate of testing and compliance\n\nThis section applies to a licensed electrical contractor who connects an electrical installation on which electrical work has been performed to a source of electricity.\nThe licensed electrical contractor must, as soon as practicable after the connection, give the person for whom the work was performed a certificate, complying with subsections&#160;(3) and (4) , about the testing of the electrical installation required under this part.\nMaximum penalty—40 penalty units.\nThe certificate must state the following—\nthe name and address of the person for whom the work was performed;\nthe electrical installation tested;\nthe day the electrical installation was tested;\nthe identifying number of the electrical contractor licence under which the electrical installation was tested.\nThe certificate must certify that the electrical installation, to the extent it is affected by the electrical work, has been tested to ensure it is electrically safe and complies with the requirements of the wiring rules.\nA licensed electrical contractor must keep a copy of a certificate given under this section for at least 5 years after the certificate is given.\nMaximum penalty—20 penalty units.\n(sec.229-ssec.1) This section applies to a licensed electrical contractor who connects an electrical installation on which electrical work has been performed to a source of electricity.\n(sec.229-ssec.2) The licensed electrical contractor must, as soon as practicable after the connection, give the person for whom the work was performed a certificate, complying with subsections&#160;(3) and (4) , about the testing of the electrical installation required under this part. Maximum penalty—40 penalty units.\n(sec.229-ssec.3) The certificate must state the following— the name and address of the person for whom the work was performed; the electrical installation tested; the day the electrical installation was tested; the identifying number of the electrical contractor licence under which the electrical installation was tested.\n(sec.229-ssec.4) The certificate must certify that the electrical installation, to the extent it is affected by the electrical work, has been tested to ensure it is electrically safe and complies with the requirements of the wiring rules.\n(sec.229-ssec.5) A licensed electrical contractor must keep a copy of a certificate given under this section for at least 5 years after the certificate is given. Maximum penalty—20 penalty units.\n- (a) the name and address of the person for whom the work was performed;\n- (b) the electrical installation tested;\n- (c) the day the electrical installation was tested;\n- (d) the identifying number of the electrical contractor licence under which the electrical installation was tested.","sortOrder":289},{"sectionNumber":"sec.230","sectionType":"section","heading":"Performance of examination or test","content":"### sec.230 Performance of examination or test\n\nA distribution entity that carries out an examination or test required under this part in relation to an electrical installation must examine or test to ensure the electrical installation, to the extent of the required examination or test, is electrically safe.\nMaximum penalty—40 penalty units.","sortOrder":290},{"sectionNumber":"sec.231","sectionType":"section","heading":"Reasons to be given for not connecting electrical installation after examination, inspection or test","content":"### sec.231 Reasons to be given for not connecting electrical installation after examination, inspection or test\n\nThis section applies to a distribution entity if, after performing an examination, inspection or test, a distribution entity does not connect or reconnect a consumer’s electrical installation on which electrical work has been performed to a source of electricity.\nThe distribution entity must, as soon as practicable after completing the examination, inspection or test, give the consumer a written report stating the reasons for not connecting or reconnecting the installation.\nMaximum penalty—40 penalty units.\n(sec.231-ssec.1) This section applies to a distribution entity if, after performing an examination, inspection or test, a distribution entity does not connect or reconnect a consumer’s electrical installation on which electrical work has been performed to a source of electricity.\n(sec.231-ssec.2) The distribution entity must, as soon as practicable after completing the examination, inspection or test, give the consumer a written report stating the reasons for not connecting or reconnecting the installation.","sortOrder":291},{"sectionNumber":"sec.232","sectionType":"section","heading":"Keeping copy of report","content":"### sec.232 Keeping copy of report\n\nThis section applies if a person (the worker ) performs an examination, inspection or test, under this part.\nA person conducting a business or undertaking who employs the worker must keep a copy of the report of the examination, inspection or test for at least 5 years after the report is made.\nMaximum penalty—20 penalty units.\n(sec.232-ssec.1) This section applies if a person (the worker ) performs an examination, inspection or test, under this part.\n(sec.232-ssec.2) A person conducting a business or undertaking who employs the worker must keep a copy of the report of the examination, inspection or test for at least 5 years after the report is made. Maximum penalty—20 penalty units.","sortOrder":292},{"sectionNumber":"pt.9-div.5","sectionType":"division","heading":"Requests and advice to distribution entities","content":"## Requests and advice to distribution entities","sortOrder":293},{"sectionNumber":"sec.233","sectionType":"section","heading":"Request for examination of electrical work","content":"### sec.233 Request for examination of electrical work\n\nThis section applies if, under this part, electrical work must be examined or tested by a distribution entity before an electrical installation is connected or reconnected to a source of electricity.\nThe person who performed the electrical work must, as soon as practicable after the completion of the electrical work, ask the distribution entity that supplies or is to supply electricity to the electrical installation, in a way approved by the distribution entity, for the work to be examined or tested.\nMaximum penalty—40 penalty units.\nIn making the request, the person must certify that—\nthe electrical work has been completed; and\nthe electrical installation complies with the requirements of this regulation.\n(sec.233-ssec.1) This section applies if, under this part, electrical work must be examined or tested by a distribution entity before an electrical installation is connected or reconnected to a source of electricity.\n(sec.233-ssec.2) The person who performed the electrical work must, as soon as practicable after the completion of the electrical work, ask the distribution entity that supplies or is to supply electricity to the electrical installation, in a way approved by the distribution entity, for the work to be examined or tested. Maximum penalty—40 penalty units.\n(sec.233-ssec.3) In making the request, the person must certify that— the electrical work has been completed; and the electrical installation complies with the requirements of this regulation.\n- (a) the electrical work has been completed; and\n- (b) the electrical installation complies with the requirements of this regulation.","sortOrder":294},{"sectionNumber":"sec.234","sectionType":"section","heading":"Advice of need to install or change meter or other equipment","content":"### sec.234 Advice of need to install or change meter or other equipment\n\nThis section applies if, because of the performance of electrical work on an electrical installation, there is a need to install or change metering, control apparatus or other ancillary equipment forming part of the works of a distribution entity.\nThe person who performed the electrical work must, as soon as practicable after the completion of the electrical work, tell the distribution entity, in a way approved by the distribution entity, of the need for the installation or change.\nMaximum penalty—40 penalty units.\nIn giving the advice, the person must certify that the electrical work has been completed.\n(sec.234-ssec.1) This section applies if, because of the performance of electrical work on an electrical installation, there is a need to install or change metering, control apparatus or other ancillary equipment forming part of the works of a distribution entity.\n(sec.234-ssec.2) The person who performed the electrical work must, as soon as practicable after the completion of the electrical work, tell the distribution entity, in a way approved by the distribution entity, of the need for the installation or change. Maximum penalty—40 penalty units.\n(sec.234-ssec.3) In giving the advice, the person must certify that the electrical work has been completed.","sortOrder":295},{"sectionNumber":"pt.10","sectionType":"part","heading":"Safety management systems","content":"# Safety management systems","sortOrder":296},{"sectionNumber":"pt.10-div.1","sectionType":"division","heading":"Prescribed electricity entities","content":"## Prescribed electricity entities","sortOrder":297},{"sectionNumber":"sec.235","sectionType":"section","heading":"Prescribed electricity entities— Act , s&#160;66","content":"### sec.235 Prescribed electricity entities— Act , s&#160;66\n\nFor section&#160;66 of the Act , definition prescribed electricity entity , an electricity entity named in schedule&#160;5 is declared to be a prescribed electricity entity for part&#160;5 of the Act .","sortOrder":298},{"sectionNumber":"pt.10-div.2","sectionType":"division","heading":"Requirements for safety management systems","content":"## Requirements for safety management systems","sortOrder":299},{"sectionNumber":"sec.236","sectionType":"section","heading":"Application of division— Act , s&#160;66 , definition safety management system","content":"### sec.236 Application of division— Act , s&#160;66 , definition safety management system\n\nFor section&#160;66 of the Act , definition safety management system , paragraph&#160;(e) , this division prescribes requirements for safety management systems.","sortOrder":300},{"sectionNumber":"sec.237","sectionType":"section","heading":"Definition for division","content":"### sec.237 Definition for division\n\nIn this division—\nmodify , a safety management system, includes any change to the safety management system after the system is given to the regulator.","sortOrder":301},{"sectionNumber":"sec.238","sectionType":"section","heading":"Content requirements","content":"### sec.238 Content requirements\n\nA prescribed electricity entity’s safety management system must use a systematic approach to identify and address the hazards and risks associated with the design, construction, operation and maintenance of the prescribed electricity entity’s works.\nThe safety management system must contain—\ndetails of the systems and procedures for—\ncomprehensively identifying hazards and assessing risks; and\ndeveloping and implementing effective risk controls; and\nsetting safety performance targets; and\nensuring safety performance targets are met by—\nmonitoring safety outcomes against safety performance targets; and\nidentifying and implementing corrective actions, if necessary; and\nmonitoring and maintaining the performance of the system; and\nan explanation of how the systems and procedures mentioned in paragraph&#160;(a) (i) to (v) provide for a systematic approach to safety management.\nAlso, the safety management system must provide for—\nmodifying the system, if required by the regulator; and\nundertaking additional assessment by an accredited auditor, if required by the regulator; and\nany auditing of the safety management system under this division to be carried out at the prescribed electricity entity’s expense.\n(sec.238-ssec.1) A prescribed electricity entity’s safety management system must use a systematic approach to identify and address the hazards and risks associated with the design, construction, operation and maintenance of the prescribed electricity entity’s works.\n(sec.238-ssec.2) The safety management system must contain— details of the systems and procedures for— comprehensively identifying hazards and assessing risks; and developing and implementing effective risk controls; and setting safety performance targets; and ensuring safety performance targets are met by— monitoring safety outcomes against safety performance targets; and identifying and implementing corrective actions, if necessary; and monitoring and maintaining the performance of the system; and an explanation of how the systems and procedures mentioned in paragraph&#160;(a) (i) to (v) provide for a systematic approach to safety management.\n(sec.238-ssec.3) Also, the safety management system must provide for— modifying the system, if required by the regulator; and undertaking additional assessment by an accredited auditor, if required by the regulator; and any auditing of the safety management system under this division to be carried out at the prescribed electricity entity’s expense.\n- (a) details of the systems and procedures for— (i) comprehensively identifying hazards and assessing risks; and (ii) developing and implementing effective risk controls; and (iii) setting safety performance targets; and (iv) ensuring safety performance targets are met by— (A) monitoring safety outcomes against safety performance targets; and (B) identifying and implementing corrective actions, if necessary; and (v) monitoring and maintaining the performance of the system; and\n- (i) comprehensively identifying hazards and assessing risks; and\n- (ii) developing and implementing effective risk controls; and\n- (iii) setting safety performance targets; and\n- (iv) ensuring safety performance targets are met by— (A) monitoring safety outcomes against safety performance targets; and (B) identifying and implementing corrective actions, if necessary; and\n- (A) monitoring safety outcomes against safety performance targets; and\n- (B) identifying and implementing corrective actions, if necessary; and\n- (v) monitoring and maintaining the performance of the system; and\n- (b) an explanation of how the systems and procedures mentioned in paragraph&#160;(a) (i) to (v) provide for a systematic approach to safety management.\n- (i) comprehensively identifying hazards and assessing risks; and\n- (ii) developing and implementing effective risk controls; and\n- (iii) setting safety performance targets; and\n- (iv) ensuring safety performance targets are met by— (A) monitoring safety outcomes against safety performance targets; and (B) identifying and implementing corrective actions, if necessary; and\n- (A) monitoring safety outcomes against safety performance targets; and\n- (B) identifying and implementing corrective actions, if necessary; and\n- (v) monitoring and maintaining the performance of the system; and\n- (A) monitoring safety outcomes against safety performance targets; and\n- (B) identifying and implementing corrective actions, if necessary; and\n- (a) modifying the system, if required by the regulator; and\n- (b) undertaking additional assessment by an accredited auditor, if required by the regulator; and\n- (c) any auditing of the safety management system under this division to be carried out at the prescribed electricity entity’s expense.","sortOrder":302},{"sectionNumber":"sec.239","sectionType":"section","heading":"Initial and modification audit requirements","content":"### sec.239 Initial and modification audit requirements\n\nA prescribed electricity entity’s safety management system must provide that, if the entity proposes to give effect to a new system or to modify the system, the proposed system must be assessed and validated by an accredited auditor before it takes effect.\nThe safety management system must also provide that the assessment and validation is to ensure the proposed system comprehensively identifies and addresses the hazards and risks associated with the design, construction, operation and maintenance of the prescribed electricity entity’s works.\nThe safety management system must also provide that the prescribed electricity entity must give the regulator the following documents before the proposed system takes effect—\nthe proposed system, as assessed and validated by the auditor;\nthe auditor’s audit report;\na certificate in the approved form from the auditor verifying that the proposed system has been assessed and validated as meeting the requirement stated in subsection&#160;(2) .\nIn this section—\naudit report , for an assessment and validation of a safety management system, means a report by an accredited auditor about whether the system meets the requirement stated in subsection&#160;(2) .\nproposed modification , of a prescribed electricity entity’s safety management system, means a modification of the system the entity proposes to make, including a modification required by the regulator.\nproposed system means a proposed safety management system, including any proposed modification, that a prescribed electricity entity proposes to make and give effect to for the purpose of section&#160;67 of the Act .\n(sec.239-ssec.1) A prescribed electricity entity’s safety management system must provide that, if the entity proposes to give effect to a new system or to modify the system, the proposed system must be assessed and validated by an accredited auditor before it takes effect.\n(sec.239-ssec.2) The safety management system must also provide that the assessment and validation is to ensure the proposed system comprehensively identifies and addresses the hazards and risks associated with the design, construction, operation and maintenance of the prescribed electricity entity’s works.\n(sec.239-ssec.3) The safety management system must also provide that the prescribed electricity entity must give the regulator the following documents before the proposed system takes effect— the proposed system, as assessed and validated by the auditor; the auditor’s audit report; a certificate in the approved form from the auditor verifying that the proposed system has been assessed and validated as meeting the requirement stated in subsection&#160;(2) .\n(sec.239-ssec.4) In this section— audit report , for an assessment and validation of a safety management system, means a report by an accredited auditor about whether the system meets the requirement stated in subsection&#160;(2) . proposed modification , of a prescribed electricity entity’s safety management system, means a modification of the system the entity proposes to make, including a modification required by the regulator. proposed system means a proposed safety management system, including any proposed modification, that a prescribed electricity entity proposes to make and give effect to for the purpose of section&#160;67 of the Act .\n- (a) the proposed system, as assessed and validated by the auditor;\n- (b) the auditor’s audit report;\n- (c) a certificate in the approved form from the auditor verifying that the proposed system has been assessed and validated as meeting the requirement stated in subsection&#160;(2) .","sortOrder":303},{"sectionNumber":"sec.240","sectionType":"section","heading":"Annual audit requirements","content":"### sec.240 Annual audit requirements\n\nA prescribed electricity entity’s safety management system must provide that an accredited auditor must carry out an audit under this section at least once each year (an annual audit ).\nThe safety management system must provide that the purpose of the annual audit is for the auditor to assess and report on the entity’s level of compliance in giving effect to the system in relation to—\nparticular hazards or risks; or\nparticular systems or procedures; or\nany other matter detailed in the system.\nThe safety management system must provide that the prescribed electricity entity must give a copy of the audit plan to the regulator on or before the later of the following days—\nthe day that is 30 days before the annual audit starts;\nthe day agreed between the prescribed electricity entity and the regulator.\nThe safety management system must provide that, as soon as possible after the annual audit is completed, the prescribed electricity entity must give the regulator—\nthe auditor’s audit report; and\na certificate from the auditor stating the audit has been completed in accordance with this section.\nIn this section—\naudit plan , for an annual audit of a safety management system, means a plan that details the scope, objectives, criteria and methodology for the audit.\naudit report , for an annual audit of a safety management system, means a report by the auditor detailing the findings of the audit by reference to the audit plan.\n(sec.240-ssec.1) A prescribed electricity entity’s safety management system must provide that an accredited auditor must carry out an audit under this section at least once each year (an annual audit ).\n(sec.240-ssec.2) The safety management system must provide that the purpose of the annual audit is for the auditor to assess and report on the entity’s level of compliance in giving effect to the system in relation to— particular hazards or risks; or particular systems or procedures; or any other matter detailed in the system.\n(sec.240-ssec.3) The safety management system must provide that the prescribed electricity entity must give a copy of the audit plan to the regulator on or before the later of the following days— the day that is 30 days before the annual audit starts; the day agreed between the prescribed electricity entity and the regulator.\n(sec.240-ssec.4) The safety management system must provide that, as soon as possible after the annual audit is completed, the prescribed electricity entity must give the regulator— the auditor’s audit report; and a certificate from the auditor stating the audit has been completed in accordance with this section.\n(sec.240-ssec.5) In this section— audit plan , for an annual audit of a safety management system, means a plan that details the scope, objectives, criteria and methodology for the audit. audit report , for an annual audit of a safety management system, means a report by the auditor detailing the findings of the audit by reference to the audit plan.\n- (a) particular hazards or risks; or\n- (b) particular systems or procedures; or\n- (c) any other matter detailed in the system.\n- (a) the day that is 30 days before the annual audit starts;\n- (b) the day agreed between the prescribed electricity entity and the regulator.\n- (a) the auditor’s audit report; and\n- (b) a certificate from the auditor stating the audit has been completed in accordance with this section.","sortOrder":304},{"sectionNumber":"pt.11","sectionType":"part","heading":"Accredited auditors","content":"# Accredited auditors","sortOrder":305},{"sectionNumber":"sec.241","sectionType":"section","heading":"Application for appointment— Act , s&#160;129","content":"### sec.241 Application for appointment— Act , s&#160;129\n\nFor section&#160;129 (2) (a) of the Act , an application for appointment as an accredited auditor must be—\nmade in the approved form; and\naccompanied by the fee stated in schedule&#160;9 for the application; and\nsupported by enough information to allow the regulator to decide the application.\nFor section&#160;129 (2) (a) of the Act , an application for renewal of a person’s appointment as an accredited auditor must be—\nmade in the approved form; and\naccompanied by the fee stated in schedule&#160;9 for the application; and\nsupported by enough information to allow the regulator to decide the application; and\nreceived by the regulator at least 14 days before the appointment ends.\n(sec.241-ssec.1) For section&#160;129 (2) (a) of the Act , an application for appointment as an accredited auditor must be— made in the approved form; and accompanied by the fee stated in schedule&#160;9 for the application; and supported by enough information to allow the regulator to decide the application.\n(sec.241-ssec.2) For section&#160;129 (2) (a) of the Act , an application for renewal of a person’s appointment as an accredited auditor must be— made in the approved form; and accompanied by the fee stated in schedule&#160;9 for the application; and supported by enough information to allow the regulator to decide the application; and received by the regulator at least 14 days before the appointment ends.\n- (a) made in the approved form; and\n- (b) accompanied by the fee stated in schedule&#160;9 for the application; and\n- (c) supported by enough information to allow the regulator to decide the application.\n- (a) made in the approved form; and\n- (b) accompanied by the fee stated in schedule&#160;9 for the application; and\n- (c) supported by enough information to allow the regulator to decide the application; and\n- (d) received by the regulator at least 14 days before the appointment ends.","sortOrder":306},{"sectionNumber":"sec.242","sectionType":"section","heading":"Term of office— Act , s&#160;130","content":"### sec.242 Term of office— Act , s&#160;130\n\nFor section&#160;130 (1) (c) of the Act , a condition on which a person holds office as an accredited auditor is that the person’s term of office is—\n5 years; or\nif the person’s instrument of appointment states a shorter period—the stated period.\n- (a) 5 years; or\n- (b) if the person’s instrument of appointment states a shorter period—the stated period.","sortOrder":307},{"sectionNumber":"sec.243","sectionType":"section","heading":"Refund of fees","content":"### sec.243 Refund of fees\n\nThis section applies if an application made under section&#160;241 is refused by the regulator or is withdrawn before it is decided.\nThe amount stated in schedule&#160;9 as the administration component of the fee paid for the application must be refunded.\n(sec.243-ssec.1) This section applies if an application made under section&#160;241 is refused by the regulator or is withdrawn before it is decided.\n(sec.243-ssec.2) The amount stated in schedule&#160;9 as the administration component of the fee paid for the application must be refunded.","sortOrder":308},{"sectionNumber":"pt.12","sectionType":"part","heading":"Works of an electricity entity","content":"# Works of an electricity entity","sortOrder":309},{"sectionNumber":"pt.12-div.1","sectionType":"division","heading":"Preliminary","content":"## Preliminary","sortOrder":310},{"sectionNumber":"sec.244","sectionType":"section","heading":"Compliance with this part","content":"### sec.244 Compliance with this part\n\nThis section applies to a person who carries out any of the following work in relation to the works of an electricity entity—\ndesigning the works;\nbuilding the works;\nmaintaining or operating the works.\nThe person must ensure that, in carrying out the work mentioned in subsection&#160;(1) , the person complies with the requirements of this part that are relevant to the work.\nMaximum penalty—40 penalty units.\n(sec.244-ssec.1) This section applies to a person who carries out any of the following work in relation to the works of an electricity entity— designing the works; building the works; maintaining or operating the works.\n(sec.244-ssec.2) The person must ensure that, in carrying out the work mentioned in subsection&#160;(1) , the person complies with the requirements of this part that are relevant to the work.\n- (a) designing the works;\n- (b) building the works;\n- (c) maintaining or operating the works.","sortOrder":311},{"sectionNumber":"pt.12-div.2","sectionType":"division","heading":"Earthing and protection","content":"## Earthing and protection","sortOrder":312},{"sectionNumber":"sec.245","sectionType":"section","heading":"Systems of earthing","content":"### sec.245 Systems of earthing\n\nThe works of an electricity entity must incorporate an earthing and protection system, in accordance with relevant industry standards and practices, capable of ensuring the following—\nreliable passage of fault current;\nreliable passage of single wire earth return load currents to ground or source;\nreliable operation of circuit protection devices;\nsafe step, touch and transfer potentials for all electrical equipment;\nappropriate coordination with the earthing and protection systems of other electricity entities;\nprotection against likely mechanical damage, inadvertent interference and chemical deterioration;\nmechanical stability and integrity of connections.\nWithout limiting subsection&#160;(1) , the following specific requirements apply for the works of an electricity entity—\nto stop, so far as is reasonably practicable, a person suffering electric shock—\nif the multiple earthed neutral system of earthing is used—the neutral conductor of the system must be effectively earthed; and\neach non-current carrying exposed conductive part of an electric line or generating plant must be effectively earthed;\neach non-current carrying exposed conductive part of a substation must be effectively earthed;\na system of earthing must be tested as soon as practicable after its installation to prove its effectiveness;\na high voltage electric line must be protected by a suitable fuse, circuit breaker or equivalent device.\nEarthing is not required under subsection&#160;(2) (a) (ii) or (b) if the electricity entity, in accordance with recognised practice in the electricity industry, considers for safety reasons that earthing is not appropriate in the circumstances.\n(sec.245-ssec.1) The works of an electricity entity must incorporate an earthing and protection system, in accordance with relevant industry standards and practices, capable of ensuring the following— reliable passage of fault current; reliable passage of single wire earth return load currents to ground or source; reliable operation of circuit protection devices; safe step, touch and transfer potentials for all electrical equipment; appropriate coordination with the earthing and protection systems of other electricity entities; protection against likely mechanical damage, inadvertent interference and chemical deterioration; mechanical stability and integrity of connections.\n(sec.245-ssec.2) Without limiting subsection&#160;(1) , the following specific requirements apply for the works of an electricity entity— to stop, so far as is reasonably practicable, a person suffering electric shock— if the multiple earthed neutral system of earthing is used—the neutral conductor of the system must be effectively earthed; and each non-current carrying exposed conductive part of an electric line or generating plant must be effectively earthed; each non-current carrying exposed conductive part of a substation must be effectively earthed; a system of earthing must be tested as soon as practicable after its installation to prove its effectiveness; a high voltage electric line must be protected by a suitable fuse, circuit breaker or equivalent device.\n(sec.245-ssec.3) Earthing is not required under subsection&#160;(2) (a) (ii) or (b) if the electricity entity, in accordance with recognised practice in the electricity industry, considers for safety reasons that earthing is not appropriate in the circumstances.\n- (a) reliable passage of fault current;\n- (b) reliable passage of single wire earth return load currents to ground or source;\n- (c) reliable operation of circuit protection devices;\n- (d) safe step, touch and transfer potentials for all electrical equipment;\n- (e) appropriate coordination with the earthing and protection systems of other electricity entities;\n- (f) protection against likely mechanical damage, inadvertent interference and chemical deterioration;\n- (g) mechanical stability and integrity of connections.\n- (a) to stop, so far as is reasonably practicable, a person suffering electric shock— (i) if the multiple earthed neutral system of earthing is used—the neutral conductor of the system must be effectively earthed; and (ii) each non-current carrying exposed conductive part of an electric line or generating plant must be effectively earthed;\n- (i) if the multiple earthed neutral system of earthing is used—the neutral conductor of the system must be effectively earthed; and\n- (ii) each non-current carrying exposed conductive part of an electric line or generating plant must be effectively earthed;\n- (b) each non-current carrying exposed conductive part of a substation must be effectively earthed;\n- (c) a system of earthing must be tested as soon as practicable after its installation to prove its effectiveness;\n- (d) a high voltage electric line must be protected by a suitable fuse, circuit breaker or equivalent device.\n- (i) if the multiple earthed neutral system of earthing is used—the neutral conductor of the system must be effectively earthed; and\n- (ii) each non-current carrying exposed conductive part of an electric line or generating plant must be effectively earthed;","sortOrder":313},{"sectionNumber":"sec.246","sectionType":"section","heading":"Connection of high voltage circuit to earth","content":"### sec.246 Connection of high voltage circuit to earth\n\nEach distinct high voltage system included in the works of an electricity entity must be connected to earth by direct connection or through a resistance or a reactance.\nAll reasonable precautions must be taken to ensure that, for all circumstances in which the system is to operate, fuses or circuit breakers in the system will operate during fault conditions.\n(sec.246-ssec.1) Each distinct high voltage system included in the works of an electricity entity must be connected to earth by direct connection or through a resistance or a reactance.\n(sec.246-ssec.2) All reasonable precautions must be taken to ensure that, for all circumstances in which the system is to operate, fuses or circuit breakers in the system will operate during fault conditions.","sortOrder":314},{"sectionNumber":"sec.247","sectionType":"section","heading":"Performance and other requirements for works","content":"### sec.247 Performance and other requirements for works\n\nThe following requirements apply for the works of an electricity entity—\nthe works must be able to perform under the service conditions and the physical environment in which the works operate;\nthe works must have enough thermal capacity to pass the electrical load for which the works are designed, without reduction of electrical or mechanical properties to a level below that at which safe operational performance can be provided;\nto the greatest practicable extent, the works must have enough capacity to pass short circuit currents to allow protective devices to operate correctly;\nthe works must have enough mechanical strength to withstand anticipated mechanical stresses caused by environmental, construction or service conditions;\nthe works must be—\ndesigned and constructed to restrict unauthorised access by a person to live exposed parts; and\noperated in a way that restricts unauthorised access by a person to live exposed parts;\nrecords about the design, construction, operation and maintenance, and testing and inspection of the works that are necessary for the electrical safety of the works must be kept in an accessible form;\nparts of the works whose identity or purpose is not obvious must be clearly identified by labels, and the labels must be updated as soon as possible after any change is made to the works;\nelectrical equipment intended to form part of the works must undergo commissioning tests and inspection to verify the electrical equipment is suitable for service and can be operated safely when initially installed or altered.\n- (a) the works must be able to perform under the service conditions and the physical environment in which the works operate;\n- (b) the works must have enough thermal capacity to pass the electrical load for which the works are designed, without reduction of electrical or mechanical properties to a level below that at which safe operational performance can be provided;\n- (c) to the greatest practicable extent, the works must have enough capacity to pass short circuit currents to allow protective devices to operate correctly;\n- (d) the works must have enough mechanical strength to withstand anticipated mechanical stresses caused by environmental, construction or service conditions;\n- (e) the works must be— (i) designed and constructed to restrict unauthorised access by a person to live exposed parts; and (ii) operated in a way that restricts unauthorised access by a person to live exposed parts;\n- (i) designed and constructed to restrict unauthorised access by a person to live exposed parts; and\n- (ii) operated in a way that restricts unauthorised access by a person to live exposed parts;\n- (f) records about the design, construction, operation and maintenance, and testing and inspection of the works that are necessary for the electrical safety of the works must be kept in an accessible form;\n- (g) parts of the works whose identity or purpose is not obvious must be clearly identified by labels, and the labels must be updated as soon as possible after any change is made to the works;\n- (h) electrical equipment intended to form part of the works must undergo commissioning tests and inspection to verify the electrical equipment is suitable for service and can be operated safely when initially installed or altered.\n- (i) designed and constructed to restrict unauthorised access by a person to live exposed parts; and\n- (ii) operated in a way that restricts unauthorised access by a person to live exposed parts;","sortOrder":315},{"sectionNumber":"sec.248","sectionType":"section","heading":"Insulation of stay wire","content":"### sec.248 Insulation of stay wire\n\nIf a stay wire attached to a pole or structure supporting an overhead electric line forming part of the works of an electricity entity does not form part of an earthing system, the wire must be insulated to prevent, so far as is reasonably practicable, any person suffering an electric shock.","sortOrder":316},{"sectionNumber":"sec.249","sectionType":"section","heading":"Protection of earth conductors","content":"### sec.249 Protection of earth conductors\n\nTo prevent, so far as is reasonably practicable, any person suffering an electric shock, earthing conductors installed on the outside of a pole or structure supporting an overhead electric line forming part of the works of an electricity entity must be, from ground level to a height of at least 2.4m—\ninsulated or suitably covered by a non-conductive material; and\nprotected from mechanical damage.\n- (a) insulated or suitably covered by a non-conductive material; and\n- (b) protected from mechanical damage.","sortOrder":317},{"sectionNumber":"pt.12-div.3","sectionType":"division","heading":"Substations","content":"## Substations","sortOrder":318},{"sectionNumber":"sec.250","sectionType":"section","heading":"Substation requirements","content":"### sec.250 Substation requirements\n\nThe following requirements apply for a substation forming part of the works of an electricity entity—\nthere must be safe access to, and exit from, the substation;\na building or enclosure forming part of the substation must be secure, and all reasonable care must be taken to stop unauthorised access to the building or enclosure;\nelectrical equipment forming part of the substation must meet relevant standards for electrical safety of persons and property;\nthe substation must have appropriate signs, labels, warning notices and barriers.\n- (a) there must be safe access to, and exit from, the substation;\n- (b) a building or enclosure forming part of the substation must be secure, and all reasonable care must be taken to stop unauthorised access to the building or enclosure;\n- (c) electrical equipment forming part of the substation must meet relevant standards for electrical safety of persons and property;\n- (d) the substation must have appropriate signs, labels, warning notices and barriers.","sortOrder":319},{"sectionNumber":"pt.12-div.4","sectionType":"division","heading":"Electric lines and control cables","content":"## Electric lines and control cables","sortOrder":320},{"sectionNumber":"sec.251","sectionType":"section","heading":"Application of division","content":"### sec.251 Application of division\n\nThis division does not apply to electric lines and control cables that are part of a substation that is part of the works of an electricity entity.","sortOrder":321},{"sectionNumber":"sec.252","sectionType":"section","heading":"Measurement of vertical and horizontal distances","content":"### sec.252 Measurement of vertical and horizontal distances\n\nFor this division—\nthe vertical distance of a conductor from the ground is the length of a vertical line between the conductor and the ground; and\nthe vertical distance of a conductor from a structure that is immediately below the conductor is the length of a vertical line between the conductor and the point on the structure immediately below the conductor; and\nthe vertical distance of a conductor from a structure that is not immediately below the conductor is the length of a vertical line between the conductor and the horizontal projection of the nearest point on the structure to the conductor; and\nthe horizontal distance of a conductor from a structure is the length of a horizontal line from the conductor to the nearest point on the structure; and\nthe horizontal distance of a conductor from a verandah, balcony, road cutting, embankment or other similar thing is the length of a horizontal line from the conductor to the vertical projection of the nearest point on the verandah, balcony, road cutting, embankment or other similar thing; and\nthe horizontal distance of a conductor from a structure that is not immediately below the conductor is the length of a horizontal line from the conductor to the vertical projection of the nearest point on the structure.\n- (a) the vertical distance of a conductor from the ground is the length of a vertical line between the conductor and the ground; and\n- (b) the vertical distance of a conductor from a structure that is immediately below the conductor is the length of a vertical line between the conductor and the point on the structure immediately below the conductor; and\n- (c) the vertical distance of a conductor from a structure that is not immediately below the conductor is the length of a vertical line between the conductor and the horizontal projection of the nearest point on the structure to the conductor; and\n- (d) the horizontal distance of a conductor from a structure is the length of a horizontal line from the conductor to the nearest point on the structure; and\n- (e) the horizontal distance of a conductor from a verandah, balcony, road cutting, embankment or other similar thing is the length of a horizontal line from the conductor to the vertical projection of the nearest point on the verandah, balcony, road cutting, embankment or other similar thing; and\n- (f) the horizontal distance of a conductor from a structure that is not immediately below the conductor is the length of a horizontal line from the conductor to the vertical projection of the nearest point on the structure.","sortOrder":322},{"sectionNumber":"sec.253","sectionType":"section","heading":"Electric line and control cable requirements","content":"### sec.253 Electric line and control cable requirements\n\nEach of the following requirements apply for electric lines and control cables forming part of the works of an electricity entity—\nthe lines and cables must be designed and constructed to ensure—\ncompliance with applicable safety clearance requirements under sections&#160;254 to 257 , and 259, for clearance to the ground, buildings and other structures, and to other conductors; and\nthe clearances are appropriate having regard to environmental, construction and service conditions;\nunderground cables are installed in a way that takes account of local environmental and service conditions, the location of other public utility provider services and the risk of damage from excavation;\nif an underground cable is located above the surface of the ground at a particular place and is accessible to the public, it must be mechanically protected from the point at which it leaves the ground up to a height of 2.4m above any surface near the place on which a person is able to stand;\na low voltage overhead service must be an insulated cable or a neutral screened cable.\nIn this section—\ninsulated cable means an insulated aerial cable complying with—\nAS/NZS 5000.1 (Electric cables—Polymeric insulated—For working voltages up to and including 0.6/1 (1.2) kV); or\nAS/NZS 3560.1 (Electric cables—Cross-linked polyethylene insulated—Aerial bundled—For working voltages up to and including 0.6/1(1.2) kV).\n(sec.253-ssec.1) Each of the following requirements apply for electric lines and control cables forming part of the works of an electricity entity— the lines and cables must be designed and constructed to ensure— compliance with applicable safety clearance requirements under sections&#160;254 to 257 , and 259, for clearance to the ground, buildings and other structures, and to other conductors; and the clearances are appropriate having regard to environmental, construction and service conditions; underground cables are installed in a way that takes account of local environmental and service conditions, the location of other public utility provider services and the risk of damage from excavation; if an underground cable is located above the surface of the ground at a particular place and is accessible to the public, it must be mechanically protected from the point at which it leaves the ground up to a height of 2.4m above any surface near the place on which a person is able to stand; a low voltage overhead service must be an insulated cable or a neutral screened cable.\n(sec.253-ssec.2) In this section— insulated cable means an insulated aerial cable complying with— AS/NZS 5000.1 (Electric cables—Polymeric insulated—For working voltages up to and including 0.6/1 (1.2) kV); or AS/NZS 3560.1 (Electric cables—Cross-linked polyethylene insulated—Aerial bundled—For working voltages up to and including 0.6/1(1.2) kV).\n- (a) the lines and cables must be designed and constructed to ensure— (i) compliance with applicable safety clearance requirements under sections&#160;254 to 257 , and 259, for clearance to the ground, buildings and other structures, and to other conductors; and (ii) the clearances are appropriate having regard to environmental, construction and service conditions;\n- (i) compliance with applicable safety clearance requirements under sections&#160;254 to 257 , and 259, for clearance to the ground, buildings and other structures, and to other conductors; and\n- (ii) the clearances are appropriate having regard to environmental, construction and service conditions;\n- (b) underground cables are installed in a way that takes account of local environmental and service conditions, the location of other public utility provider services and the risk of damage from excavation;\n- (c) if an underground cable is located above the surface of the ground at a particular place and is accessible to the public, it must be mechanically protected from the point at which it leaves the ground up to a height of 2.4m above any surface near the place on which a person is able to stand;\n- (d) a low voltage overhead service must be an insulated cable or a neutral screened cable.\n- (i) compliance with applicable safety clearance requirements under sections&#160;254 to 257 , and 259, for clearance to the ground, buildings and other structures, and to other conductors; and\n- (ii) the clearances are appropriate having regard to environmental, construction and service conditions;\n- (a) AS/NZS 5000.1 (Electric cables—Polymeric insulated—For working voltages up to and including 0.6/1 (1.2) kV); or\n- (b) AS/NZS 3560.1 (Electric cables—Cross-linked polyethylene insulated—Aerial bundled—For working voltages up to and including 0.6/1(1.2) kV).","sortOrder":323},{"sectionNumber":"sec.254","sectionType":"section","heading":"Clearance from exposed conductive parts and separation of conductors in same circuit","content":"### sec.254 Clearance from exposed conductive parts and separation of conductors in same circuit\n\nExposed conductors in the same circuit of an overhead electric line forming part of the works of an electricity entity must be separated so that, so far as is reasonably practicable, a conductor does not come in contact with or come within arcing distance of—\nanother conductor; or\nan earthed exposed conductive part; or\na stay wire attached to a pole or structure supporting an overhead electric line.\n- (a) another conductor; or\n- (b) an earthed exposed conductive part; or\n- (c) a stay wire attached to a pole or structure supporting an overhead electric line.","sortOrder":324},{"sectionNumber":"sec.255","sectionType":"section","heading":"Location of overhead circuit in relation to another overhead circuit","content":"### sec.255 Location of overhead circuit in relation to another overhead circuit\n\nThis section applies if the overhead circuits of electric lines forming part of the works of 1 or more electricity entities include different overhead circuits of electric lines that are adjacent, or that cross, and that are on 1 structure.\nThe circuits must be placed as follows—\n2 or more low voltage circuits must be placed 1 above the other or side by side;\n2 or more high voltage circuits must be placed 1 above the other or side by side;\nlow voltage circuits must be placed below high voltage circuits;\nif 2 or more high voltage circuits are placed 1 above the other, any lower voltage circuit must be placed below any higher voltage circuit.\nSubsection&#160;(2) (c) does not apply to conductors erected on a pole transformer substation.\nSubsection&#160;(2) (d) does not apply if an electricity entity considers that—\nexceptional circumstances apply; and\nfailure to comply with the requirement would not create an unsafe or hazardous situation.\n(sec.255-ssec.1) This section applies if the overhead circuits of electric lines forming part of the works of 1 or more electricity entities include different overhead circuits of electric lines that are adjacent, or that cross, and that are on 1 structure.\n(sec.255-ssec.2) The circuits must be placed as follows— 2 or more low voltage circuits must be placed 1 above the other or side by side; 2 or more high voltage circuits must be placed 1 above the other or side by side; low voltage circuits must be placed below high voltage circuits; if 2 or more high voltage circuits are placed 1 above the other, any lower voltage circuit must be placed below any higher voltage circuit.\n(sec.255-ssec.3) Subsection&#160;(2) (c) does not apply to conductors erected on a pole transformer substation.\n(sec.255-ssec.4) Subsection&#160;(2) (d) does not apply if an electricity entity considers that— exceptional circumstances apply; and failure to comply with the requirement would not create an unsafe or hazardous situation.\n- (a) 2 or more low voltage circuits must be placed 1 above the other or side by side;\n- (b) 2 or more high voltage circuits must be placed 1 above the other or side by side;\n- (c) low voltage circuits must be placed below high voltage circuits;\n- (d) if 2 or more high voltage circuits are placed 1 above the other, any lower voltage circuit must be placed below any higher voltage circuit.\n- (a) exceptional circumstances apply; and\n- (b) failure to comply with the requirement would not create an unsafe or hazardous situation.","sortOrder":325},{"sectionNumber":"sec.256","sectionType":"section","heading":"Clearance of overhead electric lines from ground","content":"### sec.256 Clearance of overhead electric lines from ground\n\nAn electricity entity must ensure the distance from the conductors of its overhead electric lines to the ground is the distance required under—\nfor an overhead electric line, including a high voltage overhead service line— schedule&#160;6 , parts&#160;2 and 4 ; and\nfor a low voltage overhead service line— schedule&#160;7 , part&#160;2 .\nSubsection&#160;(1) does not apply to electric cables known as aerial bundled cables installed with a clearance from the ground decided by the electricity entity to be a safe clearance considering the nature of the cables and their location.\n(sec.256-ssec.1) An electricity entity must ensure the distance from the conductors of its overhead electric lines to the ground is the distance required under— for an overhead electric line, including a high voltage overhead service line— schedule&#160;6 , parts&#160;2 and 4 ; and for a low voltage overhead service line— schedule&#160;7 , part&#160;2 .\n(sec.256-ssec.2) Subsection&#160;(1) does not apply to electric cables known as aerial bundled cables installed with a clearance from the ground decided by the electricity entity to be a safe clearance considering the nature of the cables and their location.\n- (a) for an overhead electric line, including a high voltage overhead service line— schedule&#160;6 , parts&#160;2 and 4 ; and\n- (b) for a low voltage overhead service line— schedule&#160;7 , part&#160;2 .","sortOrder":326},{"sectionNumber":"sec.257","sectionType":"section","heading":"Clearance of overhead electric lines from structures","content":"### sec.257 Clearance of overhead electric lines from structures\n\nAn electricity entity must ensure the distance from the conductors of its overhead electric lines to a structure is as required under—\nfor an overhead electric line, including a high voltage overhead service line— schedule&#160;6 , parts&#160;3 and 5 ; and\nfor a low voltage overhead service line— schedule&#160;7 , part&#160;3 .\nSubsection&#160;(1) does not apply to electric cables known as aerial bundled cables installed with a clearance from a structure decided by the electricity entity to be a safe clearance considering the nature of the cables and their location.\n(sec.257-ssec.1) An electricity entity must ensure the distance from the conductors of its overhead electric lines to a structure is as required under— for an overhead electric line, including a high voltage overhead service line— schedule&#160;6 , parts&#160;3 and 5 ; and for a low voltage overhead service line— schedule&#160;7 , part&#160;3 .\n(sec.257-ssec.2) Subsection&#160;(1) does not apply to electric cables known as aerial bundled cables installed with a clearance from a structure decided by the electricity entity to be a safe clearance considering the nature of the cables and their location.\n- (a) for an overhead electric line, including a high voltage overhead service line— schedule&#160;6 , parts&#160;3 and 5 ; and\n- (b) for a low voltage overhead service line— schedule&#160;7 , part&#160;3 .","sortOrder":327},{"sectionNumber":"sec.258","sectionType":"section","heading":"Building or adding to structure near electric line","content":"### sec.258 Building or adding to structure near electric line\n\nThis section applies if—\na person proposes to perform work; and\nthe proposed work is either or both of the following—\nthe construction of a building or other structure or of a change to a building or other structure;\nother work in relation to a building or other structure; and\nthe proposed work is likely to involve the building or other structure—\ncoming within the clearance requirements under this division for an overhead electric line; or\naffecting the electrical safety of an underground electric line.\nThe person must, before the work starts, give the electricity entity whose works include the electric line written notice in a form approved by the electricity entity.\nMaximum penalty—40 penalty units.\nOn receiving the notice, the electricity entity must—\ntake the action necessary to protect its works while the work is being performed and to ensure the requirements of section&#160;14 will be complied with while the work is being performed; and\nrelocate or change the electric line so that after the work is completed—\nthe requirements of this regulation for clearances will be complied with; and\nthe electric line will be accessible to the electricity entity’s employees for the line’s operation and maintenance.\nUnless otherwise agreed between the electricity entity and the person—\nthe person must pay the costs reasonably incurred by the electricity entity under subsection&#160;(3) ; and\nthe costs are a debt payable by the person to the electricity entity.\n(sec.258-ssec.1) This section applies if— a person proposes to perform work; and the proposed work is either or both of the following— the construction of a building or other structure or of a change to a building or other structure; other work in relation to a building or other structure; and the proposed work is likely to involve the building or other structure— coming within the clearance requirements under this division for an overhead electric line; or affecting the electrical safety of an underground electric line.\n(sec.258-ssec.2) The person must, before the work starts, give the electricity entity whose works include the electric line written notice in a form approved by the electricity entity. Maximum penalty—40 penalty units.\n(sec.258-ssec.3) On receiving the notice, the electricity entity must— take the action necessary to protect its works while the work is being performed and to ensure the requirements of section&#160;14 will be complied with while the work is being performed; and relocate or change the electric line so that after the work is completed— the requirements of this regulation for clearances will be complied with; and the electric line will be accessible to the electricity entity’s employees for the line’s operation and maintenance.\n(sec.258-ssec.4) Unless otherwise agreed between the electricity entity and the person— the person must pay the costs reasonably incurred by the electricity entity under subsection&#160;(3) ; and the costs are a debt payable by the person to the electricity entity.\n- (a) a person proposes to perform work; and\n- (b) the proposed work is either or both of the following— (i) the construction of a building or other structure or of a change to a building or other structure; (ii) other work in relation to a building or other structure; and\n- (i) the construction of a building or other structure or of a change to a building or other structure;\n- (ii) other work in relation to a building or other structure; and\n- (c) the proposed work is likely to involve the building or other structure— (i) coming within the clearance requirements under this division for an overhead electric line; or (ii) affecting the electrical safety of an underground electric line.\n- (i) coming within the clearance requirements under this division for an overhead electric line; or\n- (ii) affecting the electrical safety of an underground electric line.\n- (i) the construction of a building or other structure or of a change to a building or other structure;\n- (ii) other work in relation to a building or other structure; and\n- (i) coming within the clearance requirements under this division for an overhead electric line; or\n- (ii) affecting the electrical safety of an underground electric line.\n- (a) take the action necessary to protect its works while the work is being performed and to ensure the requirements of section&#160;14 will be complied with while the work is being performed; and\n- (b) relocate or change the electric line so that after the work is completed— (i) the requirements of this regulation for clearances will be complied with; and (ii) the electric line will be accessible to the electricity entity’s employees for the line’s operation and maintenance.\n- (i) the requirements of this regulation for clearances will be complied with; and\n- (ii) the electric line will be accessible to the electricity entity’s employees for the line’s operation and maintenance.\n- (i) the requirements of this regulation for clearances will be complied with; and\n- (ii) the electric line will be accessible to the electricity entity’s employees for the line’s operation and maintenance.\n- (a) the person must pay the costs reasonably incurred by the electricity entity under subsection&#160;(3) ; and\n- (b) the costs are a debt payable by the person to the electricity entity.","sortOrder":328},{"sectionNumber":"sec.259","sectionType":"section","heading":"Clearance of stay wires and control cables over road","content":"### sec.259 Clearance of stay wires and control cables over road\n\nAn electricity entity’s overhead stay wire or overhead control cable crossing the carriageway of a road must have clearance from the ground of at least—\n5.5m at the centre line of the carriageway; and\n4.9m at the kerb line of the road.\n- (a) 5.5m at the centre line of the carriageway; and\n- (b) 4.9m at the kerb line of the road.","sortOrder":329},{"sectionNumber":"sec.260","sectionType":"section","heading":"Connection to consumer’s premises","content":"### sec.260 Connection to consumer’s premises\n\nAn electricity entity, in supplying electricity to a consumer, must decide the position of its fuses, circuit breakers, disconnection links and other apparatus in accordance with recognised practice in the electricity industry.","sortOrder":330},{"sectionNumber":"pt.12-div.5","sectionType":"division","heading":"Termination requirements for low voltage overhead service lines","content":"## Termination requirements for low voltage overhead service lines","sortOrder":331},{"sectionNumber":"sec.261","sectionType":"section","heading":"Termination of low voltage overhead service line","content":"### sec.261 Termination of low voltage overhead service line\n\nAn electricity entity must ensure a low voltage overhead service line is—\nsecured to a consumer’s premises, including poles on the premises; and\ninsulated continuously; and\nnot readily accessible to persons.\nAn electricity entity must ensure a metallic pin, eye bolt or other similar fixture installed by or for the electricity entity on a consumer’s premises to support an active conductor of a low voltage overhead service line is effectively earthed.\nThe earthing must be by direct connection to the neutral conductor of the service line, at the point of support, by a conductor having an appropriate cross-sectional area.\nEarthing under subsections&#160;(2) and (3) is not required if—\nthe low voltage overhead service line is a neutral screened cable and the service fuse is mounted on the electricity entity’s pole; or\nno part of the metallic pin, eye bolt or other similar fixture, or of a metal bracket or riser supporting it, is within 25mm of other metal work on a building, pole or other structure.\n(sec.261-ssec.1) An electricity entity must ensure a low voltage overhead service line is— secured to a consumer’s premises, including poles on the premises; and insulated continuously; and not readily accessible to persons.\n(sec.261-ssec.2) An electricity entity must ensure a metallic pin, eye bolt or other similar fixture installed by or for the electricity entity on a consumer’s premises to support an active conductor of a low voltage overhead service line is effectively earthed.\n(sec.261-ssec.3) The earthing must be by direct connection to the neutral conductor of the service line, at the point of support, by a conductor having an appropriate cross-sectional area.\n(sec.261-ssec.4) Earthing under subsections&#160;(2) and (3) is not required if— the low voltage overhead service line is a neutral screened cable and the service fuse is mounted on the electricity entity’s pole; or no part of the metallic pin, eye bolt or other similar fixture, or of a metal bracket or riser supporting it, is within 25mm of other metal work on a building, pole or other structure.\n- (a) secured to a consumer’s premises, including poles on the premises; and\n- (b) insulated continuously; and\n- (c) not readily accessible to persons.\n- (a) the low voltage overhead service line is a neutral screened cable and the service fuse is mounted on the electricity entity’s pole; or\n- (b) no part of the metallic pin, eye bolt or other similar fixture, or of a metal bracket or riser supporting it, is within 25mm of other metal work on a building, pole or other structure.","sortOrder":332},{"sectionNumber":"pt.12-div.6","sectionType":"division","heading":"Service lines generally","content":"## Service lines generally","sortOrder":333},{"sectionNumber":"sec.262","sectionType":"section","heading":"Fuses and disconnectors for service line","content":"### sec.262 Fuses and disconnectors for service line\n\nAn electricity entity must provide a fuse or circuit breaker for each active conductor of a low voltage service line that provides fault current protection for a consumer’s electrical installation unless—\nelectricity to the consumer’s electrical installation is supplied direct from a transformer; and\nthe electricity entity is satisfied the fuse or circuit breaker of the transformer provides enough protection for the consumer’s electrical installation; and\nthe electricity entity uses the fuse or circuit breaker of the transformer instead of a fuse or circuit breaker in the low voltage service line.\nHowever, if under subsection&#160;(1) the electricity entity uses the fuse or circuit breaker of the transformer instead of a fuse or circuit breaker in the low voltage service line, the electricity entity must install isolating links in the electric line supplying the consumer’s electrical installation if another consumer’s electrical installation is also supplied from the transformer.\nAlso, if the electricity entity is not satisfied the fuse or circuit breaker of the transformer provides enough protection for the consumer’s electrical installation, the electricity entity must provide suitable protection on the low voltage side of the transformer.\nSubsection&#160;(3) does not apply if the electricity entity is satisfied that suitable protection is provided in the consumer’s electrical installation.\n(sec.262-ssec.1) An electricity entity must provide a fuse or circuit breaker for each active conductor of a low voltage service line that provides fault current protection for a consumer’s electrical installation unless— electricity to the consumer’s electrical installation is supplied direct from a transformer; and the electricity entity is satisfied the fuse or circuit breaker of the transformer provides enough protection for the consumer’s electrical installation; and the electricity entity uses the fuse or circuit breaker of the transformer instead of a fuse or circuit breaker in the low voltage service line.\n(sec.262-ssec.2) However, if under subsection&#160;(1) the electricity entity uses the fuse or circuit breaker of the transformer instead of a fuse or circuit breaker in the low voltage service line, the electricity entity must install isolating links in the electric line supplying the consumer’s electrical installation if another consumer’s electrical installation is also supplied from the transformer.\n(sec.262-ssec.3) Also, if the electricity entity is not satisfied the fuse or circuit breaker of the transformer provides enough protection for the consumer’s electrical installation, the electricity entity must provide suitable protection on the low voltage side of the transformer.\n(sec.262-ssec.4) Subsection&#160;(3) does not apply if the electricity entity is satisfied that suitable protection is provided in the consumer’s electrical installation.\n- (a) electricity to the consumer’s electrical installation is supplied direct from a transformer; and\n- (b) the electricity entity is satisfied the fuse or circuit breaker of the transformer provides enough protection for the consumer’s electrical installation; and\n- (c) the electricity entity uses the fuse or circuit breaker of the transformer instead of a fuse or circuit breaker in the low voltage service line.","sortOrder":334},{"sectionNumber":"sec.263","sectionType":"section","heading":"Disused service line to be disconnected","content":"### sec.263 Disused service line to be disconnected\n\nAn electricity entity must ensure a service line for a consumer’s premises is disconnected and sufficiently isolated from any electric line forming part of its works if—\nthe supply of electricity to the consumer’s premises has been disconnected; and\nthe electricity entity has removed any of its meters, control apparatus or other electrical equipment from the premises.\n- (a) the supply of electricity to the consumer’s premises has been disconnected; and\n- (b) the electricity entity has removed any of its meters, control apparatus or other electrical equipment from the premises.","sortOrder":335},{"sectionNumber":"pt.12-div.7","sectionType":"division","heading":"Maintenance of works","content":"## Maintenance of works","sortOrder":336},{"sectionNumber":"sec.264","sectionType":"section","heading":"Inspection and maintenance of integrity of insulation","content":"### sec.264 Inspection and maintenance of integrity of insulation\n\nAn electricity entity must ensure the integrity of the insulation of the relevant part of the electricity entity’s works is inspected and maintained.\nAn electricity entity must ensure the integrity of insulation for the clamp or other apparatus at the point where consumer mains are connected to the electricity entity’s service line is inspected and maintained.\nInspection and maintenance under subsection&#160;(1) or (2) must be performed at periodic reasonable intervals.\nIn this section—\nreasonable interval , for the inspection and maintenance of insulation, means an interval, based on historic performance and the degree of electrical risk, that is reasonable in the circumstances.\nrelevant part , of an electricity entity’s works, means the part of an electric line forming part of the works that—\nis adjacent to a roof or structure; and\nis in a position where it is likely that a person could come into contact with the line.\na painter, a plumber\n(sec.264-ssec.1) An electricity entity must ensure the integrity of the insulation of the relevant part of the electricity entity’s works is inspected and maintained.\n(sec.264-ssec.2) An electricity entity must ensure the integrity of insulation for the clamp or other apparatus at the point where consumer mains are connected to the electricity entity’s service line is inspected and maintained.\n(sec.264-ssec.3) Inspection and maintenance under subsection&#160;(1) or (2) must be performed at periodic reasonable intervals.\n(sec.264-ssec.4) In this section— reasonable interval , for the inspection and maintenance of insulation, means an interval, based on historic performance and the degree of electrical risk, that is reasonable in the circumstances. relevant part , of an electricity entity’s works, means the part of an electric line forming part of the works that— is adjacent to a roof or structure; and is in a position where it is likely that a person could come into contact with the line. a painter, a plumber\n- (a) is adjacent to a roof or structure; and\n- (b) is in a position where it is likely that a person could come into contact with the line. Examples of a person who is likely to come into contact with the line— a painter, a plumber","sortOrder":337},{"sectionNumber":"sec.265","sectionType":"section","heading":"Trimming of trees near overhead electric line","content":"### sec.265 Trimming of trees near overhead electric line\n\nAn electricity entity must ensure trees and other vegetation are trimmed, and other measures are taken, to prevent contact with an overhead electric line forming part of the electricity entity’s works that is likely to cause injury from electric shock to any person or damage to property.","sortOrder":338},{"sectionNumber":"pt.13","sectionType":"part","heading":"Cathodic protection systems","content":"# Cathodic protection systems","sortOrder":339},{"sectionNumber":"pt.13-div.1","sectionType":"division","heading":"Preliminary","content":"## Preliminary","sortOrder":340},{"sectionNumber":"sec.266","sectionType":"section","heading":"Definitions for part","content":"### sec.266 Definitions for part\n\nIn this part—\nanode , in relation to a cathodic protection system, means a part of the system that is an electrical conductor placed in contact with ground or water.\ncathodically protected structure means a structure protected by a cathodic protection system.\ncathodic protection standard means the following standards that are part of the series AS 2832 (Cathodic protection of metals)—\nAS 2832.1 ( Part&#160;1 —Pipes and cables);\nAS 2832.2 ( Part&#160;2 —Compact buried structures);\nAS 2832.3 ( Part&#160;3 —Fixed immersed structures);\nAS 2832.4 ( Part&#160;4 —Internal surfaces);\nAS 2832.5 ( Part&#160;5 —Steel in concrete structures).\nforeign structure , for a cathodic protection system, means a structure that is buried or submerged and that may be subject to interference arising from the system.\nforeign structure owner , for a cathodic protection system, means a person who owns a foreign structure for the system.\nimpressed current cathodic protection system means a cathodic protection system in which the current flowing between the cathodically protected structure and the anode is supplied by an external source.\nmaximum operating current , for a cathodic protection system, means the maximum value of the fixed, manually variable or automatically variable current at which the system operates, other than during short-term testing of the system.\nregistered system means a registrable system registered under this part.\nregistrable system means an impressed current cathodic protection system the converter of which is capable of delivering a current greater than 0.25A.\nshort-term testing , of a cathodic protection system, means testing for less than a total of 30 minutes in any 7 consecutive days.\n- (a) AS 2832.1 ( Part&#160;1 —Pipes and cables);\n- (b) AS 2832.2 ( Part&#160;2 —Compact buried structures);\n- (c) AS 2832.3 ( Part&#160;3 —Fixed immersed structures);\n- (d) AS 2832.4 ( Part&#160;4 —Internal surfaces);\n- (e) AS 2832.5 ( Part&#160;5 —Steel in concrete structures).","sortOrder":341},{"sectionNumber":"sec.267","sectionType":"section","heading":"Electrical values","content":"### sec.267 Electrical values\n\nIn this part, electrical values are the values as they apply for direct current.\n500mV means 500mV d.c.\n50V means 50V d.c.\n- • 500mV means 500mV d.c.\n- • 50V means 50V d.c.","sortOrder":342},{"sectionNumber":"sec.268","sectionType":"section","heading":"Exclusion from application","content":"### sec.268 Exclusion from application\n\nUnless otherwise stated in this part, this part does not apply to a cathodic protection system installed on—\na floating mobile structure; or\nfishing equipment; or\na fixed offshore structure not connected with land above sea level; or\nan internal surface of an apparatus, structure or item of equipment to which the cathodic protection standard AS 2832.4 ( Part&#160;4 —Internal surfaces) applies.\n- (a) a floating mobile structure; or\n- (b) fishing equipment; or\n- (c) a fixed offshore structure not connected with land above sea level; or\n- (d) an internal surface of an apparatus, structure or item of equipment to which the cathodic protection standard AS 2832.4 ( Part&#160;4 —Internal surfaces) applies.","sortOrder":343},{"sectionNumber":"pt.13-div.2","sectionType":"division","heading":"Installation and design","content":"## Installation and design","sortOrder":344},{"sectionNumber":"sec.269","sectionType":"section","heading":"Installation of system only if preliminary steps taken","content":"### sec.269 Installation of system only if preliminary steps taken\n\nA person must not start to install a cathodic protection system unless the person has complied with subsection&#160;(2) .\nMaximum penalty—40 penalty units.\nAt least 60 days before starting installation, the person must—\nadvise all relevant persons for the proposed cathodic protection system of the proposal to install the system; and\nallow the relevant persons to examine the proposal.\nIn this section—\nrelevant person , for a proposed cathodic protection system, means a person who will, if the system is installed, become a foreign structure owner for the system.\n(sec.269-ssec.1) A person must not start to install a cathodic protection system unless the person has complied with subsection&#160;(2) . Maximum penalty—40 penalty units.\n(sec.269-ssec.2) At least 60 days before starting installation, the person must— advise all relevant persons for the proposed cathodic protection system of the proposal to install the system; and allow the relevant persons to examine the proposal.\n(sec.269-ssec.3) In this section— relevant person , for a proposed cathodic protection system, means a person who will, if the system is installed, become a foreign structure owner for the system.\n- (a) advise all relevant persons for the proposed cathodic protection system of the proposal to install the system; and\n- (b) allow the relevant persons to examine the proposal.","sortOrder":345},{"sectionNumber":"sec.270","sectionType":"section","heading":"Correct design and installation of system","content":"### sec.270 Correct design and installation of system\n\nA person who owns a cathodic protection system must ensure the system is designed and installed in accordance with the requirements of the cathodic protection standard.\nMaximum penalty—40 penalty units.","sortOrder":346},{"sectionNumber":"pt.13-div.3","sectionType":"division","heading":"Operating requirements","content":"## Operating requirements","sortOrder":347},{"sectionNumber":"sec.271","sectionType":"section","heading":"Requirements for operation of system","content":"### sec.271 Requirements for operation of system\n\nThe owner of a cathodic protection system must not operate the system unless—\nthe system has been tested in accordance with the testing requirements of this part; and\neach foreign structure owner for the system has stated either that interference mitigation is satisfactory or is not required; and\nthe system is operated in accordance with the requirements of the cathodic protection standard; and\nif the system is a registrable system—the system is a registered system and is operated in accordance with the requirements of the conditions of its registration.\nMaximum penalty—40 penalty units.\nDespite subsection&#160;(1) (b) , (c) and (d) , a person may operate a cathodic protection system for a reasonable period to perform tests in accordance with the testing requirements of this part.\n(sec.271-ssec.1) The owner of a cathodic protection system must not operate the system unless— the system has been tested in accordance with the testing requirements of this part; and each foreign structure owner for the system has stated either that interference mitigation is satisfactory or is not required; and the system is operated in accordance with the requirements of the cathodic protection standard; and if the system is a registrable system—the system is a registered system and is operated in accordance with the requirements of the conditions of its registration. Maximum penalty—40 penalty units.\n(sec.271-ssec.2) Despite subsection&#160;(1) (b) , (c) and (d) , a person may operate a cathodic protection system for a reasonable period to perform tests in accordance with the testing requirements of this part.\n- (a) the system has been tested in accordance with the testing requirements of this part; and\n- (b) each foreign structure owner for the system has stated either that interference mitigation is satisfactory or is not required; and\n- (c) the system is operated in accordance with the requirements of the cathodic protection standard; and\n- (d) if the system is a registrable system—the system is a registered system and is operated in accordance with the requirements of the conditions of its registration.","sortOrder":348},{"sectionNumber":"pt.13-div.4","sectionType":"division","heading":"Testing requirements","content":"## Testing requirements","sortOrder":349},{"sectionNumber":"sec.272","sectionType":"section","heading":"Tests before registration or operation of system","content":"### sec.272 Tests before registration or operation of system\n\nThe owner of a cathodic protection system that is a registrable system must perform tests in accordance with this section within 90 days, or a longer period the regulator allows, before applying for registration of the system.\nMaximum penalty—40 penalty units.\nThe owner of a cathodic protection system that is not a registrable system must perform tests in accordance with this section within 90 days before starting to operate the system, other than for the tests.\nMaximum penalty—40 penalty units.\nThe tests are—\ninterference tests on all foreign structures for the system; and\nif the system has an anode immersed in water or a marine environment—tests to ensure the potential difference between any 2 accessible points spaced 1m apart in the water or marine environment are not more than 3V when the system is energised.\nThe tests must be based on the maximum value of the current at which the cathodic protection system will operate at all times, other than during short-term testing of the system in which currents of greater values are permitted.\nThe owner of the cathodic protection system must make all the arrangements for the tests, provide all the facilities and equipment for the tests and bear all the costs associated with the tests.\nWithout limiting subsection&#160;(5) , for the performance of an interference test mentioned in subsection&#160;(3) (a) , the owner of the cathodic protection system must—\narrange with all foreign structure owners a mutually acceptable time for performing the test; and\nallow the foreign structure owners to observe the performance of the test.\n(sec.272-ssec.1) The owner of a cathodic protection system that is a registrable system must perform tests in accordance with this section within 90 days, or a longer period the regulator allows, before applying for registration of the system. Maximum penalty—40 penalty units.\n(sec.272-ssec.2) The owner of a cathodic protection system that is not a registrable system must perform tests in accordance with this section within 90 days before starting to operate the system, other than for the tests. Maximum penalty—40 penalty units.\n(sec.272-ssec.3) The tests are— interference tests on all foreign structures for the system; and if the system has an anode immersed in water or a marine environment—tests to ensure the potential difference between any 2 accessible points spaced 1m apart in the water or marine environment are not more than 3V when the system is energised.\n(sec.272-ssec.4) The tests must be based on the maximum value of the current at which the cathodic protection system will operate at all times, other than during short-term testing of the system in which currents of greater values are permitted.\n(sec.272-ssec.5) The owner of the cathodic protection system must make all the arrangements for the tests, provide all the facilities and equipment for the tests and bear all the costs associated with the tests.\n(sec.272-ssec.6) Without limiting subsection&#160;(5) , for the performance of an interference test mentioned in subsection&#160;(3) (a) , the owner of the cathodic protection system must— arrange with all foreign structure owners a mutually acceptable time for performing the test; and allow the foreign structure owners to observe the performance of the test.\n- (a) interference tests on all foreign structures for the system; and\n- (b) if the system has an anode immersed in water or a marine environment—tests to ensure the potential difference between any 2 accessible points spaced 1m apart in the water or marine environment are not more than 3V when the system is energised.\n- (a) arrange with all foreign structure owners a mutually acceptable time for performing the test; and\n- (b) allow the foreign structure owners to observe the performance of the test.","sortOrder":350},{"sectionNumber":"sec.273","sectionType":"section","heading":"Further tests for registered system","content":"### sec.273 Further tests for registered system\n\nThis section applies to a cathodic protection system that is a registered system.\nThe owner of the registered system must perform interference tests on all foreign structures for the system—\nwhen an anode forming part of the system is replaced; and\nif required by the regulator—when the system, or its method of operation, is changed.\nMaximum penalty—40 penalty units.\nSubsection&#160;(4) applies if—\nan anode forming part of the registered system is immersed in water or a marine environment; and\nthe anode is redesigned, causing it to be relocated or to become subject to variation in anode current distribution.\nThe owner of the registered system must, as soon as practicable after the anode is redesigned, retest the system to ensure the potential difference between any 2 accessible points spaced 1m apart in the water or marine environment is not more than 3V when the system is energised.\nMaximum penalty—40 penalty units.\nIf, when interference tests are being performed, there is a foreign structure for the registered system for which interference tests have not previously been performed, the owner of the system must—\narrange with the foreign structure owner a mutually acceptable time for performing the tests; and\nallow the foreign structure owner to observe the performance of the tests.\nMaximum penalty—40 penalty units.\n(sec.273-ssec.1) This section applies to a cathodic protection system that is a registered system.\n(sec.273-ssec.2) The owner of the registered system must perform interference tests on all foreign structures for the system— when an anode forming part of the system is replaced; and if required by the regulator—when the system, or its method of operation, is changed. Maximum penalty—40 penalty units.\n(sec.273-ssec.3) Subsection&#160;(4) applies if— an anode forming part of the registered system is immersed in water or a marine environment; and the anode is redesigned, causing it to be relocated or to become subject to variation in anode current distribution.\n(sec.273-ssec.4) The owner of the registered system must, as soon as practicable after the anode is redesigned, retest the system to ensure the potential difference between any 2 accessible points spaced 1m apart in the water or marine environment is not more than 3V when the system is energised. Maximum penalty—40 penalty units.\n(sec.273-ssec.5) If, when interference tests are being performed, there is a foreign structure for the registered system for which interference tests have not previously been performed, the owner of the system must— arrange with the foreign structure owner a mutually acceptable time for performing the tests; and allow the foreign structure owner to observe the performance of the tests. Maximum penalty—40 penalty units.\n- (a) when an anode forming part of the system is replaced; and\n- (b) if required by the regulator—when the system, or its method of operation, is changed.\n- (a) an anode forming part of the registered system is immersed in water or a marine environment; and\n- (b) the anode is redesigned, causing it to be relocated or to become subject to variation in anode current distribution.\n- (a) arrange with the foreign structure owner a mutually acceptable time for performing the tests; and\n- (b) allow the foreign structure owner to observe the performance of the tests.","sortOrder":351},{"sectionNumber":"sec.274","sectionType":"section","heading":"Further tests for particular systems","content":"### sec.274 Further tests for particular systems\n\nThe owner of a relevant system must perform interference tests on all foreign structures for the system—\nwhen an anode forming part of the system is replaced; and\nwhen the system or its method of operation is changed.\nMaximum penalty—40 penalty units.\nIn this section—\nrelevant system means—\na cathodic protection system, other than a registered system, that is an impressed current cathodic protection system; or\na cathodic protection system with a total anode mass of more than 25kg.\n(sec.274-ssec.1) The owner of a relevant system must perform interference tests on all foreign structures for the system— when an anode forming part of the system is replaced; and when the system or its method of operation is changed. Maximum penalty—40 penalty units.\n(sec.274-ssec.2) In this section— relevant system means— a cathodic protection system, other than a registered system, that is an impressed current cathodic protection system; or a cathodic protection system with a total anode mass of more than 25kg.\n- (a) when an anode forming part of the system is replaced; and\n- (b) when the system or its method of operation is changed.\n- (a) a cathodic protection system, other than a registered system, that is an impressed current cathodic protection system; or\n- (b) a cathodic protection system with a total anode mass of more than 25kg.","sortOrder":352},{"sectionNumber":"sec.275","sectionType":"section","heading":"Further tests of new foreign structure if required by the regulator","content":"### sec.275 Further tests of new foreign structure if required by the regulator\n\nIf required by the regulator, the owner of a cathodic protection system must perform interference tests on a foreign structure for the system not previously tested by the owner.\nMaximum penalty—40 penalty units.","sortOrder":353},{"sectionNumber":"sec.276","sectionType":"section","heading":"Record keeping for particular systems","content":"### sec.276 Record keeping for particular systems\n\nThe owner of a cathodic protection system must keep records of tests carried out under this division for 10 years if the system—\nis an impressed current cathodic protection system; or\nhas a total anode mass of more than 25kg.\nMaximum penalty—20 penalty units.\nIf asked by the regulator, the owner of the cathodic protection system must give the regulator copies of the records within 14 days after the request.\nMaximum penalty—20 penalty units.\n(sec.276-ssec.1) The owner of a cathodic protection system must keep records of tests carried out under this division for 10 years if the system— is an impressed current cathodic protection system; or has a total anode mass of more than 25kg. Maximum penalty—20 penalty units.\n(sec.276-ssec.2) If asked by the regulator, the owner of the cathodic protection system must give the regulator copies of the records within 14 days after the request. Maximum penalty—20 penalty units.\n- (a) is an impressed current cathodic protection system; or\n- (b) has a total anode mass of more than 25kg.","sortOrder":354},{"sectionNumber":"sec.277","sectionType":"section","heading":"Testing by regulator","content":"### sec.277 Testing by regulator\n\nThe regulator may arrange for the testing the regulator considers necessary to decide whether a cathodic protection system complies with the requirements of this part.\nIf required by the regulator, the owner of the cathodic protection system must provide access to the system, and provide all facilities and equipment for the testing of the system.\nMaximum penalty—40 penalty units.\nIf, on testing, the cathodic protection system is found not to comply with the requirements of this part, the costs incurred by the regulator in conducting the test, including the indirect and overhead costs incurred by the regulator, are a debt payable by the owner of the system to the State.\n(sec.277-ssec.1) The regulator may arrange for the testing the regulator considers necessary to decide whether a cathodic protection system complies with the requirements of this part.\n(sec.277-ssec.2) If required by the regulator, the owner of the cathodic protection system must provide access to the system, and provide all facilities and equipment for the testing of the system. Maximum penalty—40 penalty units.\n(sec.277-ssec.3) If, on testing, the cathodic protection system is found not to comply with the requirements of this part, the costs incurred by the regulator in conducting the test, including the indirect and overhead costs incurred by the regulator, are a debt payable by the owner of the system to the State.","sortOrder":355},{"sectionNumber":"pt.13-div.5","sectionType":"division","heading":"System requirements","content":"## System requirements","sortOrder":356},{"sectionNumber":"sec.278","sectionType":"section","heading":"Electrical limits","content":"### sec.278 Electrical limits\n\nThe owner of a cathodic protection system must ensure the system complies with the requirements of this section for the system.\nMaximum penalty—40 penalty units.\nThe maximum open circuit voltage of a cathodic protection system may be more than 50V only if the owner has the written agreement of the regulator.\nIf an anode for a cathodic protection system is immersed in water or a marine environment, the potential difference between any 2 accessible points spaced 1m apart in the water or marine environment must not be more than 3V when the system is energised.\nIn a surface area of 1,000m 2 measured radially about an electrode or the centre of a group of electrodes discharging current to ground as part of a cathodic protection system on land or in non-saline water, the total current of 1 polarity must not be more than 100A.\nIn an area of surface water of 2,000m 2 bounded by a 100m length of the mean low water level contour and a line displaced 20m in a direction away from land from the contour, the total current of 1 polarity discharged to water or substrata by all electrodes in the area for a cathodic protection system must not be more than 500A.\n(sec.278-ssec.1) The owner of a cathodic protection system must ensure the system complies with the requirements of this section for the system. Maximum penalty—40 penalty units.\n(sec.278-ssec.2) The maximum open circuit voltage of a cathodic protection system may be more than 50V only if the owner has the written agreement of the regulator.\n(sec.278-ssec.3) If an anode for a cathodic protection system is immersed in water or a marine environment, the potential difference between any 2 accessible points spaced 1m apart in the water or marine environment must not be more than 3V when the system is energised.\n(sec.278-ssec.4) In a surface area of 1,000m 2 measured radially about an electrode or the centre of a group of electrodes discharging current to ground as part of a cathodic protection system on land or in non-saline water, the total current of 1 polarity must not be more than 100A.\n(sec.278-ssec.5) In an area of surface water of 2,000m 2 bounded by a 100m length of the mean low water level contour and a line displaced 20m in a direction away from land from the contour, the total current of 1 polarity discharged to water or substrata by all electrodes in the area for a cathodic protection system must not be more than 500A.","sortOrder":357},{"sectionNumber":"sec.279","sectionType":"section","heading":"Maximum potential change","content":"### sec.279 Maximum potential change\n\nThe owner of a cathodic protection system must ensure the system complies with the requirements of this section.\nMaximum penalty—40 penalty units.\nThis section states requirements for a cathodic protection system in relation to a foreign structure for the system.\nThe potential change, foreign structure to ground, must not be more than any of the following—\nat a point 100m radially from an anode, if there is no metallic link between the cathodically protected structure and the foreign structure—150mV in a negative going direction;\nat a point where buried or submerged parts of the foreign structure are in ground or water generally of 1 ohm metre or higher resistivity—10mV in a positive going direction;\nat a point where buried or submerged parts of the foreign structure are in ground or water generally below 1 ohm metre resistivity—0mV;\nfor a foreign structure that is not connected electrically to the cathodically protected structure—\n500mV in a negative going direction; or\nwith the foreign structure owner’s written agreement—1V in a negative going direction.\nHowever, for short-term testing of the cathodic protection system, 5 times the potential change stated in subsection&#160;(3) (a) or (b) and twice the potential change stated in subsection&#160;(3) (d) is permitted.\nThe potential change stated in subsection&#160;(3) (b) or (c) may be changed with the foreign structure owner’s written agreement after an assessment of the effect of any existing cathodic protection or interference mitigation measures on the foreign structure.\n(sec.279-ssec.1) The owner of a cathodic protection system must ensure the system complies with the requirements of this section. Maximum penalty—40 penalty units.\n(sec.279-ssec.2) This section states requirements for a cathodic protection system in relation to a foreign structure for the system.\n(sec.279-ssec.3) The potential change, foreign structure to ground, must not be more than any of the following— at a point 100m radially from an anode, if there is no metallic link between the cathodically protected structure and the foreign structure—150mV in a negative going direction; at a point where buried or submerged parts of the foreign structure are in ground or water generally of 1 ohm metre or higher resistivity—10mV in a positive going direction; at a point where buried or submerged parts of the foreign structure are in ground or water generally below 1 ohm metre resistivity—0mV; for a foreign structure that is not connected electrically to the cathodically protected structure— 500mV in a negative going direction; or with the foreign structure owner’s written agreement—1V in a negative going direction.\n(sec.279-ssec.4) However, for short-term testing of the cathodic protection system, 5 times the potential change stated in subsection&#160;(3) (a) or (b) and twice the potential change stated in subsection&#160;(3) (d) is permitted.\n(sec.279-ssec.5) The potential change stated in subsection&#160;(3) (b) or (c) may be changed with the foreign structure owner’s written agreement after an assessment of the effect of any existing cathodic protection or interference mitigation measures on the foreign structure.\n- (a) at a point 100m radially from an anode, if there is no metallic link between the cathodically protected structure and the foreign structure—150mV in a negative going direction;\n- (b) at a point where buried or submerged parts of the foreign structure are in ground or water generally of 1 ohm metre or higher resistivity—10mV in a positive going direction;\n- (c) at a point where buried or submerged parts of the foreign structure are in ground or water generally below 1 ohm metre resistivity—0mV;\n- (d) for a foreign structure that is not connected electrically to the cathodically protected structure— (i) 500mV in a negative going direction; or (ii) with the foreign structure owner’s written agreement—1V in a negative going direction.\n- (i) 500mV in a negative going direction; or\n- (ii) with the foreign structure owner’s written agreement—1V in a negative going direction.\n- (i) 500mV in a negative going direction; or\n- (ii) with the foreign structure owner’s written agreement—1V in a negative going direction.","sortOrder":358},{"sectionNumber":"sec.280","sectionType":"section","heading":"Identification of anode groundbed","content":"### sec.280 Identification of anode groundbed\n\nIf a registrable system is installed on land or premises not owned by the owner of the system, the owner of the system must identify the location of each anode groundbed of the system by erecting as close as practicable to the anode groundbed a clearly visible, durable sign suitably and indelibly inscribed with the location of the anode groundbed and the name of the owner of the system.\nMaximum penalty—20 penalty units.","sortOrder":359},{"sectionNumber":"pt.13-div.6","sectionType":"division","heading":"Registration of registrable systems","content":"## Registration of registrable systems","sortOrder":360},{"sectionNumber":"sec.281","sectionType":"section","heading":"Register of systems","content":"### sec.281 Register of systems\n\nThe regulator must keep a register of registered systems.\nThe register may be kept in the form, whether or not a documentary form, the regulator considers appropriate.\n(sec.281-ssec.1) The regulator must keep a register of registered systems.\n(sec.281-ssec.2) The register may be kept in the form, whether or not a documentary form, the regulator considers appropriate.","sortOrder":361},{"sectionNumber":"sec.282","sectionType":"section","heading":"Application for registration","content":"### sec.282 Application for registration\n\nAn application for registration of a cathodic protection system that is a registrable system must—\nbe made in the approved form; and\nbe accompanied by the fee stated in schedule&#160;9 for the application; and\nif required by the regulator, be accompanied by—\ndetails of the geographical location of the system; and\na plan including full particulars of the system; and\na certificate from the owner of the system stating the system has been tested as required by this part and complies with the requirements of this part.\nThe certificate mentioned in subsection&#160;(1) (c) (iii) must state—\nthe value of the maximum operating current on which the tests were based; and\nfor a system operating with an anode immersed in water or a marine environment—the operating voltage of the system corresponding to the maximum operating current mentioned in paragraph&#160;(a) ; and\nthat the owner has complied with the requirements under division&#160;4 for testing of the system before registration.\nIf asked in writing by the regulator, the applicant must give the regulator further relevant information the regulator requires to decide the application.\nThe regulator must decide the application within 60 days after receiving the application.\nIf the regulator refuses to register the system, the regulator must give notice of the refusal to the applicant within 30 days after the day the decision is made.\nThe notice must be accompanied by an information notice for the decision to refuse.\nIf the regulator decides to register the system, the regulator—\nmust impose conditions on the registration about—\nthe permitted maximum operating current of the system; and\nfor a system with an anode immersed in water or a marine environment—the permitted maximum operating voltage of the system; and\nmay impose other conditions on the registration.\nIf the regulator decides to impose conditions on the registration under subsection&#160;(7) , other than subsection&#160;(7) (a) , the regulator must give the applicant an information notice for the decision.\n(sec.282-ssec.1) An application for registration of a cathodic protection system that is a registrable system must— be made in the approved form; and be accompanied by the fee stated in schedule&#160;9 for the application; and if required by the regulator, be accompanied by— details of the geographical location of the system; and a plan including full particulars of the system; and a certificate from the owner of the system stating the system has been tested as required by this part and complies with the requirements of this part.\n(sec.282-ssec.2) The certificate mentioned in subsection&#160;(1) (c) (iii) must state— the value of the maximum operating current on which the tests were based; and for a system operating with an anode immersed in water or a marine environment—the operating voltage of the system corresponding to the maximum operating current mentioned in paragraph&#160;(a) ; and that the owner has complied with the requirements under division&#160;4 for testing of the system before registration.\n(sec.282-ssec.3) If asked in writing by the regulator, the applicant must give the regulator further relevant information the regulator requires to decide the application.\n(sec.282-ssec.4) The regulator must decide the application within 60 days after receiving the application.\n(sec.282-ssec.5) If the regulator refuses to register the system, the regulator must give notice of the refusal to the applicant within 30 days after the day the decision is made.\n(sec.282-ssec.6) The notice must be accompanied by an information notice for the decision to refuse.\n(sec.282-ssec.7) If the regulator decides to register the system, the regulator— must impose conditions on the registration about— the permitted maximum operating current of the system; and for a system with an anode immersed in water or a marine environment—the permitted maximum operating voltage of the system; and may impose other conditions on the registration.\n(sec.282-ssec.8) If the regulator decides to impose conditions on the registration under subsection&#160;(7) , other than subsection&#160;(7) (a) , the regulator must give the applicant an information notice for the decision.\n- (a) be made in the approved form; and\n- (b) be accompanied by the fee stated in schedule&#160;9 for the application; and\n- (c) if required by the regulator, be accompanied by— (i) details of the geographical location of the system; and (ii) a plan including full particulars of the system; and (iii) a certificate from the owner of the system stating the system has been tested as required by this part and complies with the requirements of this part.\n- (i) details of the geographical location of the system; and\n- (ii) a plan including full particulars of the system; and\n- (iii) a certificate from the owner of the system stating the system has been tested as required by this part and complies with the requirements of this part.\n- (i) details of the geographical location of the system; and\n- (ii) a plan including full particulars of the system; and\n- (iii) a certificate from the owner of the system stating the system has been tested as required by this part and complies with the requirements of this part.\n- (a) the value of the maximum operating current on which the tests were based; and\n- (b) for a system operating with an anode immersed in water or a marine environment—the operating voltage of the system corresponding to the maximum operating current mentioned in paragraph&#160;(a) ; and\n- (c) that the owner has complied with the requirements under division&#160;4 for testing of the system before registration.\n- (a) must impose conditions on the registration about— (i) the permitted maximum operating current of the system; and (ii) for a system with an anode immersed in water or a marine environment—the permitted maximum operating voltage of the system; and\n- (i) the permitted maximum operating current of the system; and\n- (ii) for a system with an anode immersed in water or a marine environment—the permitted maximum operating voltage of the system; and\n- (b) may impose other conditions on the registration.\n- (i) the permitted maximum operating current of the system; and\n- (ii) for a system with an anode immersed in water or a marine environment—the permitted maximum operating voltage of the system; and","sortOrder":362},{"sectionNumber":"sec.283","sectionType":"section","heading":"Refund of fees","content":"### sec.283 Refund of fees\n\nThis section applies if an application for registration of a cathodic protection system that is a registrable system—\nis refused by the regulator under section&#160;282 (5) ; or\nis withdrawn before the application is decided.\nThe amount stated in schedule&#160;9 as the administration component of the fee paid for the application must be refunded.\n(sec.283-ssec.1) This section applies if an application for registration of a cathodic protection system that is a registrable system— is refused by the regulator under section&#160;282 (5) ; or is withdrawn before the application is decided.\n(sec.283-ssec.2) The amount stated in schedule&#160;9 as the administration component of the fee paid for the application must be refunded.\n- (a) is refused by the regulator under section&#160;282 (5) ; or\n- (b) is withdrawn before the application is decided.","sortOrder":363},{"sectionNumber":"sec.284","sectionType":"section","heading":"Registration of system","content":"### sec.284 Registration of system\n\nThe regulator must register a cathodic protection system that is a registrable system by entering in the register of registered systems—\nthe name and address of the owner of the system notified to the regulator; and\nthe location of the system; and\na description of the cathodically protected structure; and\nthe conditions of registration about—\nthe permitted maximum operating current of the system; and\nfor a system operating with an anode immersed in water or a marine environment—the permitted maximum operating voltage of the system; and\nany other conditions imposed by the regulator on the system’s operation; and\nthe date of registration.\nWithin 30 days after registering the system, the regulator must give the owner of the system written notice of the registration, including—\nthe conditions about the permitted maximum operating current and, if relevant, the permitted maximum operating voltage of the system; and\nother conditions the regulator imposes on the system’s operation; and\nthe date of registration.\n(sec.284-ssec.1) The regulator must register a cathodic protection system that is a registrable system by entering in the register of registered systems— the name and address of the owner of the system notified to the regulator; and the location of the system; and a description of the cathodically protected structure; and the conditions of registration about— the permitted maximum operating current of the system; and for a system operating with an anode immersed in water or a marine environment—the permitted maximum operating voltage of the system; and any other conditions imposed by the regulator on the system’s operation; and the date of registration.\n(sec.284-ssec.2) Within 30 days after registering the system, the regulator must give the owner of the system written notice of the registration, including— the conditions about the permitted maximum operating current and, if relevant, the permitted maximum operating voltage of the system; and other conditions the regulator imposes on the system’s operation; and the date of registration.\n- (a) the name and address of the owner of the system notified to the regulator; and\n- (b) the location of the system; and\n- (c) a description of the cathodically protected structure; and\n- (d) the conditions of registration about— (i) the permitted maximum operating current of the system; and (ii) for a system operating with an anode immersed in water or a marine environment—the permitted maximum operating voltage of the system; and\n- (i) the permitted maximum operating current of the system; and\n- (ii) for a system operating with an anode immersed in water or a marine environment—the permitted maximum operating voltage of the system; and\n- (e) any other conditions imposed by the regulator on the system’s operation; and\n- (f) the date of registration.\n- (i) the permitted maximum operating current of the system; and\n- (ii) for a system operating with an anode immersed in water or a marine environment—the permitted maximum operating voltage of the system; and\n- (a) the conditions about the permitted maximum operating current and, if relevant, the permitted maximum operating voltage of the system; and\n- (b) other conditions the regulator imposes on the system’s operation; and\n- (c) the date of registration.","sortOrder":364},{"sectionNumber":"sec.285","sectionType":"section","heading":"Term of registration","content":"### sec.285 Term of registration\n\nThe registration of a registrable system is for 5 years, unless it is earlier cancelled.","sortOrder":365},{"sectionNumber":"sec.286","sectionType":"section","heading":"Change of name and address","content":"### sec.286 Change of name and address\n\nThe owner of a registered system whose name or address changes must, within 30 days after the change, update their details in the approved form.\nMaximum penalty—20 penalty units.","sortOrder":366},{"sectionNumber":"sec.287","sectionType":"section","heading":"Cancellation of registration","content":"### sec.287 Cancellation of registration\n\nThe regulator may cancel the registration of a registered system if—\nthe regulator is not satisfied the system is installed or operating in accordance with this part; or\nthe regulator has been notified by the owner of the system that the system has been removed or made permanently inoperable.\nOn cancellation of registration of a cathodic protection system, the regulator must—\nenter in the register of registered systems the date of cancellation; and\ngive the owner of the system written notice of the cancellation within 14 days after the cancellation.\nIf the cancellation is under subsection&#160;(1) (a) , the notice must be accompanied by an information notice for the decision to cancel.\n(sec.287-ssec.1) The regulator may cancel the registration of a registered system if— the regulator is not satisfied the system is installed or operating in accordance with this part; or the regulator has been notified by the owner of the system that the system has been removed or made permanently inoperable.\n(sec.287-ssec.2) On cancellation of registration of a cathodic protection system, the regulator must— enter in the register of registered systems the date of cancellation; and give the owner of the system written notice of the cancellation within 14 days after the cancellation.\n(sec.287-ssec.3) If the cancellation is under subsection&#160;(1) (a) , the notice must be accompanied by an information notice for the decision to cancel.\n- (a) the regulator is not satisfied the system is installed or operating in accordance with this part; or\n- (b) the regulator has been notified by the owner of the system that the system has been removed or made permanently inoperable.\n- (a) enter in the register of registered systems the date of cancellation; and\n- (b) give the owner of the system written notice of the cancellation within 14 days after the cancellation.","sortOrder":367},{"sectionNumber":"sec.288","sectionType":"section","heading":"Taking away or making a registered system inoperable","content":"### sec.288 Taking away or making a registered system inoperable\n\nIf a registered system is removed or made permanently inoperable, the owner of the system must give the regulator written notice within 30 days after the removal or the making inoperable.\nMaximum penalty—40 penalty units.","sortOrder":368},{"sectionNumber":"sec.289","sectionType":"section","heading":"Change to registered system to be notified","content":"### sec.289 Change to registered system to be notified\n\nIf a registered system or its method of operation is changed, the owner of the system must—\nimmediately advise the regulator; and\ngive the regulator written notice complying with subsection&#160;(2) within 14 days after the change.\nMaximum penalty—20 penalty units.\nThe notice must be accompanied by a plan clearly showing how the system has changed.\nIf required by the regulator, the owner of the registered system must take all or part of the action an applicant for registration of a registrable system is required to take under this part.\nMaximum penalty—40 penalty units.\n(sec.289-ssec.1) If a registered system or its method of operation is changed, the owner of the system must— immediately advise the regulator; and give the regulator written notice complying with subsection&#160;(2) within 14 days after the change. Maximum penalty—20 penalty units.\n(sec.289-ssec.2) The notice must be accompanied by a plan clearly showing how the system has changed.\n(sec.289-ssec.3) If required by the regulator, the owner of the registered system must take all or part of the action an applicant for registration of a registrable system is required to take under this part. Maximum penalty—40 penalty units.\n- (a) immediately advise the regulator; and\n- (b) give the regulator written notice complying with subsection&#160;(2) within 14 days after the change.","sortOrder":369},{"sectionNumber":"pt.14","sectionType":"part","heading":"Incident notification and reporting","content":"# Incident notification and reporting","sortOrder":370},{"sectionNumber":"sec.290","sectionType":"section","heading":"Definitions for part","content":"### sec.290 Definitions for part\n\nIn this part—\ndistribution entity , for a serious electrical incident or dangerous electrical event, see section&#160;291 .\nincident record see section&#160;294 (2) (b) .","sortOrder":371},{"sectionNumber":"sec.291","sectionType":"section","heading":"Meaning of distribution entity for incident or event","content":"### sec.291 Meaning of distribution entity for incident or event\n\nThe distribution entity for a serious electrical incident is—\nif the electrical equipment the subject of the incident is part of the works of a distribution entity—the distribution entity; or\notherwise—the distribution entity that supplies electricity to the electrical equipment the subject of the incident.\nThe distribution entity for a dangerous electrical event is the distribution entity that supplies electricity to, or has as part of its works, the electrical equipment that is—\nthe subject of the event; or\nthe subject of electrical work that is the subject of the event.\n(sec.291-ssec.1) The distribution entity for a serious electrical incident is— if the electrical equipment the subject of the incident is part of the works of a distribution entity—the distribution entity; or otherwise—the distribution entity that supplies electricity to the electrical equipment the subject of the incident.\n(sec.291-ssec.2) The distribution entity for a dangerous electrical event is the distribution entity that supplies electricity to, or has as part of its works, the electrical equipment that is— the subject of the event; or the subject of electrical work that is the subject of the event.\n- (a) if the electrical equipment the subject of the incident is part of the works of a distribution entity—the distribution entity; or\n- (b) otherwise—the distribution entity that supplies electricity to the electrical equipment the subject of the incident.\n- (a) the subject of the event; or\n- (b) the subject of electrical work that is the subject of the event.","sortOrder":372},{"sectionNumber":"sec.292","sectionType":"section","heading":"Serious electrical incident or dangerous electrical event—duties of person conducting business or undertaking","content":"### sec.292 Serious electrical incident or dangerous electrical event—duties of person conducting business or undertaking\n\nA person who conducts a business or undertaking must ensure the regulator is notified immediately after becoming aware that a serious electrical incident or dangerous electrical event arising out of the conduct of the business or undertaking has occurred.\nMaximum penalty—100 penalty units.\nThe notice must be given as required under this section and by the fastest possible means.\nThe notice must be given—\nby telephone; or\nin writing.\nThe written notice can be given by facsimile, email or other electronic means.\nA person giving notice by telephone must—\ngive the details of the incident or event requested by the regulator; and\nif required by the regulator, give a written notice of the incident or event within 48 hours after the requirement is made.\nA written notice must be in the approved form, or contain the details required by the regulator.\nIf the regulator receives a notice by telephone and a written notice is not required, the regulator must give the person conducting the business or undertaking—\ndetails of the information received; or\nan acknowledgement of receiving the notice.\nA person conducting a business or undertaking must keep a record of each serious electrical incident or dangerous electrical event for at least 5 years after the day that notice of the incident or event is given to the regulator under this section.\nMaximum penalty—50 penalty units.\n(sec.292-ssec.1) A person who conducts a business or undertaking must ensure the regulator is notified immediately after becoming aware that a serious electrical incident or dangerous electrical event arising out of the conduct of the business or undertaking has occurred. Maximum penalty—100 penalty units.\n(sec.292-ssec.2) The notice must be given as required under this section and by the fastest possible means.\n(sec.292-ssec.3) The notice must be given— by telephone; or in writing. The written notice can be given by facsimile, email or other electronic means.\n(sec.292-ssec.4) A person giving notice by telephone must— give the details of the incident or event requested by the regulator; and if required by the regulator, give a written notice of the incident or event within 48 hours after the requirement is made.\n(sec.292-ssec.5) A written notice must be in the approved form, or contain the details required by the regulator.\n(sec.292-ssec.6) If the regulator receives a notice by telephone and a written notice is not required, the regulator must give the person conducting the business or undertaking— details of the information received; or an acknowledgement of receiving the notice.\n(sec.292-ssec.7) A person conducting a business or undertaking must keep a record of each serious electrical incident or dangerous electrical event for at least 5 years after the day that notice of the incident or event is given to the regulator under this section. Maximum penalty—50 penalty units.\n- (a) by telephone; or\n- (b) in writing.\n- (a) give the details of the incident or event requested by the regulator; and\n- (b) if required by the regulator, give a written notice of the incident or event within 48 hours after the requirement is made.\n- (a) details of the information received; or\n- (b) an acknowledgement of receiving the notice.","sortOrder":373},{"sectionNumber":"sec.293","sectionType":"section","heading":"Duty of distribution entity to notify of serious electrical incident or dangerous electrical event","content":"### sec.293 Duty of distribution entity to notify of serious electrical incident or dangerous electrical event\n\nThis section applies if—\na distribution entity is advised about the happening of a serious electrical incident or dangerous electrical event; and\nthe distribution entity is the distribution entity for the incident or event.\nThe distribution entity must—\ngive the regulator written notice in the approved form of the incident or event; and\nensure the written notice is received by the regulator within 24 hours after the distribution entity first becomes aware of the happening of the incident or event.\nMaximum penalty—40 penalty units.\nIf the incident or event is a serious electrical incident in which a person has been killed, the distribution entity must also advise the regulator of the incident, immediately after the distribution entity becomes aware of the happening of the incident, by telephone or by email, facsimile or other electronic means.\nMaximum penalty—40 penalty units.\nThe distribution entity is not required to comply with subsection&#160;(2) or (3) if the distribution entity knows the incident or event has already been reported to the regulator.\n(sec.293-ssec.1) This section applies if— a distribution entity is advised about the happening of a serious electrical incident or dangerous electrical event; and the distribution entity is the distribution entity for the incident or event.\n(sec.293-ssec.2) The distribution entity must— give the regulator written notice in the approved form of the incident or event; and ensure the written notice is received by the regulator within 24 hours after the distribution entity first becomes aware of the happening of the incident or event. Maximum penalty—40 penalty units.\n(sec.293-ssec.3) If the incident or event is a serious electrical incident in which a person has been killed, the distribution entity must also advise the regulator of the incident, immediately after the distribution entity becomes aware of the happening of the incident, by telephone or by email, facsimile or other electronic means. Maximum penalty—40 penalty units.\n(sec.293-ssec.4) The distribution entity is not required to comply with subsection&#160;(2) or (3) if the distribution entity knows the incident or event has already been reported to the regulator.\n- (a) a distribution entity is advised about the happening of a serious electrical incident or dangerous electrical event; and\n- (b) the distribution entity is the distribution entity for the incident or event.\n- (a) give the regulator written notice in the approved form of the incident or event; and\n- (b) ensure the written notice is received by the regulator within 24 hours after the distribution entity first becomes aware of the happening of the incident or event.","sortOrder":374},{"sectionNumber":"sec.294","sectionType":"section","heading":"Action required by distribution entity on report of electric shock","content":"### sec.294 Action required by distribution entity on report of electric shock\n\nThis section applies if a distribution entity is advised by a consumer to whom the distribution entity supplies electricity that a person has received an electric shock.\nThe distribution entity must—\ntake the action necessary to be taken in the interests of the electrical safety of persons; and\nmake a written record of the incident (the incident record ), in a format approved by the regulator, within 3 days after the distribution entity is advised of the person having received the electric shock; and\nkeep the incident record for 5 years.\nMaximum penalty—40 penalty units.\n(sec.294-ssec.1) This section applies if a distribution entity is advised by a consumer to whom the distribution entity supplies electricity that a person has received an electric shock.\n(sec.294-ssec.2) The distribution entity must— take the action necessary to be taken in the interests of the electrical safety of persons; and make a written record of the incident (the incident record ), in a format approved by the regulator, within 3 days after the distribution entity is advised of the person having received the electric shock; and keep the incident record for 5 years. Maximum penalty—40 penalty units.\n- (a) take the action necessary to be taken in the interests of the electrical safety of persons; and\n- (b) make a written record of the incident (the incident record ), in a format approved by the regulator, within 3 days after the distribution entity is advised of the person having received the electric shock; and\n- (c) keep the incident record for 5 years.","sortOrder":375},{"sectionNumber":"sec.295","sectionType":"section","heading":"Report of incident records","content":"### sec.295 Report of incident records\n\nA distribution entity must, every 3 months, report to the regulator, in a format approved by the regulator, about the incident records made by the distribution entity in the 3 months.\nMaximum penalty—20 penalty units.","sortOrder":376},{"sectionNumber":"sec.296","sectionType":"section","heading":"Duty to preserve incident or event sites","content":"### sec.296 Duty to preserve incident or event sites\n\nThis section applies if a serious electrical incident or dangerous electrical event happens at a place.\nThe person with management or control of the place must ensure, so far as is reasonably practicable, that the site where the incident or event occurred is not disturbed until an inspector arrives at the site or any earlier time that an inspector directs.\nMaximum penalty—100 penalty units.\nA person must not move or otherwise interfere with any electrical equipment, or part of any electrical equipment, involved in the happening of the incident or event.\nMaximum penalty— 40 penalty units.\nSubsections&#160;(2) and (3) do not prevent any action—\nto assist an injured person; or\nto remove a deceased person; or\nthat is essential to make the site safe or to minimise the risk of a further serious electrical incident or dangerous electrical event; or\nthat is associated with a police investigation; or\nof a person acting under the authority of the distribution entity for the incident or event; or\nfor which an inspector or the regulator has given permission.\nIn this section—\nsite , where a serious electrical incident or dangerous electrical event occurs, includes any plant, substance, structure and thing associated with the incident or event.\n(sec.296-ssec.1) This section applies if a serious electrical incident or dangerous electrical event happens at a place.\n(sec.296-ssec.2) The person with management or control of the place must ensure, so far as is reasonably practicable, that the site where the incident or event occurred is not disturbed until an inspector arrives at the site or any earlier time that an inspector directs. Maximum penalty—100 penalty units.\n(sec.296-ssec.3) A person must not move or otherwise interfere with any electrical equipment, or part of any electrical equipment, involved in the happening of the incident or event. Maximum penalty— 40 penalty units.\n(sec.296-ssec.4) Subsections&#160;(2) and (3) do not prevent any action— to assist an injured person; or to remove a deceased person; or that is essential to make the site safe or to minimise the risk of a further serious electrical incident or dangerous electrical event; or that is associated with a police investigation; or of a person acting under the authority of the distribution entity for the incident or event; or for which an inspector or the regulator has given permission.\n(sec.296-ssec.5) In this section— site , where a serious electrical incident or dangerous electrical event occurs, includes any plant, substance, structure and thing associated with the incident or event.\n- (a) to assist an injured person; or\n- (b) to remove a deceased person; or\n- (c) that is essential to make the site safe or to minimise the risk of a further serious electrical incident or dangerous electrical event; or\n- (d) that is associated with a police investigation; or\n- (e) of a person acting under the authority of the distribution entity for the incident or event; or\n- (f) for which an inspector or the regulator has given permission.","sortOrder":377},{"sectionNumber":"sec.297","sectionType":"section","heading":"Storage of electrical equipment after serious electrical incident","content":"### sec.297 Storage of electrical equipment after serious electrical incident\n\nThis section applies if—\na serious electrical incident happens at a place; and\nelectrical equipment that is part of the works of a distribution entity is involved in the serious electrical incident.\nThe distribution entity must ensure that, if the equipment is removed from the place, the equipment is stored securely until—\nan inspector takes possession of the equipment; or\nan inspector gives written permission to release the equipment from storage.\nMaximum penalty—40 penalty units.\n(sec.297-ssec.1) This section applies if— a serious electrical incident happens at a place; and electrical equipment that is part of the works of a distribution entity is involved in the serious electrical incident.\n(sec.297-ssec.2) The distribution entity must ensure that, if the equipment is removed from the place, the equipment is stored securely until— an inspector takes possession of the equipment; or an inspector gives written permission to release the equipment from storage. Maximum penalty—40 penalty units.\n- (a) a serious electrical incident happens at a place; and\n- (b) electrical equipment that is part of the works of a distribution entity is involved in the serious electrical incident.\n- (a) an inspector takes possession of the equipment; or\n- (b) an inspector gives written permission to release the equipment from storage.","sortOrder":378},{"sectionNumber":"sec.298","sectionType":"section","heading":"Requirement for distribution entity to take action in interests of electrical safety","content":"### sec.298 Requirement for distribution entity to take action in interests of electrical safety\n\nThis section applies if—\na person has a reasonable concern about the electrical safety of electrical equipment to which a distribution entity supplies electricity; and\nthe person advises the distribution entity of the concern.\nThe distribution entity must take the action necessary to be taken in the interests of the electrical safety of persons.\nMaximum penalty—40 penalty units.\n(sec.298-ssec.1) This section applies if— a person has a reasonable concern about the electrical safety of electrical equipment to which a distribution entity supplies electricity; and the person advises the distribution entity of the concern.\n(sec.298-ssec.2) The distribution entity must take the action necessary to be taken in the interests of the electrical safety of persons. Maximum penalty—40 penalty units.\n- (a) a person has a reasonable concern about the electrical safety of electrical equipment to which a distribution entity supplies electricity; and\n- (b) the person advises the distribution entity of the concern.","sortOrder":379},{"sectionNumber":"pt.15","sectionType":"part","heading":"Miscellaneous provisions","content":"# Miscellaneous provisions","sortOrder":380},{"sectionNumber":"pt.15-div.1","sectionType":"division","heading":"Electrical safety contributions","content":"## Electrical safety contributions","sortOrder":381},{"sectionNumber":"sec.299","sectionType":"section","heading":"Purpose of division— Act , s&#160;203","content":"### sec.299 Purpose of division— Act , s&#160;203\n\nThe purpose of this division is to prescribe, for section&#160;203 (1) of the Act , things that are necessary or convenient for establishing and operating arrangements for the payment of electrical safety contributions.","sortOrder":382},{"sectionNumber":"sec.300","sectionType":"section","heading":"Fixing electrical safety contribution for each distribution entity for financial year","content":"### sec.300 Fixing electrical safety contribution for each distribution entity for financial year\n\nThe method for working out the amount of the electrical safety contribution payable by each distribution entity for a financial year is as follows—\nthe regulator decides the premises figure for each distribution entity\nthe regulator works out the total premises figure\nthe regulator works out the unit contribution amount for the financial year\nthe regulator works out the amount of the electrical safety contribution payable by each distribution entity for the financial year by multiplying the premises figure for the distribution entity by the unit contribution amount for the financial year.\nIn this section—\npremises figure , for a distribution entity for a financial year, means a figure that is a fair estimate of the average number of retail premises for the distribution entity for the previous financial year.\ntotal contribution amount , for a financial year, means the amount notified, for the financial year, by gazette notice.\ntotal premises figure , for a financial year, means the total of the premises figures for all distribution entities for the financial year.\nunit contribution amount , for a financial year, means the total contribution amount for the financial year divided by the total premises figure.\n(sec.300-ssec.1) The method for working out the amount of the electrical safety contribution payable by each distribution entity for a financial year is as follows— the regulator decides the premises figure for each distribution entity the regulator works out the total premises figure the regulator works out the unit contribution amount for the financial year the regulator works out the amount of the electrical safety contribution payable by each distribution entity for the financial year by multiplying the premises figure for the distribution entity by the unit contribution amount for the financial year.\n(sec.300-ssec.2) In this section— premises figure , for a distribution entity for a financial year, means a figure that is a fair estimate of the average number of retail premises for the distribution entity for the previous financial year. total contribution amount , for a financial year, means the amount notified, for the financial year, by gazette notice. total premises figure , for a financial year, means the total of the premises figures for all distribution entities for the financial year. unit contribution amount , for a financial year, means the total contribution amount for the financial year divided by the total premises figure.\n- • the regulator decides the premises figure for each distribution entity\n- • the regulator works out the total premises figure\n- • the regulator works out the unit contribution amount for the financial year\n- • the regulator works out the amount of the electrical safety contribution payable by each distribution entity for the financial year by multiplying the premises figure for the distribution entity by the unit contribution amount for the financial year.","sortOrder":383},{"sectionNumber":"sec.301","sectionType":"section","heading":"Payment of electrical safety contribution by instalments","content":"### sec.301 Payment of electrical safety contribution by instalments\n\nThe electrical safety contribution for a distribution entity for a financial year may be paid in equal instalments.","sortOrder":384},{"sectionNumber":"pt.15-div.2","sectionType":"division","heading":"Prescribed matters","content":"## Prescribed matters","sortOrder":385},{"sectionNumber":"sec.302","sectionType":"section","heading":"Prescribed electrical equipment— Act , s&#160;14A","content":"### sec.302 Prescribed electrical equipment— Act , s&#160;14A\n\nFor section&#160;14A (c) of the Act , water equipment is prescribed.\nIn this section—\nwater equipment means any apparatus, appliance, cable, conductor, fitting, insulator, material, meter or wire that—\nis operated or used for controlling, generating, supplying, transforming or transmitting electricity at extra low voltage; and\ncan only be operated or used when connected to an external source of electricity; and\nis designed for use in the interior of the container of a swimming pool, paddling pool, spa pool or bathtub.\n(sec.302-ssec.1) For section&#160;14A (c) of the Act , water equipment is prescribed.\n(sec.302-ssec.2) In this section— water equipment means any apparatus, appliance, cable, conductor, fitting, insulator, material, meter or wire that— is operated or used for controlling, generating, supplying, transforming or transmitting electricity at extra low voltage; and can only be operated or used when connected to an external source of electricity; and is designed for use in the interior of the container of a swimming pool, paddling pool, spa pool or bathtub.\n- (a) is operated or used for controlling, generating, supplying, transforming or transmitting electricity at extra low voltage; and\n- (b) can only be operated or used when connected to an external source of electricity; and\n- (c) is designed for use in the interior of the container of a swimming pool, paddling pool, spa pool or bathtub.","sortOrder":386},{"sectionNumber":"sec.303","sectionType":"section","heading":"Prescribed person for delegation by regulator— Act , s&#160;122B","content":"### sec.303 Prescribed person for delegation by regulator— Act , s&#160;122B\n\nFor section&#160;122B (1) of the Act , the WHS prosecutor is prescribed.","sortOrder":387},{"sectionNumber":"sec.304","sectionType":"section","heading":"Inspectors’ identity cards— Act , s&#160;123A","content":"### sec.304 Inspectors’ identity cards— Act , s&#160;123A\n\nFor section&#160;123A (1) of the Act , the following matters are prescribed—\na recent photograph of the inspector;\na copy of the inspector’s signature;\nthe date, if any, on which the inspector’s appointment ends;\nany conditions to which the inspector’s appointment is subject, including, for example, the kinds of workplaces in relation to which the inspector may exercise the inspector’s compliance powers.\n- (a) a recent photograph of the inspector;\n- (b) a copy of the inspector’s signature;\n- (c) the date, if any, on which the inspector’s appointment ends;\n- (d) any conditions to which the inspector’s appointment is subject, including, for example, the kinds of workplaces in relation to which the inspector may exercise the inspector’s compliance powers.","sortOrder":388},{"sectionNumber":"sec.305","sectionType":"section","heading":"Provision of information by retailer— Act , s&#160;153","content":"### sec.305 Provision of information by retailer— Act , s&#160;153\n\nFor section&#160;153 (1) of the Act , the following information is prescribed—\na customer’s full name;\nthe address of the premises at which a customer receives customer retail services;\na customer’s postal address and telephone number;\na contact person for a customer;\nthe date a retail entity agreed to provide customer retail services to the premises of the customer;\nthe location of a meter at the customer’s premises;\nthe number of meters at the customer’s premises;\nthe tariff applying to a meter at the customer’s premises;\nthe identifying number of a pole or pillar used in supplying electricity to the customer’s premises;\ninformation relevant to locating the customer’s premises or gaining access to the premises;\nfor premises that are a domestic residence—whether an approved safety switch is installed for the domestic residence.\n- (a) a customer’s full name;\n- (b) the address of the premises at which a customer receives customer retail services;\n- (c) a customer’s postal address and telephone number;\n- (d) a contact person for a customer;\n- (e) the date a retail entity agreed to provide customer retail services to the premises of the customer;\n- (f) the location of a meter at the customer’s premises;\n- (g) the number of meters at the customer’s premises;\n- (h) the tariff applying to a meter at the customer’s premises;\n- (i) the identifying number of a pole or pillar used in supplying electricity to the customer’s premises;\n- (j) information relevant to locating the customer’s premises or gaining access to the premises;\n- (k) for premises that are a domestic residence—whether an approved safety switch is installed for the domestic residence.","sortOrder":389},{"sectionNumber":"sec.306","sectionType":"section","heading":"Prescribed Act— Act , s&#160;193","content":"### sec.306 Prescribed Act— Act , s&#160;193\n\nEach Act stated in schedule&#160;8 is prescribed for section&#160;193 (3) (c) (ii) of the Act .","sortOrder":390},{"sectionNumber":"pt.15-div.3","sectionType":"division","heading":"Other matters","content":"## Other matters","sortOrder":391},{"sectionNumber":"sec.307","sectionType":"section","heading":"Duties of person conducting a business or undertaking about supervising training person","content":"### sec.307 Duties of person conducting a business or undertaking about supervising training person\n\nA person conducting a business or undertaking that employs a training person who has not finished 6 months of the person’s apprenticeship or training program must ensure the training person does not work—\nin the immediate vicinity of a live high voltage exposed part; or\nwhere there is a risk the training person could come into contact with a live low voltage exposed part.\nMaximum penalty—40 penalty units.\nHowever, subsection&#160;(1) does not apply to a training person performing duties as a safety observer if—\nthe training person is a safety observer and has been capable of being a safety observer for at least 1 year immediately before the start of the training person’s apprenticeship or training program; and\nthe person conducting the business or undertaking keeps a written record of the assessment mentioned in schedule&#160;10 , definition safety observer , paragraph&#160;(a) (ii) for the training person.\nA person conducting a business or undertaking must ensure that a training person who performs electrical work is supervised at all times by a licensed electrical worker licensed to perform the work.\nMaximum penalty—40 penalty units.\nThe level of supervision required under subsection&#160;(3) must be appropriate, having regard to—\nthe type of electrical work performed; and\nthe adequacy of the training person’s training; and\nthe competency of the training person.\n(sec.307-ssec.1) A person conducting a business or undertaking that employs a training person who has not finished 6 months of the person’s apprenticeship or training program must ensure the training person does not work— in the immediate vicinity of a live high voltage exposed part; or where there is a risk the training person could come into contact with a live low voltage exposed part. Maximum penalty—40 penalty units.\n(sec.307-ssec.2) However, subsection&#160;(1) does not apply to a training person performing duties as a safety observer if— the training person is a safety observer and has been capable of being a safety observer for at least 1 year immediately before the start of the training person’s apprenticeship or training program; and the person conducting the business or undertaking keeps a written record of the assessment mentioned in schedule&#160;10 , definition safety observer , paragraph&#160;(a) (ii) for the training person.\n(sec.307-ssec.3) A person conducting a business or undertaking must ensure that a training person who performs electrical work is supervised at all times by a licensed electrical worker licensed to perform the work. Maximum penalty—40 penalty units.\n(sec.307-ssec.4) The level of supervision required under subsection&#160;(3) must be appropriate, having regard to— the type of electrical work performed; and the adequacy of the training person’s training; and the competency of the training person.\n- (a) in the immediate vicinity of a live high voltage exposed part; or\n- (b) where there is a risk the training person could come into contact with a live low voltage exposed part.\n- (a) the training person is a safety observer and has been capable of being a safety observer for at least 1 year immediately before the start of the training person’s apprenticeship or training program; and\n- (b) the person conducting the business or undertaking keeps a written record of the assessment mentioned in schedule&#160;10 , definition safety observer , paragraph&#160;(a) (ii) for the training person.\n- (a) the type of electrical work performed; and\n- (b) the adequacy of the training person’s training; and\n- (c) the competency of the training person.","sortOrder":392},{"sectionNumber":"sec.308","sectionType":"section","heading":"Inspection of entries in registers","content":"### sec.308 Inspection of entries in registers\n\nThe regulator must keep each register under this regulation open for inspection, on payment of any fixed fee applying to the inspection, by members of the public during office hours on business days.\nA person may obtain a copy of an entry in a register on payment of any fixed fee applying to obtaining the copy.\n(sec.308-ssec.1) The regulator must keep each register under this regulation open for inspection, on payment of any fixed fee applying to the inspection, by members of the public during office hours on business days.\n(sec.308-ssec.2) A person may obtain a copy of an entry in a register on payment of any fixed fee applying to obtaining the copy.","sortOrder":393},{"sectionNumber":"sec.309","sectionType":"section","heading":"Climbing poles of electricity entity prohibited","content":"### sec.309 Climbing poles of electricity entity prohibited\n\nA person must not climb a pole, standard or other structure that is part of the works of an electricity entity, or a ladder attached to a pole, standard or other structure that is part of the works of an electricity entity, if the electricity entity has not authorised the person to climb the pole, standard, other structure or ladder.\nMaximum penalty—40 penalty units.\nSubsection&#160;(1) does not apply to—\nan inspector; or\na licensed electrical contractor or licensed electrical worker who, under section&#160;224 , de-energises and re-energises a consumer’s electrical installation by—\nremoving and replacing a fuse wedge from a service fuse; or\nswitching off and on a circuit breaker installed as a service line disconnector.\n(sec.309-ssec.1) A person must not climb a pole, standard or other structure that is part of the works of an electricity entity, or a ladder attached to a pole, standard or other structure that is part of the works of an electricity entity, if the electricity entity has not authorised the person to climb the pole, standard, other structure or ladder. Maximum penalty—40 penalty units.\n(sec.309-ssec.2) Subsection&#160;(1) does not apply to— an inspector; or a licensed electrical contractor or licensed electrical worker who, under section&#160;224 , de-energises and re-energises a consumer’s electrical installation by— removing and replacing a fuse wedge from a service fuse; or switching off and on a circuit breaker installed as a service line disconnector.\n- (a) an inspector; or\n- (b) a licensed electrical contractor or licensed electrical worker who, under section&#160;224 , de-energises and re-energises a consumer’s electrical installation by— (i) removing and replacing a fuse wedge from a service fuse; or (ii) switching off and on a circuit breaker installed as a service line disconnector.\n- (i) removing and replacing a fuse wedge from a service fuse; or\n- (ii) switching off and on a circuit breaker installed as a service line disconnector.\n- (i) removing and replacing a fuse wedge from a service fuse; or\n- (ii) switching off and on a circuit breaker installed as a service line disconnector.","sortOrder":394},{"sectionNumber":"sec.310","sectionType":"section","heading":"Electrical distribution entity may isolate powerlines in emergency","content":"### sec.310 Electrical distribution entity may isolate powerlines in emergency\n\nAn electrical distribution entity may isolate powerlines from sources of electricity—\nin an emergency; or\nif there is a flood or fire\nto prevent an emergency from happening.\nif there are extreme conditions with the potential to create an emergency, including, for example, sparking lines in high wind in high fire danger conditions\nIn this section—\nemergency means an emergency in relation to a person or the electrical distribution entity’s property or other property.\n(sec.310-ssec.1) An electrical distribution entity may isolate powerlines from sources of electricity— in an emergency; or if there is a flood or fire to prevent an emergency from happening. if there are extreme conditions with the potential to create an emergency, including, for example, sparking lines in high wind in high fire danger conditions\n(sec.310-ssec.2) In this section— emergency means an emergency in relation to a person or the electrical distribution entity’s property or other property.\n- (a) in an emergency; or Example for paragraph&#160;(a) — if there is a flood or fire\n- (b) to prevent an emergency from happening. Example for paragraph&#160;(b) — if there are extreme conditions with the potential to create an emergency, including, for example, sparking lines in high wind in high fire danger conditions","sortOrder":395},{"sectionNumber":"sec.311","sectionType":"section","heading":"Provision of information by Residential Tenancies Authority","content":"### sec.311 Provision of information by Residential Tenancies Authority\n\nThe Residential Tenancies Authority may, if asked, give the regulator information that—\nthe authority has obtained in the performance of its functions; and\nis relevant to a person’s compliance with section&#160;29 .\nthe address of the domestic residence\nIn this section—\nResidential Tenancies Authority means the Residential Tenancies Authority established under the Residential Tenancies and Rooming Accommodation Act 2008 , section&#160;465 .\n(sec.311-ssec.1) The Residential Tenancies Authority may, if asked, give the regulator information that— the authority has obtained in the performance of its functions; and is relevant to a person’s compliance with section&#160;29 . the address of the domestic residence\n(sec.311-ssec.2) In this section— Residential Tenancies Authority means the Residential Tenancies Authority established under the Residential Tenancies and Rooming Accommodation Act 2008 , section&#160;465 .\n- (a) the authority has obtained in the performance of its functions; and\n- (b) is relevant to a person’s compliance with section&#160;29 .","sortOrder":396},{"sectionNumber":"sec.312","sectionType":"section","heading":"Fees","content":"### sec.312 Fees\n\nThe fees payable under the Act are stated in schedule&#160;9 .","sortOrder":397},{"sectionNumber":"pt.16","sectionType":"part","heading":"Transitional provisions","content":"# Transitional provisions","sortOrder":398},{"sectionNumber":"pt.16-div.1","sectionType":"division","heading":"Preliminary","content":"## Preliminary","sortOrder":399},{"sectionNumber":"sec.313","sectionType":"section","heading":"Definitions for part","content":"### sec.313 Definitions for part\n\nIn this part—\nexpired regulation means the expired Electrical Safety Regulation 2013 .\nformer , in relation to a provision of the expired regulation, means the provision of the expired regulation as in force immediately before the commencement.\nnew , in relation to a provision of this regulation, means the provision as in force from the commencement.","sortOrder":400},{"sectionNumber":"pt.16-div.2","sectionType":"division","heading":"General provisions","content":"## General provisions","sortOrder":401},{"sectionNumber":"sec.314","sectionType":"section","heading":"Applications made but not decided before commencement","content":"### sec.314 Applications made but not decided before commencement\n\nThis section applies to an application made, but not decided, before the commencement under a former section mentioned in column 1 of the following table.\nFrom the commencement, the application is taken to have been made under the new section mentioned in column 2 of the table opposite the former section.\nAnything done in relation to the application under the expired regulation is taken to have been done in relation to the application under this regulation.\nColumn 1\nColumn 2\nFormer section\nNew section\n1\nsection&#160;48(3) (Eligibility requirements for electrical contractor licence)\nsection&#160;173\n2\nsection&#160;58(1) (Replacement of electrical licence)\nsection&#160;179(1)\n3\nsection&#160;154 (Application for certificate of conformity)\nsection&#160;83\n4\nsection&#160;157 (Modification of certificate of conformity—change of name or model)\nsection&#160;86\n5\nsection&#160;158 (Modification of certificate of conformity—other than a change of name or model)\nsection&#160;87\n6\nsection&#160;159 (Renewal of certificate of conformity)\nsection&#160;88\n7\nsection&#160;160 (Transfer of certificate)\nsection&#160;89\n8\nsection&#160;167 (Application for regulator’s declaration of scheme)\nsection&#160;96\n9\nsection&#160;235(2) (Appointment)\nsection&#160;241\n10\nsection&#160;255 (Application for registration of registrable system)\nsection&#160;282\n(sec.314-ssec.1) This section applies to an application made, but not decided, before the commencement under a former section mentioned in column 1 of the following table.\n(sec.314-ssec.2) From the commencement, the application is taken to have been made under the new section mentioned in column 2 of the table opposite the former section.\n(sec.314-ssec.3) Anything done in relation to the application under the expired regulation is taken to have been done in relation to the application under this regulation. Column 1 Column 2 Former section New section 1 section&#160;48(3) (Eligibility requirements for electrical contractor licence) section&#160;173 2 section&#160;58(1) (Replacement of electrical licence) section&#160;179(1) 3 section&#160;154 (Application for certificate of conformity) section&#160;83 4 section&#160;157 (Modification of certificate of conformity—change of name or model) section&#160;86 5 section&#160;158 (Modification of certificate of conformity—other than a change of name or model) section&#160;87 6 section&#160;159 (Renewal of certificate of conformity) section&#160;88 7 section&#160;160 (Transfer of certificate) section&#160;89 8 section&#160;167 (Application for regulator’s declaration of scheme) section&#160;96 9 section&#160;235(2) (Appointment) section&#160;241 10 section&#160;255 (Application for registration of registrable system) section&#160;282","sortOrder":402},{"sectionNumber":"sec.315","sectionType":"section","heading":"Notices or advice required to be given to regulator","content":"### sec.315 Notices or advice required to be given to regulator\n\nThis section applies if—\nbefore the commencement, a person was required to give the regulator a notice or advice under a former section mentioned in column 1 of the following table; and\nimmediately before the commencement—\nthe person had not given the regulator the notice or advice; and\nthe period for giving the regulator the notice or advice (the compliance period ) had not ended.\nThe notice or advice must be given—\nunder the new section mentioned in column 2 of the table opposite the former section; and\nbefore the compliance period ends.\nColumn 1\nColumn 2\nFormer section\nNew section\n1\nsection&#160;49 (Removal of endorsement from electrical contractor licence)\nsection&#160;174\n2\nsection&#160;52 (Change of name of corporation or partnership)\nsection&#160;176\n3\nsection&#160;53 (Change in membership of partnership)\nsection&#160;177\n4\nsection&#160;83 (Notice to regulator about approved safety switch and other matters)\nsection&#160;27\n5\nsection&#160;259 (Change of name and address)\nsection&#160;286\n6\nsection&#160;261 (Taking away or making a registered system inoperable)\nsection&#160;288\n7\nsection&#160;262 (Change to registered system to be notified)\nsection&#160;289\n8\nsection&#160;265 (Duty of person conducting a business or undertaking to notify of serious electrical incident or dangerous electrical event)\nsection&#160;292\n9\nsection&#160;266 (Duty of distribution entity to notify of serious electrical incident or dangerous electrical event)\nsection&#160;293\n(sec.315-ssec.1) This section applies if— before the commencement, a person was required to give the regulator a notice or advice under a former section mentioned in column 1 of the following table; and immediately before the commencement— the person had not given the regulator the notice or advice; and the period for giving the regulator the notice or advice (the compliance period ) had not ended.\n(sec.315-ssec.2) The notice or advice must be given— under the new section mentioned in column 2 of the table opposite the former section; and before the compliance period ends. Column 1 Column 2 Former section New section 1 section&#160;49 (Removal of endorsement from electrical contractor licence) section&#160;174 2 section&#160;52 (Change of name of corporation or partnership) section&#160;176 3 section&#160;53 (Change in membership of partnership) section&#160;177 4 section&#160;83 (Notice to regulator about approved safety switch and other matters) section&#160;27 5 section&#160;259 (Change of name and address) section&#160;286 6 section&#160;261 (Taking away or making a registered system inoperable) section&#160;288 7 section&#160;262 (Change to registered system to be notified) section&#160;289 8 section&#160;265 (Duty of person conducting a business or undertaking to notify of serious electrical incident or dangerous electrical event) section&#160;292 9 section&#160;266 (Duty of distribution entity to notify of serious electrical incident or dangerous electrical event) section&#160;293\n- (a) before the commencement, a person was required to give the regulator a notice or advice under a former section mentioned in column 1 of the following table; and\n- (b) immediately before the commencement— (i) the person had not given the regulator the notice or advice; and (ii) the period for giving the regulator the notice or advice (the compliance period ) had not ended.\n- (i) the person had not given the regulator the notice or advice; and\n- (ii) the period for giving the regulator the notice or advice (the compliance period ) had not ended.\n- (i) the person had not given the regulator the notice or advice; and\n- (ii) the period for giving the regulator the notice or advice (the compliance period ) had not ended.\n- (a) under the new section mentioned in column 2 of the table opposite the former section; and\n- (b) before the compliance period ends.","sortOrder":403},{"sectionNumber":"sec.316","sectionType":"section","heading":"Documents required to be kept","content":"### sec.316 Documents required to be kept\n\nThis section applies if, before the commencement—\na person was required to keep a document for a stated period under a former section mentioned in column 1 of the following table; and\nthe period had not ended.\nThe document must be kept under the new section mentioned in column 2 of the table opposite the former section for the remainder of the period.\nColumn 1\nColumn 2\nFormer section\nNew section\n1\nsection&#160;23(2) or (3) (Record keeping)\nsection&#160;204(2) or (3)\n2\nsection&#160;26(5) (Certificate of testing and safety)\nsection&#160;208(5)\n3\nsection&#160;91(2) (Assessment of electrical risk)\nsection&#160;41(2)\n4\nsection&#160;94(2) (Requirement for electrical safety inspection and test)\nsection&#160;44(2)\n5\nsection&#160;95(4) (Requirement for approved safety switch or permanent marking for electrical circuits)\nsection&#160;45(4)\n6\nsection&#160;120F(2) or (3) (Record keeping)\nsection&#160;36(2) or (3)\n7\nsection&#160;147(2) (Responsible supplier to keep evidence)\nsection&#160;76(2)\n8\nsection&#160;148(2) (Registered responsible supplier must keep compliance folder)\nsection&#160;77(2)\n9\nsection&#160;194(6) (Hiring electrical equipment)\nsection&#160;142(7)\n10\nsection&#160;220(4) (Reconnection of electrical installation to electricity source)\nsection&#160;220(4)\n11\nsection&#160;227(4) (Certificate of testing and compliance)\nsection&#160;229(5)\n12\nsection&#160;230(2) (Keeping copy of report)\nsection&#160;232(2)\n13\nsection&#160;248(1) (Records of tests to be kept)\nsection&#160;276(1)\n14\nsection&#160;265(6) (Duty of person conducting a business or undertaking to notify of serious electrical incident or dangerous electrical event)\nsection&#160;292(7)\n15\nsection&#160;267(2)(c) (Action required by distribution entity on report of electric shock)\nsection&#160;294(2)(c)\n(sec.316-ssec.1) This section applies if, before the commencement— a person was required to keep a document for a stated period under a former section mentioned in column 1 of the following table; and the period had not ended.\n(sec.316-ssec.2) The document must be kept under the new section mentioned in column 2 of the table opposite the former section for the remainder of the period. Column 1 Column 2 Former section New section 1 section&#160;23(2) or (3) (Record keeping) section&#160;204(2) or (3) 2 section&#160;26(5) (Certificate of testing and safety) section&#160;208(5) 3 section&#160;91(2) (Assessment of electrical risk) section&#160;41(2) 4 section&#160;94(2) (Requirement for electrical safety inspection and test) section&#160;44(2) 5 section&#160;95(4) (Requirement for approved safety switch or permanent marking for electrical circuits) section&#160;45(4) 6 section&#160;120F(2) or (3) (Record keeping) section&#160;36(2) or (3) 7 section&#160;147(2) (Responsible supplier to keep evidence) section&#160;76(2) 8 section&#160;148(2) (Registered responsible supplier must keep compliance folder) section&#160;77(2) 9 section&#160;194(6) (Hiring electrical equipment) section&#160;142(7) 10 section&#160;220(4) (Reconnection of electrical installation to electricity source) section&#160;220(4) 11 section&#160;227(4) (Certificate of testing and compliance) section&#160;229(5) 12 section&#160;230(2) (Keeping copy of report) section&#160;232(2) 13 section&#160;248(1) (Records of tests to be kept) section&#160;276(1) 14 section&#160;265(6) (Duty of person conducting a business or undertaking to notify of serious electrical incident or dangerous electrical event) section&#160;292(7) 15 section&#160;267(2)(c) (Action required by distribution entity on report of electric shock) section&#160;294(2)(c)\n- (a) a person was required to keep a document for a stated period under a former section mentioned in column 1 of the following table; and\n- (b) the period had not ended.","sortOrder":404},{"sectionNumber":"pt.16-div.3","sectionType":"division","heading":"Licensing","content":"## Licensing","sortOrder":405},{"sectionNumber":"sec.317","sectionType":"section","heading":"Electrical licences continued","content":"### sec.317 Electrical licences continued\n\nThis section applies to an electrical licence that was in effect under the expired regulation immediately before the commencement.\nFrom the commencement, the licence—\ncontinues in effect as a licence of the same class under this regulation for the remaining term of the licence; and\nis subject to the conditions to which it was subject immediately before the commencement.\n(sec.317-ssec.1) This section applies to an electrical licence that was in effect under the expired regulation immediately before the commencement.\n(sec.317-ssec.2) From the commencement, the licence— continues in effect as a licence of the same class under this regulation for the remaining term of the licence; and is subject to the conditions to which it was subject immediately before the commencement.\n- (a) continues in effect as a licence of the same class under this regulation for the remaining term of the licence; and\n- (b) is subject to the conditions to which it was subject immediately before the commencement.","sortOrder":406},{"sectionNumber":"sec.318","sectionType":"section","heading":"Electrical licence applications made before commencement","content":"### sec.318 Electrical licence applications made before commencement\n\nThis section applies if an application for the issue, renewal or reinstatement of an electrical licence was made, but not decided or withdrawn, before the commencement.\nFrom the commencement, the new eligibility requirements apply for the issue, renewal or reinstatement of the electrical licence.\nAnything done in relation to the application under the expired regulation is taken to have been done under new part&#160;7.\nNew section&#160;185 applies if the application is refused or withdrawn before it is decided.\nIn this section—\nnew eligibility requirements , for an electrical licence, means—\nfor the issue of an electrical work licence, other an electrical work training permit—new part&#160;7, division&#160;3, subdivision&#160;2; or\nfor the issue of an electrical work training permit—new part&#160;7, division&#160;3, subdivision&#160;3; or\nfor the issue of an electrical contractor licence—new part&#160;7, division&#160;4; or\nfor the renewal or reinstatement of an electrical licence—new part&#160;7, division&#160;5.\n(sec.318-ssec.1) This section applies if an application for the issue, renewal or reinstatement of an electrical licence was made, but not decided or withdrawn, before the commencement.\n(sec.318-ssec.2) From the commencement, the new eligibility requirements apply for the issue, renewal or reinstatement of the electrical licence.\n(sec.318-ssec.3) Anything done in relation to the application under the expired regulation is taken to have been done under new part&#160;7.\n(sec.318-ssec.4) New section&#160;185 applies if the application is refused or withdrawn before it is decided.\n(sec.318-ssec.5) In this section— new eligibility requirements , for an electrical licence, means— for the issue of an electrical work licence, other an electrical work training permit—new part&#160;7, division&#160;3, subdivision&#160;2; or for the issue of an electrical work training permit—new part&#160;7, division&#160;3, subdivision&#160;3; or for the issue of an electrical contractor licence—new part&#160;7, division&#160;4; or for the renewal or reinstatement of an electrical licence—new part&#160;7, division&#160;5.\n- (a) for the issue of an electrical work licence, other an electrical work training permit—new part&#160;7, division&#160;3, subdivision&#160;2; or\n- (b) for the issue of an electrical work training permit—new part&#160;7, division&#160;3, subdivision&#160;3; or\n- (c) for the issue of an electrical contractor licence—new part&#160;7, division&#160;4; or\n- (d) for the renewal or reinstatement of an electrical licence—new part&#160;7, division&#160;5.","sortOrder":407},{"sectionNumber":"sec.319","sectionType":"section","heading":"Existing electrical contractor licence—endorsement of qualified business person or qualified technical person","content":"### sec.319 Existing electrical contractor licence—endorsement of qualified business person or qualified technical person\n\nThis section applies to a person who, immediately before the commencement, was endorsed under the expired regulation as a qualified business person or qualified technical person for an electrical contractor licence.\nFrom the commencement, the person is taken to be endorsed under this regulation as a qualified business person or qualified technical person for the electrical contractor licence.\n(sec.319-ssec.1) This section applies to a person who, immediately before the commencement, was endorsed under the expired regulation as a qualified business person or qualified technical person for an electrical contractor licence.\n(sec.319-ssec.2) From the commencement, the person is taken to be endorsed under this regulation as a qualified business person or qualified technical person for the electrical contractor licence.","sortOrder":408},{"sectionNumber":"sec.320","sectionType":"section","heading":"Eligibility of particular persons for electrical linesperson licence","content":"### sec.320 Eligibility of particular persons for electrical linesperson licence\n\nThis section applies to a person if—\nimmediately before 1 October 2002, the person complied with the requirements under the repealed Electricity Regulation 1994 , section&#160;47 (2) or (3) , for the issue of a licence as an electrical linesperson; and\nfrom 1 July 2007, the repealed Electrical Safety Regulation 2002 , section&#160;215(2) continued to apply to the person.\nSee the repealed Electrical Safety Regulation 2002 , sections&#160;215 and 222.\nThe person is taken to comply with the eligibility requirements for the issue, renewal or reinstatement of an electrical linesperson licence under this regulation.\n(sec.320-ssec.1) This section applies to a person if— immediately before 1 October 2002, the person complied with the requirements under the repealed Electricity Regulation 1994 , section&#160;47 (2) or (3) , for the issue of a licence as an electrical linesperson; and from 1 July 2007, the repealed Electrical Safety Regulation 2002 , section&#160;215(2) continued to apply to the person. See the repealed Electrical Safety Regulation 2002 , sections&#160;215 and 222.\n(sec.320-ssec.2) The person is taken to comply with the eligibility requirements for the issue, renewal or reinstatement of an electrical linesperson licence under this regulation.\n- (a) immediately before 1 October 2002, the person complied with the requirements under the repealed Electricity Regulation 1994 , section&#160;47 (2) or (3) , for the issue of a licence as an electrical linesperson; and\n- (b) from 1 July 2007, the repealed Electrical Safety Regulation 2002 , section&#160;215(2) continued to apply to the person.","sortOrder":409},{"sectionNumber":"sec.321","sectionType":"section","heading":"Eligibility of particular persons for electrical jointer licence","content":"### sec.321 Eligibility of particular persons for electrical jointer licence\n\nThis section applies to a person if—\nimmediately before 1 October 2002, the person complied with the requirements of the repealed Electricity Regulation 1994 , section&#160;46(2) or (3) for the issue of a licence as an electrical jointer; and\nfrom 1 July 2007, the repealed Electrical Safety Regulation 2002 , section&#160;214(2) continued to apply to the person.\nSee the repealed Electrical Safety Regulation 2002 , sections&#160;214 and 221.\nThe person is taken to comply with the eligibility requirements for the issue, renewal or reinstatement of an electrical jointer licence under this regulation.\n(sec.321-ssec.1) This section applies to a person if— immediately before 1 October 2002, the person complied with the requirements of the repealed Electricity Regulation 1994 , section&#160;46(2) or (3) for the issue of a licence as an electrical jointer; and from 1 July 2007, the repealed Electrical Safety Regulation 2002 , section&#160;214(2) continued to apply to the person. See the repealed Electrical Safety Regulation 2002 , sections&#160;214 and 221.\n(sec.321-ssec.2) The person is taken to comply with the eligibility requirements for the issue, renewal or reinstatement of an electrical jointer licence under this regulation.\n- (a) immediately before 1 October 2002, the person complied with the requirements of the repealed Electricity Regulation 1994 , section&#160;46(2) or (3) for the issue of a licence as an electrical jointer; and\n- (b) from 1 July 2007, the repealed Electrical Safety Regulation 2002 , section&#160;214(2) continued to apply to the person.","sortOrder":410},{"sectionNumber":"sec.322","sectionType":"section","heading":"Automatic suspension and cancellation of electrical contractor licence","content":"### sec.322 Automatic suspension and cancellation of electrical contractor licence\n\nThis section applies if, immediately before the commencement—\nthere was no qualified business person or qualified technical person endorsed on an electrical contractor licence; and\nthe licence was suspended under former section&#160;50.\nFrom the commencement, new section&#160;175 applies in relation to the licence as if it were suspended under new section&#160;175(1) on the day the suspension mentioned in subsection&#160;(1)(b) started.\n(sec.322-ssec.1) This section applies if, immediately before the commencement— there was no qualified business person or qualified technical person endorsed on an electrical contractor licence; and the licence was suspended under former section&#160;50.\n(sec.322-ssec.2) From the commencement, new section&#160;175 applies in relation to the licence as if it were suspended under new section&#160;175(1) on the day the suspension mentioned in subsection&#160;(1)(b) started.\n- (a) there was no qualified business person or qualified technical person endorsed on an electrical contractor licence; and\n- (b) the licence was suspended under former section&#160;50.","sortOrder":411},{"sectionNumber":"sec.323","sectionType":"section","heading":"Other changes to particular electrical contractor licences","content":"### sec.323 Other changes to particular electrical contractor licences\n\nThis section applies if—\na change mentioned in a relevant licensing provision happened in relation to an electrical contractor licence before the commencement; and\nimmediately before the commencement, the regulator had not decided or dealt with the change to the licence as a result of the change.\nSee also section&#160;315.\nFrom the commencement, the corresponding section applies in relation to the change.\nIn this section—\ncorresponding section , for a relevant licensing provision, means—\nfor former section&#160;49(1) or (2)—new section&#160;174; or\nfor former section&#160;52(1)—new section&#160;176; or\nfor former section&#160;53(1)—new section&#160;177.\nrelevant licensing provision means—\nformer section&#160;49(1) or (2); or\nformer section&#160;52(1); or\nformer section&#160;53(1).\n(sec.323-ssec.1) This section applies if— a change mentioned in a relevant licensing provision happened in relation to an electrical contractor licence before the commencement; and immediately before the commencement, the regulator had not decided or dealt with the change to the licence as a result of the change. See also section&#160;315.\n(sec.323-ssec.2) From the commencement, the corresponding section applies in relation to the change.\n(sec.323-ssec.3) In this section— corresponding section , for a relevant licensing provision, means— for former section&#160;49(1) or (2)—new section&#160;174; or for former section&#160;52(1)—new section&#160;176; or for former section&#160;53(1)—new section&#160;177. relevant licensing provision means— former section&#160;49(1) or (2); or former section&#160;52(1); or former section&#160;53(1).\n- (a) a change mentioned in a relevant licensing provision happened in relation to an electrical contractor licence before the commencement; and\n- (b) immediately before the commencement, the regulator had not decided or dealt with the change to the licence as a result of the change.\n- (a) for former section&#160;49(1) or (2)—new section&#160;174; or\n- (b) for former section&#160;52(1)—new section&#160;176; or\n- (c) for former section&#160;53(1)—new section&#160;177.\n- (a) former section&#160;49(1) or (2); or\n- (b) former section&#160;52(1); or\n- (c) former section&#160;53(1).","sortOrder":412},{"sectionNumber":"pt.16-div.4","sectionType":"division","heading":"In-scope electrical equipment","content":"## In-scope electrical equipment","sortOrder":413},{"sectionNumber":"sec.324","sectionType":"section","heading":"Existing accepted standards for level 2 or 3 in-scope electrical equipment","content":"### sec.324 Existing accepted standards for level 2 or 3 in-scope electrical equipment\n\nThis section applies if—\nbefore the commencement, a standard had been accepted by the regulator under former section&#160;127 as a standard that can be readily applied to a type of level 2 or 3 in-scope electrical equipment; and\nimmediately before the commencement, the standard had not been superseded or withdrawn.\nFrom the commencement, the standard is taken to have been accepted by the regulator as a standard that can be readily applied to the type under new section&#160;56.\n(sec.324-ssec.1) This section applies if— before the commencement, a standard had been accepted by the regulator under former section&#160;127 as a standard that can be readily applied to a type of level 2 or 3 in-scope electrical equipment; and immediately before the commencement, the standard had not been superseded or withdrawn.\n(sec.324-ssec.2) From the commencement, the standard is taken to have been accepted by the regulator as a standard that can be readily applied to the type under new section&#160;56.\n- (a) before the commencement, a standard had been accepted by the regulator under former section&#160;127 as a standard that can be readily applied to a type of level 2 or 3 in-scope electrical equipment; and\n- (b) immediately before the commencement, the standard had not been superseded or withdrawn.","sortOrder":414},{"sectionNumber":"sec.325","sectionType":"section","heading":"Continued registration of responsible supplier or in-scope electrical equipment","content":"### sec.325 Continued registration of responsible supplier or in-scope electrical equipment\n\nThis section applies if, immediately before the commencement—\na responsible supplier of in-scope electrical equipment was registered under former part&#160;7, division&#160;2; or\na type of level 2 or 3 in-scope electrical equipment was registered under former part&#160;7, division&#160;2.\nFrom the commencement, the registration continues in effect under this regulation for its remaining term.\n(sec.325-ssec.1) This section applies if, immediately before the commencement— a responsible supplier of in-scope electrical equipment was registered under former part&#160;7, division&#160;2; or a type of level 2 or 3 in-scope electrical equipment was registered under former part&#160;7, division&#160;2.\n(sec.325-ssec.2) From the commencement, the registration continues in effect under this regulation for its remaining term.\n- (a) a responsible supplier of in-scope electrical equipment was registered under former part&#160;7, division&#160;2; or\n- (b) a type of level 2 or 3 in-scope electrical equipment was registered under former part&#160;7, division&#160;2.","sortOrder":415},{"sectionNumber":"sec.326","sectionType":"section","heading":"Applications for registration of responsible supplier or in-scope electrical equipment made before commencement","content":"### sec.326 Applications for registration of responsible supplier or in-scope electrical equipment made before commencement\n\nThis section applies if, before the commencement, a registration process had started but not ended under former part&#160;7, division&#160;2.\nFrom the commencement, the registration process must be completed under new part&#160;4, division&#160;2.\nAnything done in relation to the registration process under the expired regulation is taken to have been done in relation to the registration process under this regulation.\n(sec.326-ssec.1) This section applies if, before the commencement, a registration process had started but not ended under former part&#160;7, division&#160;2.\n(sec.326-ssec.2) From the commencement, the registration process must be completed under new part&#160;4, division&#160;2.\n(sec.326-ssec.3) Anything done in relation to the registration process under the expired regulation is taken to have been done in relation to the registration process under this regulation.","sortOrder":416},{"sectionNumber":"sec.327","sectionType":"section","heading":"Approved marks continued","content":"### sec.327 Approved marks continued\n\nThis section applies if—\nbefore the commencement, the regulator approved a mark under former section&#160;153; and\nimmediately before the commencement, the approval had not been revoked.\nFrom the commencement, the mark is taken to have been approved under new section&#160;82.\n(sec.327-ssec.1) This section applies if— before the commencement, the regulator approved a mark under former section&#160;153; and immediately before the commencement, the approval had not been revoked.\n(sec.327-ssec.2) From the commencement, the mark is taken to have been approved under new section&#160;82.\n- (a) before the commencement, the regulator approved a mark under former section&#160;153; and\n- (b) immediately before the commencement, the approval had not been revoked.","sortOrder":417},{"sectionNumber":"sec.328","sectionType":"section","heading":"Certificates of conformity continued","content":"### sec.328 Certificates of conformity continued\n\nThis section applies if, immediately before the commencement, a certificate of conformity was in force under former section&#160;156.\nFrom the commencement, the certificate of conformity continues in force as if it had been issued under new part&#160;4, division&#160;7.\n(sec.328-ssec.1) This section applies if, immediately before the commencement, a certificate of conformity was in force under former section&#160;156.\n(sec.328-ssec.2) From the commencement, the certificate of conformity continues in force as if it had been issued under new part&#160;4, division&#160;7.","sortOrder":418},{"sectionNumber":"sec.329","sectionType":"section","heading":"Existing cancellation processes","content":"### sec.329 Existing cancellation processes\n\nThis section applies if—\nbefore the commencement, the regulator gave a person a notice (a cancellation notice ) under a former section mentioned in column 1 of the following table; and\nimmediately before the commencement, the regulator had not decided whether to cancel the registration or certificate that was the subject of the cancellation notice.\nThe cancellation notice—\nis taken to have been given under the new section mentioned in column 2 of the table opposite the former section; and\nmust be decided under the new section mentioned in column 3 of the table opposite the former section.\nThe new section mentioned in column 3 of the table applies to the decision to cancel, or not to cancel, the registration or certificate.\nAnything done in relation to the proposed cancellation under the expired regulation is taken to have been done in relation to the proposed cancellation under this regulation.\nColumn 1\nColumn 2\nColumn 3\nFormer notice section\nNew notice section\nNew decision section\n1\nsection&#160;140 (Procedure before cancellation)\nsection&#160;69(2)\nsection&#160;70\n2\nsection&#160;162 (Procedure before cancellation)\nsection&#160;91(1)\nsection&#160;91(2) and (3)\n3\nsection&#160;177 (Procedure before cancellation)\nsection&#160;106(1)\nsection&#160;106(3) and (5)\n(sec.329-ssec.1) This section applies if— before the commencement, the regulator gave a person a notice (a cancellation notice ) under a former section mentioned in column 1 of the following table; and immediately before the commencement, the regulator had not decided whether to cancel the registration or certificate that was the subject of the cancellation notice.\n(sec.329-ssec.2) The cancellation notice— is taken to have been given under the new section mentioned in column 2 of the table opposite the former section; and must be decided under the new section mentioned in column 3 of the table opposite the former section.\n(sec.329-ssec.3) The new section mentioned in column 3 of the table applies to the decision to cancel, or not to cancel, the registration or certificate.\n(sec.329-ssec.4) Anything done in relation to the proposed cancellation under the expired regulation is taken to have been done in relation to the proposed cancellation under this regulation. Column 1 Column 2 Column 3 Former notice section New notice section New decision section 1 section&#160;140 (Procedure before cancellation) section&#160;69(2) section&#160;70 2 section&#160;162 (Procedure before cancellation) section&#160;91(1) section&#160;91(2) and (3) 3 section&#160;177 (Procedure before cancellation) section&#160;106(1) section&#160;106(3) and (5)\n- (a) before the commencement, the regulator gave a person a notice (a cancellation notice ) under a former section mentioned in column 1 of the following table; and\n- (b) immediately before the commencement, the regulator had not decided whether to cancel the registration or certificate that was the subject of the cancellation notice.\n- (a) is taken to have been given under the new section mentioned in column 2 of the table opposite the former section; and\n- (b) must be decided under the new section mentioned in column 3 of the table opposite the former section.","sortOrder":419},{"sectionNumber":"sec.330","sectionType":"section","heading":"Particular references relating to cancellation and offences","content":"### sec.330 Particular references relating to cancellation and offences\n\nSubsection&#160;(2) applies if either of the following was cancelled before the commencement under former section&#160;141—\na responsible supplier’s registration;\nthe registration of a type of level 2 or 3 in-scope electrical equipment registered in relation to a registered responsible supplier.\nNew section&#160;70(2) to (4) applies as if the registration had been cancelled under that section.\nSubsection&#160;(4) applies if, immediately before the commencement, a person was—\na registered responsible supplier; or\nthe holder of a certificate of conformity.\nA reference in new section&#160;68(1)(a) or (2)(a) or 90(e) to an offence against this regulation includes a reference to an offence against the expired regulation.\n(sec.330-ssec.1) Subsection&#160;(2) applies if either of the following was cancelled before the commencement under former section&#160;141— a responsible supplier’s registration; the registration of a type of level 2 or 3 in-scope electrical equipment registered in relation to a registered responsible supplier.\n(sec.330-ssec.2) New section&#160;70(2) to (4) applies as if the registration had been cancelled under that section.\n(sec.330-ssec.3) Subsection&#160;(4) applies if, immediately before the commencement, a person was— a registered responsible supplier; or the holder of a certificate of conformity.\n(sec.330-ssec.4) A reference in new section&#160;68(1)(a) or (2)(a) or 90(e) to an offence against this regulation includes a reference to an offence against the expired regulation.\n- (a) a responsible supplier’s registration;\n- (b) the registration of a type of level 2 or 3 in-scope electrical equipment registered in relation to a registered responsible supplier.\n- (a) a registered responsible supplier; or\n- (b) the holder of a certificate of conformity.","sortOrder":420},{"sectionNumber":"sec.331","sectionType":"section","heading":"Compliance with notices given before commencement","content":"### sec.331 Compliance with notices given before commencement\n\nThis section applies if—\na person was given a notice by the regulator under a former section mentioned in column 1 of the following table; and\nimmediately before the commencement—\nthe person had not complied with the notice; and\nthe period for complying with the notice (the compliance period ) had not ended.\nThe notice is taken to have been given under the new section mentioned in column 2 of the table opposite the former section.\nThe notice must be complied with before the compliance period ends.\nColumn 1\nColumn 2\nFormer section\nNew section\n1\nsection&#160;164 (Certificate of conformity holder to return certificate if cancelled)\nsection&#160;93\n2\nsection&#160;179 (Reporting requirements for declaration holder)\nsection&#160;108\n3\nsection&#160;182 (Procedure for obtaining item of in-scope electrical equipment for testing)\nsection&#160;111\n4\nsection&#160;185 (Return of item of level 2 or 3 in-scope electrical equipment provided to regulator)\nsection&#160;114\n(sec.331-ssec.1) This section applies if— a person was given a notice by the regulator under a former section mentioned in column 1 of the following table; and immediately before the commencement— the person had not complied with the notice; and the period for complying with the notice (the compliance period ) had not ended.\n(sec.331-ssec.2) The notice is taken to have been given under the new section mentioned in column 2 of the table opposite the former section.\n(sec.331-ssec.3) The notice must be complied with before the compliance period ends. Column 1 Column 2 Former section New section 1 section&#160;164 (Certificate of conformity holder to return certificate if cancelled) section&#160;93 2 section&#160;179 (Reporting requirements for declaration holder) section&#160;108 3 section&#160;182 (Procedure for obtaining item of in-scope electrical equipment for testing) section&#160;111 4 section&#160;185 (Return of item of level 2 or 3 in-scope electrical equipment provided to regulator) section&#160;114\n- (a) a person was given a notice by the regulator under a former section mentioned in column 1 of the following table; and\n- (b) immediately before the commencement— (i) the person had not complied with the notice; and (ii) the period for complying with the notice (the compliance period ) had not ended.\n- (i) the person had not complied with the notice; and\n- (ii) the period for complying with the notice (the compliance period ) had not ended.\n- (i) the person had not complied with the notice; and\n- (ii) the period for complying with the notice (the compliance period ) had not ended.","sortOrder":421},{"sectionNumber":"sec.332","sectionType":"section","heading":"In-scope electrical equipment reclassified before the commencement","content":"### sec.332 In-scope electrical equipment reclassified before the commencement\n\nThis section applies if—\nbefore the commencement, a type of level 1 or 2 in-scope electrical equipment was reclassified to a higher level; and\nimmediately before the commencement, the period mentioned in former section&#160;150(2) has not ended.\nFrom the commencement, new section&#160;79 applies as if the in-scope electrical equipment were reclassified to a higher level under that section on the day the equipment was reclassified.\n(sec.332-ssec.1) This section applies if— before the commencement, a type of level 1 or 2 in-scope electrical equipment was reclassified to a higher level; and immediately before the commencement, the period mentioned in former section&#160;150(2) has not ended.\n(sec.332-ssec.2) From the commencement, new section&#160;79 applies as if the in-scope electrical equipment were reclassified to a higher level under that section on the day the equipment was reclassified.\n- (a) before the commencement, a type of level 1 or 2 in-scope electrical equipment was reclassified to a higher level; and\n- (b) immediately before the commencement, the period mentioned in former section&#160;150(2) has not ended.","sortOrder":422},{"sectionNumber":"sec.333","sectionType":"section","heading":"Items of in-scope electrical equipment submitted to regulator for testing and examination","content":"### sec.333 Items of in-scope electrical equipment submitted to regulator for testing and examination\n\nSubsection&#160;(2) applies if—\nbefore the commencement, an item of level 3 in-scope electrical equipment was given to the regulator under former part&#160;7, division&#160;7; and\nimmediately before the commencement, the item had not been collected, disposed of or destroyed under former section&#160;185.\nSee also section&#160;331.\nNew section&#160;114 applies in relation to the item as if the item had been obtained under new part&#160;4, division&#160;7.\nSubsection&#160;(4) applies if—\nbefore the commencement, an item of level 2 or 3 in-scope electrical equipment was given to the regulator for testing and examination under former part&#160;7, division&#160;9; and\nimmediately before the commencement, the item had not been collected, disposed of or destroyed under former section&#160;185.\nSee also section&#160;331.\nNew sections&#160;112 to 114 apply in relation to the item as if it had been obtained under new section&#160;111(1)(a).\n(sec.333-ssec.1) Subsection&#160;(2) applies if— before the commencement, an item of level 3 in-scope electrical equipment was given to the regulator under former part&#160;7, division&#160;7; and immediately before the commencement, the item had not been collected, disposed of or destroyed under former section&#160;185. See also section&#160;331.\n(sec.333-ssec.2) New section&#160;114 applies in relation to the item as if the item had been obtained under new part&#160;4, division&#160;7.\n(sec.333-ssec.3) Subsection&#160;(4) applies if— before the commencement, an item of level 2 or 3 in-scope electrical equipment was given to the regulator for testing and examination under former part&#160;7, division&#160;9; and immediately before the commencement, the item had not been collected, disposed of or destroyed under former section&#160;185. See also section&#160;331.\n(sec.333-ssec.4) New sections&#160;112 to 114 apply in relation to the item as if it had been obtained under new section&#160;111(1)(a).\n- (a) before the commencement, an item of level 3 in-scope electrical equipment was given to the regulator under former part&#160;7, division&#160;7; and\n- (b) immediately before the commencement, the item had not been collected, disposed of or destroyed under former section&#160;185.\n- (a) before the commencement, an item of level 2 or 3 in-scope electrical equipment was given to the regulator for testing and examination under former part&#160;7, division&#160;9; and\n- (b) immediately before the commencement, the item had not been collected, disposed of or destroyed under former section&#160;185.","sortOrder":423},{"sectionNumber":"sec.334","sectionType":"section","heading":"Provision for recognised external certification schemes","content":"### sec.334 Provision for recognised external certification schemes\n\nThis section applies to a declared scheme that was in effect immediately before the commencement.\nFrom the commencement, the external certification scheme is taken to be a declared scheme under new part&#160;4, division&#160;8.\nA condition imposed under a former section mentioned in column 1 of the following table is taken to have been imposed under the new section mentioned in column 2 opposite the former section.\nColumn 1\nColumn 2\nFormer section\nNew section\n1\nsection&#160;171 (Regulator may impose conditions on declared scheme)\nsection&#160;100\n2\nsection&#160;172 (Condition imposed by regulation)\nsection&#160;101\nSubsection&#160;(5) applies if, before the commencement, the regulator had given a declaration holder a written notice under former section&#160;174(1), but had not made a decision about amending the conditions.\nFrom the commencement, the notice is taken to have been given under new section&#160;103(1).\n(sec.334-ssec.1) This section applies to a declared scheme that was in effect immediately before the commencement.\n(sec.334-ssec.2) From the commencement, the external certification scheme is taken to be a declared scheme under new part&#160;4, division&#160;8.\n(sec.334-ssec.3) A condition imposed under a former section mentioned in column 1 of the following table is taken to have been imposed under the new section mentioned in column 2 opposite the former section. Column 1 Column 2 Former section New section 1 section&#160;171 (Regulator may impose conditions on declared scheme) section&#160;100 2 section&#160;172 (Condition imposed by regulation) section&#160;101\n(sec.334-ssec.4) Subsection&#160;(5) applies if, before the commencement, the regulator had given a declaration holder a written notice under former section&#160;174(1), but had not made a decision about amending the conditions.\n(sec.334-ssec.5) From the commencement, the notice is taken to have been given under new section&#160;103(1).","sortOrder":424},{"sectionNumber":"sec.335","sectionType":"section","heading":"Programs for certificates of suitability continued","content":"### sec.335 Programs for certificates of suitability continued\n\nThis section applies to a program that—\nwas established, before the commencement, under former section&#160;187; and\nimmediately before the commencement, had not been disestablished.\nFrom the commencement, the program is taken to have been established under new section&#160;116.\n(sec.335-ssec.1) This section applies to a program that— was established, before the commencement, under former section&#160;187; and immediately before the commencement, had not been disestablished.\n(sec.335-ssec.2) From the commencement, the program is taken to have been established under new section&#160;116.\n- (a) was established, before the commencement, under former section&#160;187; and\n- (b) immediately before the commencement, had not been disestablished.","sortOrder":425},{"sectionNumber":"pt.16-div.5","sectionType":"division","heading":"Existing overhead electric lines","content":"## Existing overhead electric lines","sortOrder":426},{"sectionNumber":"sec.336","sectionType":"section","heading":"Clearances for lines built before 1 January 1995","content":"### sec.336 Clearances for lines built before 1 January 1995\n\nThis section applies to an overhead electric line built before 1 January 1995 that—\nimmediately before 1 January 1995, complied with the clearance requirements of the repealed Electricity Regulation 1989 ; and\nwould be in compliance with the clearance requirements mentioned in paragraph&#160;(a) if the requirements were still in effect; and\nwas not rebuilt or replaced before the commencement.\nThe overhead electric line is taken to comply with clearance requirements under new part&#160;12, division&#160;4 for overhead electric lines.\nThis section stops applying if the overhead electric line is replaced or rebuilt.\n(sec.336-ssec.1) This section applies to an overhead electric line built before 1 January 1995 that— immediately before 1 January 1995, complied with the clearance requirements of the repealed Electricity Regulation 1989 ; and would be in compliance with the clearance requirements mentioned in paragraph&#160;(a) if the requirements were still in effect; and was not rebuilt or replaced before the commencement.\n(sec.336-ssec.2) The overhead electric line is taken to comply with clearance requirements under new part&#160;12, division&#160;4 for overhead electric lines.\n(sec.336-ssec.3) This section stops applying if the overhead electric line is replaced or rebuilt.\n- (a) immediately before 1 January 1995, complied with the clearance requirements of the repealed Electricity Regulation 1989 ; and\n- (b) would be in compliance with the clearance requirements mentioned in paragraph&#160;(a) if the requirements were still in effect; and\n- (c) was not rebuilt or replaced before the commencement.","sortOrder":427},{"sectionNumber":"sec.337","sectionType":"section","heading":"Termination of low voltage overhead service line built before 1 January 1995","content":"### sec.337 Termination of low voltage overhead service line built before 1 January 1995\n\nThis section applies to a low voltage overhead service line built before 1 January 1995 that—\nimmediately before 1 January 1995, complied with the termination requirements of the repealed Electricity Regulation 1989 ; and\nwould be in compliance with the termination requirements mentioned in paragraph&#160;(a) if the requirements were still in effect; and\nwas not rebuilt or replaced before the commencement.\nThe low voltage overhead service line is taken to comply with termination requirements under new part&#160;12, division&#160;5 for low voltage overhead service lines.\nThis section stops applying if the low voltage overhead service line is replaced or rebuilt.\n(sec.337-ssec.1) This section applies to a low voltage overhead service line built before 1 January 1995 that— immediately before 1 January 1995, complied with the termination requirements of the repealed Electricity Regulation 1989 ; and would be in compliance with the termination requirements mentioned in paragraph&#160;(a) if the requirements were still in effect; and was not rebuilt or replaced before the commencement.\n(sec.337-ssec.2) The low voltage overhead service line is taken to comply with termination requirements under new part&#160;12, division&#160;5 for low voltage overhead service lines.\n(sec.337-ssec.3) This section stops applying if the low voltage overhead service line is replaced or rebuilt.\n- (a) immediately before 1 January 1995, complied with the termination requirements of the repealed Electricity Regulation 1989 ; and\n- (b) would be in compliance with the termination requirements mentioned in paragraph&#160;(a) if the requirements were still in effect; and\n- (c) was not rebuilt or replaced before the commencement.","sortOrder":428},{"sectionNumber":"sec.338","sectionType":"section","heading":"Clearances for lines built between 1 January 1995 and 1 October 2002","content":"### sec.338 Clearances for lines built between 1 January 1995 and 1 October 2002\n\nThis section applies to an overhead electric line built on or after 1 January 1995 but before 1 October 2002 that—\nimmediately before 1 October 2002, complied with the clearance requirements of the repealed Electricity Regulation 1994 ; and\nwould be in compliance with the clearance requirements of the repealed Electricity Regulation 1994 if the requirements were still in force; and\nwas not rebuilt or replaced before the commencement.\nThe overhead electric line is taken to comply with clearance requirements under new part&#160;12, division&#160;4 for overhead electric lines.\nThis section stops applying if the overhead electric line is replaced or rebuilt.\n(sec.338-ssec.1) This section applies to an overhead electric line built on or after 1 January 1995 but before 1 October 2002 that— immediately before 1 October 2002, complied with the clearance requirements of the repealed Electricity Regulation 1994 ; and would be in compliance with the clearance requirements of the repealed Electricity Regulation 1994 if the requirements were still in force; and was not rebuilt or replaced before the commencement.\n(sec.338-ssec.2) The overhead electric line is taken to comply with clearance requirements under new part&#160;12, division&#160;4 for overhead electric lines.\n(sec.338-ssec.3) This section stops applying if the overhead electric line is replaced or rebuilt.\n- (a) immediately before 1 October 2002, complied with the clearance requirements of the repealed Electricity Regulation 1994 ; and\n- (b) would be in compliance with the clearance requirements of the repealed Electricity Regulation 1994 if the requirements were still in force; and\n- (c) was not rebuilt or replaced before the commencement.","sortOrder":429},{"sectionNumber":"pt.16-div.6","sectionType":"division","heading":"Safety management systems","content":"## Safety management systems","sortOrder":430},{"sectionNumber":"sec.339","sectionType":"section","heading":"Deferral of new pt&#160;10, div&#160;2","content":"### sec.339 Deferral of new pt&#160;10, div&#160;2\n\nNew part&#160;10, division&#160;2 does not apply in relation to a prescribed electricity entity during the period—\nstarting on the day of the commencement; and\nending on 1 September 2027.\nDuring the period mentioned in subsection&#160;(1), former section&#160;234 continues to apply as if this regulation had not been made.\n(sec.339-ssec.1) New part&#160;10, division&#160;2 does not apply in relation to a prescribed electricity entity during the period— starting on the day of the commencement; and ending on 1 September 2027.\n(sec.339-ssec.2) During the period mentioned in subsection&#160;(1), former section&#160;234 continues to apply as if this regulation had not been made.\n- (a) starting on the day of the commencement; and\n- (b) ending on 1 September 2027.","sortOrder":431},{"sectionNumber":"pt.16-div.7","sectionType":"division","heading":"Miscellaneous","content":"## Miscellaneous","sortOrder":432},{"sectionNumber":"sec.340","sectionType":"section","heading":"Existing high voltage live line work authorisations","content":"### sec.340 Existing high voltage live line work authorisations\n\nThis section applies if, immediately before the commencement, a person was authorised in writing to perform high voltage live line work under former section&#160;24.\nFrom the commencement, the authorisation is taken to have been given under new section&#160;205.\n(sec.340-ssec.1) This section applies if, immediately before the commencement, a person was authorised in writing to perform high voltage live line work under former section&#160;24.\n(sec.340-ssec.2) From the commencement, the authorisation is taken to have been given under new section&#160;205.","sortOrder":433},{"sectionNumber":"sec.341","sectionType":"section","heading":"Former s&#160;74 continued in relation to particular defect notices","content":"### sec.341 Former s&#160;74 continued in relation to particular defect notices\n\nThis section applies if—\nbefore the commencement, a notice relating to a defect was given to a person in control of electrical equipment under former section&#160;74; and\nimmediately before the commencement, the person had not taken all reasonable steps to ensure the defect was fixed.\nFrom the commencement, former section&#160;74 continues to apply to the person in relation to the notice as if this regulation had not been made.\n(sec.341-ssec.1) This section applies if— before the commencement, a notice relating to a defect was given to a person in control of electrical equipment under former section&#160;74; and immediately before the commencement, the person had not taken all reasonable steps to ensure the defect was fixed.\n(sec.341-ssec.2) From the commencement, former section&#160;74 continues to apply to the person in relation to the notice as if this regulation had not been made.\n- (a) before the commencement, a notice relating to a defect was given to a person in control of electrical equipment under former section&#160;74; and\n- (b) immediately before the commencement, the person had not taken all reasonable steps to ensure the defect was fixed.","sortOrder":434},{"sectionNumber":"sec.342","sectionType":"section","heading":"Registers continued","content":"### sec.342 Registers continued\n\nThe following registers kept under the expired regulation immediately before the commencement are, from the commencement, taken to be kept under this regulation—\nthe register of electrical licences;\nthe register of registered systems.\n- (a) the register of electrical licences;\n- (b) the register of registered systems.","sortOrder":435},{"sectionNumber":"sec.343","sectionType":"section","heading":"Existing registrable systems","content":"### sec.343 Existing registrable systems\n\nThis section applies if, immediately before the commencement, a registrable system was registered under former section&#160;257.\nFrom the commencement, the registrable system is taken to be registered under new section&#160;284.\n(sec.343-ssec.1) This section applies if, immediately before the commencement, a registrable system was registered under former section&#160;257.\n(sec.343-ssec.2) From the commencement, the registrable system is taken to be registered under new section&#160;284.","sortOrder":436},{"sectionNumber":"sec.344","sectionType":"section","heading":"References to expired regulation","content":"### sec.344 References to expired regulation\n\nIn an instrument—\na reference to the expired regulation may, if the context permits, be taken to be a reference to this regulation; and\na reference to a former provision, if the context permits, may be taken to be a reference to the new provision corresponding to the former provision.\n- (a) a reference to the expired regulation may, if the context permits, be taken to be a reference to this regulation; and\n- (b) a reference to a former provision, if the context permits, may be taken to be a reference to the new provision corresponding to the former provision.","sortOrder":437},{"sectionNumber":"sch.2-pt.1","sectionType":"part","heading":"Preliminary","content":"# Preliminary","sortOrder":438},{"sectionNumber":"sch.2-sec.1","sectionType":"section","heading":"Definitions for sch&#160;2","content":"### sch.2-sec.1 Definitions for sch&#160;2\n\nIn this schedule—\nanother safe system , for the operation of operating plant, means a system of work that—\nhas been developed in consultation with persons who are broadly representative of industrial organisations of employees whose members commonly operate operating plant of the operating plant’s type; and\nprovides, for persons and property, the same level of electrical safety as, or a greater level of electrical safety than, the level of electrical safety provided with a safety observer.\nauthorised person , for an electric line, means a person who—\nhas enough technical knowledge and experience to do work that involves contact with, or being near to, the electric line; and\neither—\nhas been approved by the person in control of the electric line to do work that involves contact with, or being near to, the electric line; or\nis authorised to act for the person in control of the electric line.\ninstructed person , for an electric line, means a person who is acting under the supervision of an authorised person for the electric line.\nsafety observer , for the operation of operating plant, means a person who—\nobserves the operating plant; and\nadvises the operator of the operating plant if it is likely that the operating plant will come within an exclusion zone for the operating plant for an overhead electric line.\nuntrained person , for an electric line, means a person who is not an authorised person or an instructed person for the electric line.\n- (a) has been developed in consultation with persons who are broadly representative of industrial organisations of employees whose members commonly operate operating plant of the operating plant’s type; and\n- (b) provides, for persons and property, the same level of electrical safety as, or a greater level of electrical safety than, the level of electrical safety provided with a safety observer.\n- (a) has enough technical knowledge and experience to do work that involves contact with, or being near to, the electric line; and\n- (b) either— (i) has been approved by the person in control of the electric line to do work that involves contact with, or being near to, the electric line; or (ii) is authorised to act for the person in control of the electric line.\n- (i) has been approved by the person in control of the electric line to do work that involves contact with, or being near to, the electric line; or\n- (ii) is authorised to act for the person in control of the electric line.\n- (i) has been approved by the person in control of the electric line to do work that involves contact with, or being near to, the electric line; or\n- (ii) is authorised to act for the person in control of the electric line.\n- (a) observes the operating plant; and\n- (b) advises the operator of the operating plant if it is likely that the operating plant will come within an exclusion zone for the operating plant for an overhead electric line.","sortOrder":439},{"sectionNumber":"sch.2-sec.2","sectionType":"section","heading":"Authorised persons and instructed persons taken to be untrained persons in particular circumstances","content":"### sch.2-sec.2 Authorised persons and instructed persons taken to be untrained persons in particular circumstances\n\nThis section applies if operating plant is operated—\nby an authorised person or instructed person for an electric line; and\nwithout a safety observer or another safe system.\nThe operating plant is taken to be operated by an untrained person for the electric line.\n(sch.2-sec.2-ssec.1) This section applies if operating plant is operated— by an authorised person or instructed person for an electric line; and without a safety observer or another safe system.\n(sch.2-sec.2-ssec.2) The operating plant is taken to be operated by an untrained person for the electric line.\n- (a) by an authorised person or instructed person for an electric line; and\n- (b) without a safety observer or another safe system.","sortOrder":440},{"sectionNumber":"sch.2-sec.3","sectionType":"section","heading":"Exclusion zones for operating plant fitted with certain safety devices","content":"### sch.2-sec.3 Exclusion zones for operating plant fitted with certain safety devices\n\nThis section applies if—\noperating plant, operated by an authorised person or instructed person for an electric line, is fitted with a device capable of stopping the operation of the plant immediately when the operating plant is at the exclusion zone for an authorised person or instructed person for the electric line; and\na safe system of work for the use of the operating plant is in place; and\nthe safe system of work has been developed in consultation with persons who are broadly representative of industrial organisations of employees whose members commonly operate operating plant of the operating plant’s type; and\nwithout limiting paragraph&#160;(b) , the safe system of work ensures the device mentioned in paragraph&#160;(a) —\nis operating properly; and\nis set for at least the correct exclusion zone distance.\nThe exclusion zone for an authorised person or instructed person for the electric line applies as the exclusion zone for the operating plant for the electric line.\n(sch.2-sec.3-ssec.1) This section applies if— operating plant, operated by an authorised person or instructed person for an electric line, is fitted with a device capable of stopping the operation of the plant immediately when the operating plant is at the exclusion zone for an authorised person or instructed person for the electric line; and a safe system of work for the use of the operating plant is in place; and the safe system of work has been developed in consultation with persons who are broadly representative of industrial organisations of employees whose members commonly operate operating plant of the operating plant’s type; and without limiting paragraph&#160;(b) , the safe system of work ensures the device mentioned in paragraph&#160;(a) — is operating properly; and is set for at least the correct exclusion zone distance.\n(sch.2-sec.3-ssec.2) The exclusion zone for an authorised person or instructed person for the electric line applies as the exclusion zone for the operating plant for the electric line.\n- (a) operating plant, operated by an authorised person or instructed person for an electric line, is fitted with a device capable of stopping the operation of the plant immediately when the operating plant is at the exclusion zone for an authorised person or instructed person for the electric line; and\n- (b) a safe system of work for the use of the operating plant is in place; and\n- (c) the safe system of work has been developed in consultation with persons who are broadly representative of industrial organisations of employees whose members commonly operate operating plant of the operating plant’s type; and\n- (d) without limiting paragraph&#160;(b) , the safe system of work ensures the device mentioned in paragraph&#160;(a) — (i) is operating properly; and (ii) is set for at least the correct exclusion zone distance.\n- (i) is operating properly; and\n- (ii) is set for at least the correct exclusion zone distance.\n- (i) is operating properly; and\n- (ii) is set for at least the correct exclusion zone distance.","sortOrder":441},{"sectionNumber":"sch.2-pt.2","sectionType":"part","heading":"Overhead uninsulated electric lines","content":"# Overhead uninsulated electric lines","sortOrder":442},{"sectionNumber":"sch.2-pt.2-div.1","sectionType":"division","heading":"Exclusion zones for untrained persons","content":"## Exclusion zones for untrained persons","sortOrder":443},{"sectionNumber":"sch.2-pt.2-div.2","sectionType":"division","heading":"Exclusion zones for authorised or instructed persons","content":"## Exclusion zones for authorised or instructed persons","sortOrder":444},{"sectionNumber":"sch.2-pt.3","sectionType":"part","heading":"Overhead insulated electric lines","content":"# Overhead insulated electric lines","sortOrder":445},{"sectionNumber":"sch.2-pt.3-div.1","sectionType":"division","heading":"Exclusion zone for untrained persons","content":"## Exclusion zone for untrained persons","sortOrder":446},{"sectionNumber":"sch.2-pt.3-div.2","sectionType":"division","heading":"Exclusion zone for authorised or instructed persons","content":"## Exclusion zone for authorised or instructed persons","sortOrder":447},{"sectionNumber":"sch.3-pt.1","sectionType":"part","heading":"Responsible supplier’s declaration","content":"# Responsible supplier’s declaration","sortOrder":448},{"sectionNumber":"sch.3-pt.2","sectionType":"part","heading":"Responsible supplier’s level 2 in-scope electrical equipment declaration","content":"# Responsible supplier’s level 2 in-scope electrical equipment declaration","sortOrder":449},{"sectionNumber":"sch.3-pt.3","sectionType":"part","heading":"Responsible supplier’s level 3 in-scope electrical equipment declaration","content":"# Responsible supplier’s level 3 in-scope electrical equipment declaration","sortOrder":450},{"sectionNumber":"sch.6-pt.1","sectionType":"part","heading":"Preliminary","content":"# Preliminary","sortOrder":451},{"sectionNumber":"sch.6-sec.1","sectionType":"section","heading":"Definitions for schedule","content":"### sch.6-sec.1 Definitions for schedule\n\nIn this schedule—\ninsulated , for a conductor, means a conductor insulated in accordance with—\nAS/NZS 3560.1 (Electric cables—Cross-linked polyethylene insulated—Aerial bundled—For working voltages up to and including 0.6/1(1.2) kV); or\nAS/NZS 5000.1 (Electric cables—Polymeric insulated—For working voltages up to and including 0.6/1(1.2) kV).\nuninsulated , for a conductor, means a conductor other than an insulated conductor.\nunroofed pedestrian area means an unroofed terrace, balcony, sun deck, paved area or similar area that—\nis subject to pedestrian traffic only; and\nhas a surrounding hand rail or wall; and\nis an area on which a person is likely to stand.\n- (a) AS/NZS 3560.1 (Electric cables—Cross-linked polyethylene insulated—Aerial bundled—For working voltages up to and including 0.6/1(1.2) kV); or\n- (b) AS/NZS 5000.1 (Electric cables—Polymeric insulated—For working voltages up to and including 0.6/1(1.2) kV).\n- (a) is subject to pedestrian traffic only; and\n- (b) has a surrounding hand rail or wall; and\n- (c) is an area on which a person is likely to stand.","sortOrder":452},{"sectionNumber":"sch.6-sec.2","sectionType":"section","heading":"Application of vertical and horizontal clearances for particular conductors","content":"### sch.6-sec.2 Application of vertical and horizontal clearances for particular conductors\n\nThis section applies for a minimum clearance of a conductor stated in any of the following provisions of this schedule (each a prescribed clearance provision )—\npart&#160;2 , item 4;\npart&#160;3 , item 1, 2 or 5;\npart&#160;4 , item 4;\npart&#160;5 , item 1, 2 or 5.\nFor a prescribed clearance provision mentioned in subsection&#160;(1) (b) or (d) , either the vertical clearance for the conductor, or the horizontal clearance for the conductor, stated in the provision must be maintained.\nIn addition to a clearance mentioned in a prescribed clearance provision, in the zone outside the vertical alignment of a building, road cutting, embankment or similar place either of the following clearances must be maintained—\nthe horizontal clearance from the vertical alignment;\nthe vertical clearance from the horizontal level on which a person is likely to stand.\n(sch.6-sec.2-ssec.1) This section applies for a minimum clearance of a conductor stated in any of the following provisions of this schedule (each a prescribed clearance provision )— part&#160;2 , item 4; part&#160;3 , item 1, 2 or 5; part&#160;4 , item 4; part&#160;5 , item 1, 2 or 5.\n(sch.6-sec.2-ssec.2) For a prescribed clearance provision mentioned in subsection&#160;(1) (b) or (d) , either the vertical clearance for the conductor, or the horizontal clearance for the conductor, stated in the provision must be maintained.\n(sch.6-sec.2-ssec.3) In addition to a clearance mentioned in a prescribed clearance provision, in the zone outside the vertical alignment of a building, road cutting, embankment or similar place either of the following clearances must be maintained— the horizontal clearance from the vertical alignment; the vertical clearance from the horizontal level on which a person is likely to stand.\n- (a) part&#160;2 , item 4;\n- (b) part&#160;3 , item 1, 2 or 5;\n- (c) part&#160;4 , item 4;\n- (d) part&#160;5 , item 1, 2 or 5.\n- (a) the horizontal clearance from the vertical alignment;\n- (b) the vertical clearance from the horizontal level on which a person is likely to stand.","sortOrder":453},{"sectionNumber":"sch.6-pt.2","sectionType":"part","heading":"Low voltage conductor clearance—from ground","content":"# Low voltage conductor clearance—from ground","sortOrder":454},{"sectionNumber":"sch.6-pt.3","sectionType":"part","heading":"Low voltage conductor clearance—from structures","content":"# Low voltage conductor clearance—from structures","sortOrder":455},{"sectionNumber":"sch.6-pt.4","sectionType":"part","heading":"High voltage conductor clearance—from ground","content":"# High voltage conductor clearance—from ground","sortOrder":456},{"sectionNumber":"sch.6-pt.5","sectionType":"part","heading":"High voltage conductor clearance—from structures","content":"# High voltage conductor clearance—from structures","sortOrder":457},{"sectionNumber":"sch.7-pt.1","sectionType":"part","heading":"Preliminary","content":"# Preliminary","sortOrder":458},{"sectionNumber":"sch.7-sec.1","sectionType":"section","heading":"Vertical or horizontal clearance of particular service lines to be maintained","content":"### sch.7-sec.1 Vertical or horizontal clearance of particular service lines to be maintained\n\nThis section applies for a minimum clearance of a low voltage overhead service line stated in part&#160;3 , items 1 and 2 of this schedule.\nEither the vertical clearance for the service line, or the horizontal clearance for the service line, stated in the provision must be maintained.\nIn addition to a clearance for the service line mentioned in subsection&#160;(2) , in the zone outside the vertical alignment of the building or structure, either of the following clearances must be maintained—\nthe horizontal clearance from the vertical alignment;\nthe vertical clearance above the horizontal level on which a person is likely to stand.\n(sch.7-sec.1-ssec.1) This section applies for a minimum clearance of a low voltage overhead service line stated in part&#160;3 , items 1 and 2 of this schedule.\n(sch.7-sec.1-ssec.2) Either the vertical clearance for the service line, or the horizontal clearance for the service line, stated in the provision must be maintained.\n(sch.7-sec.1-ssec.3) In addition to a clearance for the service line mentioned in subsection&#160;(2) , in the zone outside the vertical alignment of the building or structure, either of the following clearances must be maintained— the horizontal clearance from the vertical alignment; the vertical clearance above the horizontal level on which a person is likely to stand.\n- (a) the horizontal clearance from the vertical alignment;\n- (b) the vertical clearance above the horizontal level on which a person is likely to stand.","sortOrder":459},{"sectionNumber":"sch.7-sec.2","sectionType":"section","heading":"Clearance does not apply to service line attached to particular part of building","content":"### sch.7-sec.2 Clearance does not apply to service line attached to particular part of building\n\nThis section applies for a minimum clearance of a low voltage overhead service line stated in part&#160;3 , items 1, 2, 4 and 5 of this schedule.\nThe minimum clearance for the service line applies to a service line that is not attached to any part of the building described in the provision.\n(sch.7-sec.2-ssec.1) This section applies for a minimum clearance of a low voltage overhead service line stated in part&#160;3 , items 1, 2, 4 and 5 of this schedule.\n(sch.7-sec.2-ssec.2) The minimum clearance for the service line applies to a service line that is not attached to any part of the building described in the provision.","sortOrder":460},{"sectionNumber":"sch.7-sec.3","sectionType":"section","heading":"Clearance does not apply to part of service line not under tension","content":"### sch.7-sec.3 Clearance does not apply to part of service line not under tension\n\nA minimum clearance stated in this schedule does not apply to a part of a low voltage service line that is not under tension.","sortOrder":461},{"sectionNumber":"sch.7-sec.4","sectionType":"section","heading":"Meaning of unroofed pedestrian area","content":"### sch.7-sec.4 Meaning of unroofed pedestrian area\n\nIn this schedule, unroofed pedestrian area has the meaning given by schedule&#160;6 , section&#160;1 .","sortOrder":462},{"sectionNumber":"sch.7-pt.2","sectionType":"part","heading":"Clearance from ground","content":"# Clearance from ground","sortOrder":463},{"sectionNumber":"sch.7-pt.3","sectionType":"part","heading":"Clearance from structures","content":"# Clearance from structures","sortOrder":464}],"analysis":{"flash_summary":{"complexity_score":9,"scope_assessment":{"changed":true,"description":"Yes. This Regulation substantially broadens the instrument from on‑site electrical safety to an integrated national product‑safety and market‑compliance regime. Examples: it creates supplier registration and labelling obligations (see sec.57: responsible supplier may register; sec.72: “must not sell… unless… registered”); a national register and compliance-folder/certificate rules for level 2/3 equipment (secs 76–78, 94); and recognition of external certification schemes (secs 96–104). It also layers in auditing, accredited auditors and mandatory annual audits for prescribed electricity entities (secs 239–240). These product‑ and audit‑focused measures extend scope beyond traditional workplace safety and into upstream supply‑chain regulation, while retaining workplace duties (e.g. risk management under sec.12 and incident notification under sec.292)."},"complexity_factors":["Very long instrument (many Parts, Divisions and Schedules — e.g. schedule references in secs 5,6,9,10)","Multiple defined-term sources (dictionary in schedule 10; words taken from wiring rules) — see sec.6","Extensive cross-references to other laws and standards (Act, WHS Regulation, AS/NZS standards, Wiring Rules) — e.g. sec.12 links to WHS Regulation, chapter 3, part 3.1","Layered product‑safety regime: registration of responsible suppliers, level 1/2/3 categories, certificates of conformity/suitability, compliance folders, national register (see pts 4 divs 1–7; secs 50–78, 83–94)","Conditional logic and exceptions throughout (many ‘does not apply if’, deferrals, transitional rules) — e.g. exclusions for mines/petroleum plants (sec.4)","Auditing and certification tracks (accredited auditors, declared external schemes) with detailed procedures and timelines — see secs 96–106, 239–240","Licensing complexity: multiple licence classes, endorsement of qualified business/technical persons, automatic suspension/cancellation rules (secs 143, 162–175)","Detailed technical compliance obligations (safety switches AS/NZS 3760 — sec.130; wiring rules compliance — secs 191–192; electrical installation/testing duties — secs 207–229)","Penalty and record‑keeping matrix: varying maximum penalties, retention periods (e.g. sec.36, sec.41(2), sec.204), and differing duties for individuals vs corporates","Extensive transitional regime moving many former provisions forward and preserving prior approvals (Part 16: secs 314–344)"],"plain_english_summary":"This Regulation bundles workplace electrical-safety duties (risk management, exclusion zones, safe work on/near energised equipment), product and supplier controls (registration, RCM marking, certificates of conformity/suitability), licensing/testing rules, distribution and generator requirements, incident notification and cathodic-protection limits. It cross‑links mandatory Australian standards (wiring rules, AS/NZS standards) and creates auditing, registration and enforcement mechanisms. Notable specific duties include owner obligations to install safety switches (see sec.28) and immediate incident notification (see sec.292). This is general legal information, not legal advice—get a qualified Australian lawyer to check before acting."}},"importantCases":[],"_links":{"self":"/api/acts/electrical-safety-regulation-2026","history":"/api/acts/electrical-safety-regulation-2026/history","analysis":"/api/acts/electrical-safety-regulation-2026/analysis","conflicts":"/api/acts/electrical-safety-regulation-2026/conflicts","importantCases":"/api/acts/electrical-safety-regulation-2026/important-cases","documents":"/api/acts/electrical-safety-regulation-2026/documents"}}